Line Interactive Sinewave UPS 800 /1.1 K/ 1.5 K/ 2K/2.5K/3K VA Uninterruptible P ower Supply S ystem User Manual.
1 T able of Contents 1. Important Safety Warning……………… ………… …………………… 2 1-1. T r ansportati on 2 1-2. Prepar ation 2 1-3. Installation 2 1-4. O perati on 2 1-5. Maintenanc e, Service And F aults 3 2. Installa tion And S etup……… …………… …………………… ………… 4 2-1.
2 1. Importan t Safety Warnin g Please comply with all warnings and operatin g instructions in this manual strictly. Save this manual pro perly and read carefully the following instructions bef ore installing the unit. Do not operate this unit before reading through all safety information and operating instructions carefully 1-1.
3 1-5. Maintenance, Service And Faults The UPS system operates with hazardous voltages. R epairs may be carried out only by qualified maintenance personnel.
4 2. Installation An d Setup NOTE: Before installation, please inspect t he unit. Be sure that nothing inside the package is damaged. Please keep t he original package in a safe p lace for future use. 2-1 . Rear Panel View 800 /1. 1K /1.5K/2K IEC Type 2.
5 2-2. Install The UPS F or safety consider ation, the UPS is shipped out from fact ory without connecting battery wires. Before install the UPS, p lease follow below steps to re -connect battery wires f irst. Step 1 Step 2 Step 3 R emove front pa ne l.
6 Step 3: Communication connection Communication ports: USB port RS -232 port Intelligent slot T o allow for unattended UPS shutdo wn/start-up and status monitoring, connect the communication cable one end to the USB/RS- 232 port a nd the other to the communication port of your PC.
7 Step 7: Turn on the UPS Press the ON/Mute button on the front panel for two seconds to power on t he UPS. Note: The battery charges fully during the first five hours of normal operat ion. Do not expect full battery run capability during this initial charge p eriod.
8 2-5 Battery Kit Assembly ( option) NOTICE: Please assemble battery kit f irst before installing it inside of UPS. Please select correct batt ery kit procedure below to assemble it. 2-battery kit Step 1: R e mov e adhesive tapes. Step 2: Connect all battery terminals b y following below chart.
9 6-battery kit Step 1: R e mov e adhesive tapes. Step 2: Connect all battery terminals b y following below chart. Step 3: Put assembled battery packs on one side of plastic shells. Step 4: Co ver the other side of plastic shell as below chart. Then, battery kit is assembly well.
10 3. Operations 3-1. Button Operation Button Function ON/MUTE Button Turn on the UPS: Press and hold ON/Mute button for at least 2 seconds to turn on the UPS. Mute the alarm: After the UPS is turned on in battery mode, press and hold this button for at least 5 seconds to disable or ena ble the alarm system.
11 Display Function Backup time information Indicates the backup time in pie chart. Indicates the backup time in numbers. H: hours, M: minute Warning & Fault information Indicates that the warning and fault occurs. Indicates the warning and fault codes, a nd the codes are listed in details in 3-5 section.
12 3-4. LCD Display Wordings Index Abbreviation Display content Meaning ENA Enable DIS Disable ESC Escape EP EPO FA F an TP T emperat ure CH Charger RAC Rack displa y T OE T ower display SF Site F ault 3-5. UPS Setting There are two p ar ameters to set up the UPS.
13 03: Progr ammable outlets setting Interface Setting Setting the backup time limits in minutes from 0-999 for programmable outlets which connect to non-critical devices on battery mode. 04 : LCD display direction set ting Interface Setting RAC: the LCD d isplay is horizontal.
14 Step 4: Press the “ Up “ butt on (ON/MUTE) again to switch to "03" of progr am lis t . Then press “E nter “ button for setting progra mmable outlet time. P us h “Up” button to change the value of backup time according your demand.
15 Operating mode Description LCD display Standby mode UPS is powered off and no output supply power, but still can charge batteries. 3-7. Faults Reference Code F ault event F ault code Icon F ault ev.
16 4. Troubleshoo ting If the UPS system does not oper ate correctly , please solve the problem by using the ta ble be low . Symptom Possible cause Remedy No indication and alarm even though the mains is normal. The AC input power is not connected well.
17 Sy mptom Possible cause Remedy F ault code is shown as 1, 2, 3, 4, 11, 12, 13 and 41 on L CD display and alarm is continuously sounding. A UPS internal fault has occurred. Contact your dealer Battery backup time is shorter than nominal v alue Batteries are not fully charged Charge the bat teries for at least 5 hours and then check capacity .
18 5. Storage and M aintenance 5-1. Operation The UPS s ystem contains no use r-se rviceable parts. If the battery service lif e (3~5 years at 25°C ambient temperature) has been exceeded, the b atteries must be replaced. In t his case, please contact your dealer.
19 MODEL 800 1.1K(L) 1.5K 2K (L) 2. 5K 3K (L) CAPAC ITY 800 VA / 640 W 1100 VA / 880 W 1500 VA / 1200 W 2000 VA / 1600 W 2500 VA / 2000 W 3000 VA / 2400 W INPUT Acceptable Vol tage Range 81 -145 VAC o.
An important point after buying a device East EA300PRO-800 (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought East EA300PRO-800 yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data East EA300PRO-800 - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, East EA300PRO-800 you will learn all the available features of the product, as well as information on its operation. The information that you get East EA300PRO-800 will certainly help you make a decision on the purchase.
If you already are a holder of East EA300PRO-800, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime East EA300PRO-800.
However, one of the most important roles played by the user manual is to help in solving problems with East EA300PRO-800. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device East EA300PRO-800 along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center