Owner’s Manual
This manual is for the installation, operation, and maintenance of the
ScaleGard ™ PLUS 2 Water Treatment Systems
STM150
TSR150
Installer please leave manual with end user.

Read, understand, and follow all safety information contained in these instructions prior to installation and use of the CUNO Foodservice STM150/TSR150 ScaleGard™ PLUS 2 Water Treatment Systems. Retain these instructions for future reference.
Intended use: The CUNO Foodservice STM150/TSR150 ScaleGard PLUS 2 water treatment systems are intended for use in fi ltering and scale reductions for water used in coffee and espresso equipment, steam kettles and tables, combis, electric and gas steamers, misters or other similar equipment, and have not been evaluated for other uses. The system is typically installed near where treated water is desired, and must be installed as specifi ed in the instal- lation instructions.



Space Requirement
11” (27.9 cm)
system.
Congratulations on your purchase of the CUNO Foodservice ScaleGard™ PLUS 2 water treatment system. The ScaleGard PLUS 2 systems utilize some of the world’s most advanced scale and corrosion control tech- nologies in a compact, highly efficient package. The ScaleGard PLUS 2 system is designed for food service equipment with low water draw such as steam kettles and tables, combis, electric and gas steamers, misters or other applications, where water consump- tion does not exceed 6 gph (22.7 lph) continuous. See estimated water production chart below.
The ScaleGard PLUS 2 STM150 is recommended where a minimal TDS level is required for proper equipment operation. The ScaleGard PLUS 2 TSR150 is recommended for applications where zero hardness is required such as proofing ovens, flash steamers, injection steamers and misters.
Before beginning the installation, take a few minutes to familiarize your- self with the system by reviewing the entire installation, operating and maintenance manual. It is also important to review the criteria below to make sure that the requirements have been or will be met when the installation is complete. Be sure to confirm that the feedwater falls within the limits shown below. If you’re not sure if this has been done, check with your distributor before installing the system. This is important because failures caused by water related problems are not covered under the system warranty.
7 3/4” (19.7 cm)
16 11/16” (42.4 cm)
Installation must comply with state and local plumbing requirements. Feedwater Parameters: Feed TDS Up to 2000 ppm (mg/L) Hardness* < 10 grains (171 mg/L) Iron (Fe) < 0.1 mg/L Hydrogen Sulfide none allowable Feed pH 4-11 Free chlorine < 2 mg/L Manganese(Mn) < 0.05 mg/L Turbidity < 5 NTU * Note: For waters over 10 grain hard, a CUNO water softener is recommended for pretreatment. Consult CUNO technical services for correct sizing. Electrical Requirements: Confirm that transformer is compatible with available electrical power supply.
Water Production (Gallons Per Hour/Liters Per Hour)

3 Feedwater Temperature (°F/°C)

. y s s A e v l a V d i o n e l o S s s a p y B
e c i v r e S o T
s s a p y B l a u n a M
) l a n o i t p O (
t e l n I
e v l a V
y l p p u S
e n i L r e t a W O R " 8 / 3
k n a T O R
r e t a W
m e t s y S O R
s u l P v e B
s m e t s y S R S T
e v l a V k c e h C
k n a T l a u n a M
e v l a V
n i a r D
n/Sample Valve i a r D k n a T
If your water analysis indicates that any of these parameters are not in range, additional pretreatment or higher frequency of maintenance may be required. Contact your distributor for assistance. The presence of silica or flocculants (e.g. alum or cationic polymers) in the feedwater can cause membrane fouling and may require special chemical pre- treatment or periodic membrane cleaning.
Plumbing Connections (not supplied)
Operating Parameters: Typical TDS Cartridge Rejection >95% Feed Temperature 40-100°F (4-38°C) Feed Pressure 20-65 psi (138-448 kPa)* Production Chart on page 3 shows output in gallons per hour at varying water temperatures. Actual output may vary according to feedwater conditions and membrane variations.
*To reduce the risk associated with property damage due to water leakage: • Do not install on systems where line pressures above 65 psi (448 kPa) may occur. Line water pressure in excess of 65 psi will re- quire installation of a pressure regulator prior to the unit.
Service Shut · Off Valve (Optional)


Drain Connection Important: An approved air gap should exist between the filter system drain lines and the drain opening to meet local plumbing codes. 1. Run a minimum 3/8” O.D. tube from the reject port to the drain. 2. The 3/8” O.D. reject tubing line may be run up to 10 ft (3 m) from the filter system to the drain. Care must be taken not to crimp or block the reject tubing line.
The water pressure in the tank will increase as the tank fills with water. When the pressure in the tank reaches approxi- mately 80 psi (552 kPa) the filter system shuts off. When water is drawn from the tank and the pressure drops to approximately 60 psi (414 kPa), the filter system will automatical- ly turn on.
Automatic Bypass Valve The auto-bypass valve has 3/8” MNPT inlet and outlet ports and a 6’ (183 cm) power cord that plugs into the filter system. This auto-bypass valve should be installed between the incoming unfiltered water line to the filter system and the water line to service after check valve. (Refer to page 4.)
Storage Tank Installation Note: Storage tanks are purchased separately. Consult the CUNO® Foodservice Price List for applicable sizes and part numbers. 1. Follow installation instructions provided with tank. 2. Check the air pressure in the tank at the valve in the top of the tank. With the tank empty, the pressure should be 20 psi (137.9 kPa). Adjust the air pressure as required. 3. Place the tank in the desired location. It should be placed in an area where it will not be bumped or jarred. 4. Connect fitting and minimum 3/8” O.D. tubing to product port of the unit. 5. Run tubing from the other side of the TEE to the check valve and on to point of use connection and bypass line. Refer to Installation Schematic on page 4. 6. Open the ball valve on the tank by turning the handle until it is parallel with the body of the valve.
If the tank pressure drops to 40 psi (276 kPa) the auto-bypass solenoid valve will open allowing unfiltered water to flow to service until tank pressure reaches approximately 60 psi (414 kPa). When the filter sys- tem is in auto-bypass the red light on the front of the bracket will come on.
Storage Tank Diameter Height Pipe Connection
2.5 gal. (9.5 lit.) 9 1/16" (23 cm) 14 1/8" (35.9 cm) 1/4" (0.6 cm)
5 gal. (19 lit.) 15 3/8" (39.1 cm) 17 3/8" (44.1 cm) 3/4" (1.9 cm)
10 gal. (38 lit.) 16" (40.6 cm) 32 1/2" (82.6 cm) 1" (2.5 cm)
20 gal. (76 lit.) 16" (40.6 cm) 57 1/2" (146.1 cm) 1" (2.5 cm)
40 gal. (151 lit.) 24" (61 cm) 56 1/2" (143.5 cm) 1 1/4" (3.2 cm)
IMPORTANT! The use of metallic piping materials for high quality water is not recommend- ed because the water is aggressive due to low TDS and pH. Plastic tubing and pipe are most suitable. Solvent bonded plastic pipe should be assembled care- fully to avoid excessive glue inside the pipe. Piping of any type should be flushed thoroughly before use. Be sure piping conforms to local plumbing codes.
Tank to Point of Use
up to 5 ft (0-1.5 m) 1/2" O.D. (1.3 cm) 3/8" (1 cm) Schedule 40 PVC
5-20 ft (1.5-6.1 m) 3/4" O.D. (1.9 cm) 1/2" (1.3 cm) Schedule 40 PVC
20-40 ft. (6.1-12.2 m) N/R 1/2" (1.3 cm) Schedule 40 PVC
40-60 ft. (12.2-18.3 m) N/R 3/4" (1.9 cm) Schedule 40 PVC
Select the tubing or pipe size that will help provide adequate flow and pressure to the point of use (i.e. Longer runs require larger tubing).
The type of tubing or pipe used must conform to local plumbing codes. Tubing or pipe used for drinking water applications must be NSF listed or made of FDA compliant materials.


1. De-pressurize the system as instructed above. 2. Locate the TDS reduction filter. To remove the TDS reduction filter, turn to the left 1/4 turn. Pull down to remove. 3. Disconnect reject tubing by pushing in the white collet on plastic fitting to release the tubing (see page 9). Discard the used cartridge. 4. Remove the plug from the plastic fitting on the new cartridge and connect the reject tubing. 5. Insert the new filter by aligning the tabs with the filter head. Push up to insert and turn to the right 1/4 turn. Note: The first full tank of water filtered after the filter is replaced should be discarded. See start-up procedure, page 7.

‘Push-In’ Tubing Connector (John Guest® Fitting) This product is outfitted with user friendly “Push In” connectors. Proper use of the connectors is shown in the diagrams. It is most important that the tubing selected for use with these connectors be of high quality, exact size and roundness, and with no surface nicks or scratches. If it is neces- sary to cut the tubing, use a plastic tubing cutter or sharp razor knife. Make a clean square cut. Should a leak occur at a ‘Push In’ connector, the cause is usually defective tubing.
Push tubing straight in as far as it will go.
Tubing is secured in.
Push in grey collet to release tubing.
Pull tubing straight out.







CUNO Incorporated warrants the original purchaser-con- sumer of its Product that is free of defects in materials and workmanship. Any defect, malfunction, or other failure of the Product to conform to this warranty will be remedied by CUNO in the manner provided below. This Warranty, together with any warranties implied by law, shall be limited to a duration of two (2) years from the original date of purchase by the consumer. This Warranty does not apply to defects that result from abuse, misuse, alteration or damage not caused by CUNO. IMPORTANT: To file a claim under this warranty you must complete and mail the Warranty Registration Card supplied with this product to CUNO at the address below within ten (10) days of original purchase date. THIS WARRANTY DOES NOT COVER, AND IS INTENDED TO EXCLUDE ANY LIABILITY ON THE PART OF CUNO, WHETHER UNDER THIS WARRANTY OR UNDER ANY WARRANTY IMPLIED BY LAW, FOR ANY INDIRECT OR CONSEQUENTIAL DAMAGES FOR BREACH HEREOF OR THEREOF. Note: Some states prohibit limitations on the duration of implied warranties and on the exclusion of indirect or conse- quential damages; and so the limitation on implied warranties and on incidental and consequential damages may not be appli- cable to you. RESPONSIBILITY OF CUNO CUNO’s responsibility under this warranty shall be to repair at its expense, at no charge to the original purchaser-consumer, any product that is actually defective, malfunctioning, or oth- erwise in violation of this warranty. If CUNO for any reason cannot repair a Product covered hereby within two (2) weeks after receipt of the original purchaser-consumer’s notification of a Warranty claim, then CUNO’s responsibility shall be, at its option, either to replace the defective Product with a compa-
rable new unit at no charge to the consumer or to refund the full purchase price. CUNO’s obligations of repair, replacement, or refund are conditioned upon return of the defective Product to CUNO. If any Product covered hereby is actually defective within the terms of this Warranty, then CUNO will bear all the reasonable and proper shipping and mailing charges actually incurred in the consumer’s return of the Product set forth herein. If the Product proves not to be defective within the terms of this Warranty, then all costs and expenses in connection with the processing of the consumer’s claim hereunder shall be borne by the consumer.
RESPONSIBILITY OF THE CONSUMER The original purchaser-consumer’s sole responsibility in the instance of a warranty claim shall be to notify CUNO of the defect, malfunction, or other manner in which the terms of this Warranty are violated. You may secure performance of obliga- tions hereunder by (in writing): 1. Identifying the Product involved (by model or serial number or other sufficient description that will allow CUNO to determine which product is defective). 2. Specifying where, when, and from whom the Product was purchased. 3. Describing the nature of the defect, malfunction, or other violation of this Warranty. 4. Sending such notification together with the defective Product and $5.00 check or money order to cover postage and handling to:
CUNO Incorporated, 400 Research Parkway, Meriden, Connecticut 06450, USA
THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS, AND YOU MAY ALSO HAVE OTHER RIGHTS, WHICH VARY FROM STATE TO STATE
400 Research Parkway Meriden, CT 06450, USA Toll Free: 1-888-218-CUNO
CUNO and ScaleGard are trademarks of 3M Company used under license. John Guest is a trademark of John Guest International Limited.
© 2007 3M Company. All rights reserved.
a 3M company