Instructions SC & FC/PC3 Pull-Proof Fiber Optic Connectors T ermination Procedures for Single-mode and Multimode Field-Mountable Connectors using Epoxy Issue 1, May 1993.
2 Contents: A) W arnings, Recommendations and Overview ................................................................................................ 3 B) Jacketed Cable Preparation ...................................................................
3 SECTION A Warnings, Recommendations and Overview 1. Most fibers can be mechanically stripped without the aid of chemicals or heat. If the fiber is not mechanically strippable, contact 3M's Training Department or the cable manufacturer for their recommendations.
4 (A) - Strain Relief Boot (B) - Crimp Ring (C) - Connector (D) - Housing SECTION A Warnings, Recommendations and Overview This manual is for terminating the following field mountable connectors: Iden.
5 Fig. B1 SECTION B Jacketed Cable Preparation This section is for mounting the 3M brand SC and FC/PC3 field- mountable connectors on 2.4 mm cable and 3.0 mm cable. The process for mounting on 900 ϑ m buf fered fiber can be found in Section H. 1. TURN THE OVEN ON When the oven is heated to the proper temperature the heater light will go of f.
6 SECTION B Jacketed Cable Preparation 5. SLIP THE STRAIN RELIEF BOOT AND THE CORRECT CRIMP RING ONT O THE CABLE DO NOT FORGET T O DO THIS STEP . The boot will not fit over a mounted connector assembly so it is essential that it be slipped onto the cable at this time.
7 SECTION B Jacketed Cable Preparation 9. BUFFER REMOV AL With the modified No-Nik tool's arrow pointing in the direction of the stripping, remove the fiber's buffer in small bites, about 3/16" (5 mm). Be sure to remove the stripped material from the tool after each incremental cut.
8 SECTION C Mounting 1. INSPECT THE CONNECT OR Before mounting, hold the connector up to a light to ensure that the capillary hole of the ceramic ferrule is clear . If the hole is obstructed, blow it clear with air or use a piece of stainless steel wire supplied with the kit.
9 Fig. C5 Fig. C6 Fig. C7 SECTION C Mounting 4. PREP ARE THE SYRINGE AND EPOXY Remove the plunger and protective cap from the syringe and place both parts on a clean convenient surface along with the dispensing tip. The epoxy supplied has been specifically designed for use with fiber optic connectors and is packaged in premeasured 2 gram bi-packs.
10 Fig. C8 Fig. C9 Fig. C10 Fig. C11 SECTION C Mounting 8. THREAD THE CONNECTOR ONT O THE FIBER Slide the crimp ring up the cable within 1/2" (13 mm) of the end of the jacket. Hold the cable in one hand directly behind the crimp ring and hold the connector in the other hand.
11 Fig. C12 Fig. C13 SECTION C Mounting 1 1. SECURE THE STRAIN RELIEF BOOT Use the syringe to apply two dabs of epoxy onto the larger half of the crimp ring (Fig. C12). While holding the load adapter , slide the boot up over the crimp ring and rotate it to evenly distribute the epoxy .
12 SECTION D Scoring 1. CAREFULL Y REMOVE THE LOAD ADAPTER 2. SCORE THE FIBER Hold the connector in a vertical position with the fiber pointing upward. Score the fiber by drawing the scoring blade lightly against the fiber , just above the epoxy bead (Fig.
13 SECTION E Standard Polishing Process for Single-mode and Multimode Connectors (>30dB) Note: See Section F to achieve >40 dB Return Loss. 1. PREP ARE THE 5 ϑ m POLISHING SURF ACE Clean the surface of the soft polishing pad with a lint-free cloth dampened with isopropyl alcohol.
14 SECTION E Standard Polishing Process for Single-mode and Multimode Connectors 3. PERFORM THE 5 ϑ m FINISH While holding the polishing jig in your hand, insert the connector so that the ferrule end does not protrude past the bottom of the polishing jig.
15 SECTION E Standard Polishing Process for Single-mode and Multimode Connectors 4. PREP ARE T O PERFORM THE 1 ϑ m FINISH Using an isopropyl alcohol dampened lint-free cloth, clean the ferrule, the polishing jig, and the 5 ϑ m lapping acetate. Blow all pieces dry with compressed air .
16 SECTION F Polishing Process for Single-mode Connector Return Loss >40dB This process will need to be used for single-mode finishes with a reflection requirement of 40dB or better . This specification is outlined in Bellcore TR-NWT-00326 Issue 3.
17 SECTION F Polishing Process for Single-mode Connector Return Loss >40dB 4. PERFORM THE 5 ϑ m FINISH While holding the polishing jig in your hand, insert the connector so that the ferrule end does not protrude past the bottom of the polishing jig.
18 SECTION F Polishing Process for Single-mode Connector Return Loss >40dB 6. PERFORM THE 1.5 ϑ m FINISH Insert the ferrule into the jig and lower it gently onto the 1.5 ϑ m acetate. Using medium pressure (equivalent to 1 lb of force), perform four figure 8 strokes.
19 SECTION F Polishing Process for Single-mode Connector Return Loss >40dB 7. PREP ARE TO PERFORM THE FINAL POLISH Using an isopropyl alcohol dampened lint-free cloth, clean the ferrule and the polishing jig. Clean a sheet of the final polishing film and place it shiny side down onto the clean polishing pad.
20 SECTION G Final Cleaning 1. BLOW THE DUST CAP WITH COMPRESSED AIR 2. WIPE THE CERAMIC FERRULE WITH AN ISOPROPYL ALCOHOL DAMPENED LINT-FREE CLOTH (Fig.
21 SECTION H Mounting Unjacketed/900 m Buffered Fiber 7. THREAD THE CONNECTOR ONT O THE FIBER Slide the strain relief tube with the crimp ring within 1/2" (13 mm) of the buffer .
22 SECTION I Connector Assembly and Installation 1. CONNECT OR ASSEMBL Y Once the SC connector has been mounted and polished, the housing can be installed onto the body . A. Standard Density Applications While holding the connector firmly by the boot, align the chamfers on both the connector and housing and snap into place (Fig.
23 SECTION I Connector Assembly and Installation Fig. I5 Fig. I6 4. SC CONNECTOR - HIGH DENSITY MA TING Installation A. Clean the connector and coupling as described above. B. Hold the connector by the boot. C. Align the connector chamfers with the coupling (Fig.
Litho in U.S.A. 3M Telecom Systems Group Important Notice All statements, technical information and recommendations related to the Seller's products are based on information believed to be reliable, but the accuracy or completeness thereof is not guaranteed.
An important point after buying a device 3M PC3 (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought 3M PC3 yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data 3M PC3 - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, 3M PC3 you will learn all the available features of the product, as well as information on its operation. The information that you get 3M PC3 will certainly help you make a decision on the purchase.
If you already are a holder of 3M PC3, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime 3M PC3.
However, one of the most important roles played by the user manual is to help in solving problems with 3M PC3. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device 3M PC3 along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center