EN
Dimplex logo
Official user manual

Dimplex S1 7KS

24 pages·2 MB·Heat Pump·PDF·ENDEFRITNLJA
Dimplex S1 7KS
Table of Contents 80 sections CE · INSTALLATION and OPERATING INSTRUCTIONS · Brine-to-Water Heat Pump · for Indoor Installation · … ShowHide
CEp.1INSTALLATION and OPERATING INSTRUCTIONSp.1Brine-to-Water Heat Pumpp.1for Indoor Installationp.1SI 11KS SI 14KS SI 7KS SI 9KSp.1Order No.: 452231.67.01 FD 8504p.1CONTENTSp.21 PLEASE READ IMMEDIATELY 3p.22 PURPOSE OF THE HEAT PUMP 4p.23 BASELINE UNIT 4p.24 ACCESSORIES 5p.25 TRANSPORT 5p.26 INSTALLATION 6p.27 MOUNTING 6/7p.28 COMMISSIONING 8p.29 CARE/CLEANING 8/9p.210 MALFUNCTIONS/TROUBLESHOOTING 9p.211 DECOMMISSIONING 9p.212 APPENDIX 10p.2PLEASE READ IMMEDIATELYp.3READ IMMEDIATELYp.3CAUTION!p.31.1 Important Informationp.31.2 Legal Provisions and Directivesp.31.3 Energy-Efficient Use of the Heat Pumpp.3PURPOSE OF HEAT PUMP BASELINE UNITp.4PURPOSE OF THE HEAT PUMPp.4BASELINE UNITp.42.1 Applicationp.42.2 Principle of Operationp.4ACCESSORIESp.5TRANSPORTp.55 4 ACCESSORIESp.54.1 Brine Manifoldp.54.2 Brine Pressostatp.5INSTALLATION MOUNTINGp.6INSTALLATIONp.6MOUNTINGp.66.1 General Informationp.67.1 Generalp.67.2 Heating-Side Connectionp.66.2 Sound Emissionsp.67.4 Electrical Connectionp.7COMMISSIONING CARE/CLEANINGp.8COMMISSIONINGp.88.1 Generalp.88.2 Preparatory Stepsp.8CARE/CLEANINGp.89.1 Carep.88.3 Commissioning Procedurep.89.2 Cleaning of Heating Sidep.8CARE/CLEANING MALFUNCTIONS/TROUBLESHOOTINGp.9DECOMMISSIONINGp.9MALFUNCTIONS/ TROUBLESHOOTINGp.911.1 Shutdown in Summerp.911.2 End-of-Life Decommissioning/ Disposalp.99.3 Cleaning of Heat Source Sidep.9APPENDIXp.10APPENDIX 12p.1012.1 DIMENSIONED DRAWING 11p.1012.2 EQUIPMENT DATA 12p.1012.5 HYDR. BLOCK DIAGRAM 21p.1012.6 EC DECLARATION OF CONFORMITY 22p.1012.7 WARRANTY CERTIFICATE/ AFTER-SALES SERVICE 23p.10APPENDIX: 12.1 DIMENSIONED DRAWINGp.11Dimensioned Drawingp.11APPENDIX: 12.2 EQUIPMENT DATAp.12Equipment Datap.12APPENDIX: 12.3 SCHEMATICSp.1312.3.1 Characteristics .. 7KSp.1312.3.2 Characteristics .. 9KSp.1412.3.3 Characteristics .. 11KSp.1512.3.4 Characteristics .. 14KSp.16APPENDIX: 12.4 WIRING DIAGRAMSp.1712.4.1 Control .. 7KS to .. 14KSp.1712.4.2 Load .. 7KS to .. 14KSp.1812.4.3 Terminal Diagram .. 7KS to .. 14KSp.1912.4.4 Legend .. 7KS to .. 14KSp.20APPENDIX: 12.5 HYDRAULIC BLOCK DIAGRAMp.21Hydraulic Block Diagramp.21
Page 1 of the Dimplex S1 7KS user manual — CE
Page 1 · click to enlarge
Page 1

CE

INSTALLATION and OPERATING INSTRUCTIONS

Brine-to-Water Heat Pump

for Indoor Installation

SI 11KS SI 14KS SI 7KS SI 9KS

Order No.: 452231.67.01 FD 8504

Page 2 of the Dimplex S1 7KS user manual — Table of Contents
Page 2 · Contents
Contents

Contents

CEp.1INSTALLATION and OPERATING INSTRUCTIONSp.1Brine-to-Water Heat Pumpp.1for Indoor Installationp.1SI 11KS SI 14KS SI 7KS SI 9KSp.1Order No.: 452231.67.01 FD 8504p.1CONTENTSp.21 PLEASE READ IMMEDIATELY 3p.22 PURPOSE OF THE HEAT PUMP 4p.23 BASELINE UNIT 4p.24 ACCESSORIES 5p.25 TRANSPORT 5p.26 INSTALLATION 6p.27 MOUNTING 6/7p.28 COMMISSIONING 8p.29 CARE/CLEANING 8/9p.210 MALFUNCTIONS/TROUBLESHOOTING 9p.211 DECOMMISSIONING 9p.212 APPENDIX 10p.2PLEASE READ IMMEDIATELYp.3READ IMMEDIATELYp.3CAUTION!p.31.1 Important Informationp.31.2 Legal Provisions and Directivesp.31.3 Energy-Efficient Use of the Heat Pumpp.3PURPOSE OF HEAT PUMP BASELINE UNITp.4PURPOSE OF THE HEAT PUMPp.4BASELINE UNITp.42.1 Applicationp.42.2 Principle of Operationp.4ACCESSORIESp.5TRANSPORTp.55 4 ACCESSORIESp.54.1 Brine Manifoldp.54.2 Brine Pressostatp.5INSTALLATION MOUNTINGp.6INSTALLATIONp.6MOUNTINGp.66.1 General Informationp.67.1 Generalp.67.2 Heating-Side Connectionp.66.2 Sound Emissionsp.67.4 Electrical Connectionp.7COMMISSIONING CARE/CLEANINGp.8COMMISSIONINGp.88.1 Generalp.88.2 Preparatory Stepsp.8CARE/CLEANINGp.89.1 Carep.88.3 Commissioning Procedurep.89.2 Cleaning of Heating Sidep.8CARE/CLEANING MALFUNCTIONS/TROUBLESHOOTINGp.9DECOMMISSIONINGp.9MALFUNCTIONS/ TROUBLESHOOTINGp.911.1 Shutdown in Summerp.911.2 End-of-Life Decommissioning/ Disposalp.99.3 Cleaning of Heat Source Sidep.9APPENDIXp.10APPENDIX 12p.1012.1 DIMENSIONED DRAWING 11p.1012.2 EQUIPMENT DATA 12p.1012.5 HYDR. BLOCK DIAGRAM 21p.1012.6 EC DECLARATION OF CONFORMITY 22p.1012.7 WARRANTY CERTIFICATE/ AFTER-SALES SERVICE 23p.10APPENDIX: 12.1 DIMENSIONED DRAWINGp.11Dimensioned Drawingp.11APPENDIX: 12.2 EQUIPMENT DATAp.12Equipment Datap.12APPENDIX: 12.3 SCHEMATICSp.1312.3.1 Characteristics .. 7KSp.1312.3.2 Characteristics .. 9KSp.1412.3.3 Characteristics .. 11KSp.1512.3.4 Characteristics .. 14KSp.16APPENDIX: 12.4 WIRING DIAGRAMSp.1712.4.1 Control .. 7KS to .. 14KSp.1712.4.2 Load .. 7KS to .. 14KSp.1812.4.3 Terminal Diagram .. 7KS to .. 14KSp.1912.4.4 Legend .. 7KS to .. 14KSp.20APPENDIX: 12.5 HYDRAULIC BLOCK DIAGRAMp.21Hydraulic Block Diagramp.21
Page 3 of the Dimplex S1 7KS user manual — CAUTION!
Page 3 · click to enlarge
Page 3

PLEASE READ IMMEDIATELY

READ IMMEDIATELY

CAUTION!

The supplied strainer is to be fitted in the heat source inlet of the heat pump in order to protect the evaporator against contamination.

1.1 Important Information

CAUTION!

The heat pump is not secured to the wooden pallet.

CAUTION!

Any work on the heat pump may only be performed by authorised and qualified customer service agents.

CAUTION!

The heat pump must not be tilted more than max. 45° (in either direction).

CAUTION!

Do not lift unit by the holes in the panel assemblies!

1.2 Legal Provisions and Directives

This heat pump conforms to all relevant DIN/VDE regulations and EU directives. For details refer to the EC Declaration of Conformity in the appendix.

CAUTION!

In the case of large-capacity heating circuits, the installed expansion vessel (24 litres, 1.0 bar admission pressure) must be supplemented by an additional vessel.

The electrical connection of the heat pump must be performed according to and conforming with all re- levant VDE, EN and IEC standards. Beyond that, the connection requirements of the local utility compa- nies have to be observed.

CAUTION!

The brine solution must contain at least 25 % of an antifreeze and corrosion protection agent on a monoethylene glycol or propylene glycol basis.

The heat pump is to be connected to the heat source and heat distribution systems in accordance with all applicable provisions.

CAUTION!

On connecting the electrical load lines, the clockwise phase sequence must be observed (in the case of an incorrect phase sequence the heat pump will deliver no output and generate a lot of noise).

1.3 Energy-Efficient Use of the Heat Pump

By operating this heat pump you contribute to the protection of our environment. A prerequisite for an efficient operation is the proper design and sizing of the heating system and the heat source system. In particular, it is important to keep water flow temperatures as low as possible. All energy consumers connected should therefore be suitable for low flow temperatures. A 1 K higher heating water temperature corresponds to an increase in power consumption of approx. 2.5 %. Underfloor heating systems with flow temperatures between 30 °C and 40 °C are optimally suited for energy-efficient operation.

CAUTION!

Commissioning of the heat pump must be performed in accordance with the installation and operating manual of the heat pump controller.

CAUTION!

Caution - Heating Contractors ! Depending on the filling water quality and quantity, in particular in the case of mixed installations and plastic pipes, mineral deposits (rust sludge, lime) may form, impairing the pro- per functioning of the heating installation. A reason for this is the water hardness and oxygen dissolved in the filling water as well as additional oxygen from the air, which may penetrate via valves, fittings and plastic pipes (oxygen diffusion). As a preventive measure it is recommended that a physical water conditio- ner such as ELYSATOR be used.

Page 4 of the Dimplex S1 7KS user manual — 2.2 Principle of Operation
Page 4 · click to enlarge
Page 4

PURPOSE OF HEAT PUMP BASELINE UNIT

PURPOSE OF THE HEAT PUMP

BASELINE UNIT

The baseline unit consists of a heat pump of compact design, ready for connection. In addition to the control panel with integrated controller, the unit also contains essential components of the heating and brine circuits:

2.1 Application

The brine-to-water heat pump is designed for use in existing or newly built heating systems. Brine is used as the heat carrier in the heat source system. Ground coils, ground collectors or similar systems can be used as the heat source.

- expansion vessels - circulating pumps - pressure relief valves - pressure gauges - overflow valve (heating circuit)

2.2 Principle of Operation

The refrigeration cycle contains the refrigerant R407C. Refrigerant R407C is CFC-free, non-ozone depleting and non-combustible.

The heat generated by the sun, wind and rain is stored in the ground. This heat stored in the ground is collected at low temperature by the brine circulating in the ground collector, ground coil or similar device. A circulating pump then conveys the warmed brine to the evaporator of the heat pump. There, the heat is given off to the refrigerant in the refrigeration cycle. When so doing, the brine cools so that it can again take up heat energy in the brine circuit.

All components required for the operation of the heat pump are provided on the control panel. The power feed for load and control current must be field- installed by the customer.

The collector loops including brine manifold must be provided by the customer.

The refrigerant, however, is drawn in by the electrically driven compressor, is compressed and "pumped" to a higher temperature level. The electrical power needed to run the compressor is not lost in this process, but most of the generated heat is trans- ferred to the refrigerant as well.

Dimplex S1 7KS — 2.2 Principle of Operation diagram (page 4)
Fig. 1 · 2.2 Principle of Operation

Subsequently, the refrigerant is passed through the condenser where it transfers its heat energy to the heating water. Based on the thermostat setting, the heating water is thus heated to up to 55 °C.

3 4 5 6

1. Control panel 4) Compressor 2) Circulating pumps 5) Evaporator 3) Condenser 6) Expansion vessel
Page 5 of the Dimplex S1 7KS user manual — CAUTION!
Page 5 · click to enlarge
Page 5

ACCESSORIES

TRANSPORT

5 4 ACCESSORIES

TRANSPORT

4.1 Brine Manifold

A lift truck is suited for transporting the unit on a level surface. If the heat pump needs to be transported on an uneven surface or carried up or down stairs, carrying straps may be used for this type of transport. These straps may be passed directly underneath the wooden pallet.

The brine manifold ties the individual collector loops of the heat source system into a single main line which is connected to the heat pump. Integrated ball valves allow individual brine circuits to be shut off for venting purposes.

CAUTION!

The heat pump is not secured to the wooden pallet.

CAUTION!

4.2 Brine Pressostat

The heat pump must not be tilted more than max. 45° (in either direction).

Where this is a legal requirement, a low-pressure brine pressostat may be installed in the unit. In this case, the connection provided above the brine expansion vessel should be used.

For lifting the unit without pallet, the holes provided in the sides of the frame should be used. The side panel assemblies must be removed for this purpose. A commercially available pipe can be used as a carrying aid.

CAUTION!

Do not use the holes in the panel assemblies for lifting the unit!

Page 6 of the Dimplex S1 7KS user manual — 6.2 Sound Emissions
Page 6 · click to enlarge
Page 6

INSTALLATION MOUNTING

INSTALLATION

MOUNTING

6.1 General Information

7.1 General

As a rule, the unit must be installed indoors on a level, smooth and horizontal surface. The entire base frame should thereby make close contact with the surface in order to ensure adequate sound insulation. Failing this, additional sound insulation measures may become necessary.

The following connections need to be established on the heat pump:

- supply/return flow of the brine system - supply/return flow of the space heating and

water heating system - common return of space heating and water

The heat pump should be located to allow safe and easy maintenance/service access. This is ensured if a clearance of approx. 1 m in front of and to each side of the heat pump is maintained.

heating system - return, overflow valve - connection for additional expansion vessel

(as required) - drain lines of overflow valves - condensate drain - power supply

7.2 Heating-Side Connection

The heat pump features separate outlets for the space heating and water heating circuit.

In cases where the heat pump has no water heating mode, the hot water outlet has to be permanently sealed.

Prior to establishing the heat pump connections on the heating water side, the heating installation must be flushed in order to remove any impurities that may be present , as well as residues of sealing material, or the like. Any accumulation of deposits in the condenser may result in a total failure of the heat pump.

6.2 Sound Emissions

The heat pump offers silent operation due to efficient sound insulation. Noise transmission to the foundation or the heating system is largely prevented by internal decoupling measures.

In systems equipped with heating water flow shut- off devices such as radiator or thermostat valves, an overflow valve is installed. This assures a minimum heating water flow through the heat pump and prevents any malfunctions for occurring.

Once the installation on the heating side has been completed, the heating system must be filled, deaerated and pressure-tested.

Frost Protection for Installations Prone to Frost Provided the controller and the heating circulating pumps are ready for operation, the frost protection function of the controller is always activated. If the heat pump is taken out of service or in the event of a power failure, the system must be drained. In heat

Page 7 of the Dimplex S1 7KS user manual — CAUTION!
Page 7 · click to enlarge
Page 7

MOUNTING

pump installations where a power failure cannot readily be detected (e.g. holiday houses), the heating circuit must contain a suitable antifreeze product.

7.4 Electrical Connection

The following electrical connections must be established on the heat pump.

The integrated expansion vessel has a capacity of 24 litres.This capacity is appropriate for buildings with a heated living space floor area of up to 200 m2.

- Connection of the load wire to the control panel of the heat pump.

- Connection of the control voltage wire to the control panel of the heat pump.

The planner of the heating system should verify that the capacity of the expansion vessel is adequate. An additional expansion vessel may have to be installed, if required (as per DIN 4751 Part 1). Charts in manufacturer catalogues facilitate the proper selection of the proper size according to the amount of water in the system.

All electrical components required for the operation of the heat pump are located on the control panel..

For detailed instructions concerning the connection of external components and the operation of the heat pump controller refer to the heat pump terminal dia- gram and the operating manual of the controller.

CAUTION!

With large-capacity heating circuits, the installed expansion vessel (24 litres, 1.0 bar admission pressure) must be supplemented by an additional vessel.

Connection of the load wire to the control panel via terminals X1: L1/L2/L3/PE.

7.3 Connection on Heat Source Side The following procedure must be observed when making the connection: Connect the brine line to the flow and return pipe of the heat pump. The supplied strainer and vent must be field-installed in the brine inlet of the heat pump. The powerful vent must be installed at the highest point of the heat source system CAU The hydraulic block schematic must be taken into account when so doing. The brine liquid must be produced prior to charging the system. The brine concentration must be at least 25 %. Freeze protection down to -14 °C can thus be ensured. Only antifreeze agents on a monoethylene glycol or propylene glycol basis are to be used. The heat source system has to be vented and leaktested. UTION! The brine solution must contain at least 25 % of an antifreeze and corrosion protection agent on a monoethylene glycol or propylene glycol basis.conductors must be provided . The required crosssectional area of the conductor is to be selected according to the power consumption of the heat pump, the technical connection requirements of the relevant utility company and all applicable regulations. Power consumption data of the heat pump is provided in the product literature and on the nameplate. The terminals are designed for a max. conductor cross-section of 10 mm˝. TION! The clockwise phase sequence must be observed when connecting the electric load lines (in the case of an incorrect phase sequence the heat pump will deliver no output and generate a lot of noise). Connection of the control voltage wire is effected via terminals X1: L/N/PE. If a more powerful brine pump is required than the one integrated, a motor contactor and an appropriate motor protecting switch need to be installed. The contactor must be connected to the terminals of the internal brine pump (controller terminals J12/N03 and X1-N). The power supply of the larger pump must be provided by the mains supply. CAUTION!
Page 8 of the Dimplex S1 7KS user manual — 9.2 Cleaning of Heating Side
Page 8 · click to enlarge
Page 8

COMMISSIONING CARE/CLEANING

COMMISSIONING

Close all of the heating circuits that may also be closed during operation (depending on the type of heat pump usage) so that the least favourable operating state - with respect to the water flow rate - is achieved. Normally, these are the heating circuits of the rooms located on the south and west sides of buildings. At least one heating circuit must remain open (e.g. bathroom).

8.1 General

To ensure proper commissioning it should be carried out by an after-sales service authorised by the manufacturer. Only then can an extended warranty period of 3 years in total be granted (cf. Warranty service).

The overflow valve is to be opened to such an extent that based on the current heat source tem- perature the maximum temperature difference between heating supply and return flow tem- perature is obtained, as indicated in the table below. The temperature difference should be measured as closely to the heat pump as possible. In mono-energetic systems, the electric heating element is to be deactivated.

8.2 Preparatory Steps

Prior to commissioning, the following items need to be checked:

Heat source temperature from tomax. difference between heating supply and return temperature -5 °C0 °C10 K 1 °C5 °C11 K 6 °C9 °C12 K 10 °C14 °C13 K 15 °C20 °C14 K 21 °C25 °C15 K

- All connections of the heat pump must have been made as described in Chapter 7.

- The heat source system and the heating circuit must be filled and tested.

- Strainer and vent must be fitted in the brine inlet of the heat pump.

Any malfunctions occurring during operation are indicated on the display of the heat pump controller and can be corrected as described in the operating manual of the heat pump controller.

- All valves that could impair the proper water flow must be open in the brine and heating circuits.

- The heat pump controller must be adapted to the heating installation in accordance with the instructions contained in its operating manual.

CARE/CLEANING

- Proper condensate drainage must be ensured.

9.1 Care

- Drainage of the liquid emerging from the brine and heating water overflow valves must be ensured.

The heat pump is designed for maintenance-free operation. To prevent operating malfunctions caused by dirt deposits in the heat exchangers, care must be taken that no contamination whatsoever can enter the heat source and heating systems. In the event that operating malfunctions due to contamination occur nevertheless, the system should be cleaned as described below.

8.3 Commissioning Procedure

The start-up of the heat pump is effected via the heat pump controller.

CAUTION!

9.2 Cleaning of Heating Side

Commissioning of the heat pump must be carried out in accordance with the installation and operating manual of the heat pump controller.

The ingress of oxygen into the heating water circuit may result in the formation of oxidation products (rust). It is therefore important - in particular with respect to the piping of the underfloor heating systems - that the installation is executed in a diffusion-proof manner.

The delivery rate of the circulating pump must be adapted to the heating system.

The setting of the overflow valve must be adapted to the requirements of the heating system. An incorrect setting may result in various error symptoms and an increased electric power consumption. To correctly set the overflow valve, the following procedure is recommended:

Also residues of lubricating and sealing agents may contaminate the heating water.

In the case of severe contamination leading to a reduction in the performance of the condenser in the heat pump, the system must be cleaned by a heating technician.

Page 9 of the Dimplex S1 7KS user manual — CAUTION!
Page 9 · click to enlarge
Page 9

CARE/CLEANING MALFUNCTIONS/TROUBLESHOOTING

DECOMMISSIONING

According to current knowledge, we recommend cleaning with a 5% phosphoric acid solution or, in the case that cleaning needs to be performed more frequently, with a 5% formic acid solution.

MALFUNCTIONS/ TROUBLESHOOTING

In either case, the cleaning fluid should be at room temperature. It is recommended that the heat exchanger be cleaned in the direction opposite to the normal flow direction.

This heat pump is a quality product and is designed for trouble-free operation. In the event that a malfunction occurs nevertheless, you will be able to correct the problem yourself in most of the cases. Simply consult the Malfunctions and Trouble- shooting table contained in the operating manual of the heat pump controller.

To prevent acidic cleaning agents from entering the circuit of the heating installation we recom- mend that the flushing device be fitted directly to the supply and return lines of the condenser. To prevent any damage caused by cleaning agent residues that may be present in the system it is important that the system be thoroughly flushed using appropriate neutralising agents.

Additional malfunctions can be interrogated at the heat pump controller.

If you cannot correct the malfunction yourself, please contact the after-sales service agent in charge (see Warranty Certificate).

The acids must be used with great care, all rele- vant regulations of the employers' liability insurance associations must be adhered to.

If in doubt, contact the manufacturer of the chemicals!

CAUTION!

All work on the heat pump may only be performed by an authorised and qualified after-sales service.

CAUTION!

Caution - Heating Technicians ! Depending on the filling water quality and quantity, in particular in the case of mixed installations and plastic pipes, mineral deposits (rust sludge, lime) may form, impairing the pro- per functioning of the heating installation. A reason for this is the water hardness and oxygen dissolved in the filling waters as well as additional oxygen from the air, which may penetrate via valves, fittings and plastic pipes (oxygen diffusion). As a preventive measure it is recommended that a physical water conditio- ner such as ELYSATOR be used.

DECOMMISSIONING

11.1 Shutdown in Summer

Shutting down the heating system in summer is effected by switching the heat pump controller to the "Summer" operating mode.

11.2 End-of-Life Decommissioning/ Disposal

9.3 Cleaning of Heat Source Side

Before removing the heat pump, disconnect the machine from the power source and close all valves. Environment-relevant requirements regarding the recovery, recycling and disposal of service fuels and components in accordance with all relevant standards must be adhered to. Particular attention must hereby be paid to the proper disposal of refrigerants and refrigeration oils.

CAUTION!

The supplied strainer is to be install- ed in the heat source inlet of the heat pump in order to protect the evaporator against conta- mination.

The filter screen of the strainer should be cleaned one day after commissioning, thereafter every week. If no more contamination can be noticed any more, the strainer filter can be removed in order to reduce pressure losses.

Page 10 of the Dimplex S1 7KS user manual — 12.5 HYDR. BLOCK DIAGRAM 21
Page 10 · click to enlarge
Page 10

APPENDIX

APPENDIX 12

12.1 DIMENSIONED DRAWING 11

12.2 EQUIPMENT DATA 12

12.3 SCHEMATICS 12.3.1 Characteristics .. 7KS 13 12.3.2 Characteristics .. 9KS 14 12.3.3 Characteristics .. 11KS 15 12.3.4 Characteristics .. 14KS 16

12.4 WIRING DIAGRAMS 12.4.1 Control .. 7KS to .. 14KS 17 12.4.2 Load .. 7KS to .. 14KS 18 12.4.3 Terminal Diagram .. 7KS to .. 14KS 19 12.4.4 Legend .. 7KS to .. 14KS 20

12.5 HYDR. BLOCK DIAGRAM 21

12.6 EC DECLARATION OF CONFORMITY 22

12.7 WARRANTY CERTIFICATE/ AFTER-SALES SERVICE 23

Page 11 of the Dimplex S1 7KS user manual — Dimensioned Drawing
Page 11 · click to enlarge
Page 11

APPENDIX: 12.1 DIMENSIONED DRAWING

12. 1 Maßbilder 12. 1 Maßbilder 12. 1 Maßbilder 12. 1 Maßbilder 12. 1 Maßbilder

Dimensioned Drawing

Dimplex S1 7KS — Dimensioned Drawing diagram (page 11)
Fig. 2 · Dimensioned Drawing
Page 12 of the Dimplex S1 7KS user manual — APPENDIX: 12.2 EQUIPMENT DATA
Page 12 · click to enlarge
Page 12

APPENDIX: 12.2 EQUIPMENT DATA

Equipment Data

EQUIPMENT DATA for Brine-to-Water Heat Pumps for Heating 1 TYPE AND COMMERCIAL DESCRIPTION..7KS..9KS..11KS..14KS 2 MODEL 2.1 Typecompactcompactcompactcompact 2.2 Enclosure type acc. to EN 60 529IP 20IP 20IP 20IP 20 2.3 Installation siteindoorsindoorsindoorsindoors 3 PERFORMANCE DATA 3.1 Operating temperature limits: Heating water supply °C Brine (heat source) °C Antifreeze agent Minimum brine concentration (-13°C freezing temperature)max. 55 -5 to +25 monoethylene glycol 25%max. 55 -5 to +25 monoethylene glycol 25%max. 55 -5 to +25 monoethylene glycol 25%max. 55 -5 to +25 monoethylene glycol 25% 3.2 Heating water temperature difference at B0 / W35 K9,910,510,19,6 3.3 Heating capacity / coeff.of perform. at B-5 / W55 1) kW / --- at B0 / W50 1) kW / --- at B0 / W35 1) kW / ---5,6 / 2,2 6,7 / 2,9 6,9 / 4,37,7 / 2,3 9,0 / 3,1 9,2 / 4,49,4 / 2,4 11,3 / 3,0 11,8 / 4,412,5 / 2,6 14,2 / 3,4 14,5 / 4,5 3.4 Sound power level dB(A)51515151 3.5 Heating water flow rate at internal pressure difference m³/h / Pa0,6 / 25000,75 / 45001,0 / 35001,3 / 3500 3.6 Free presssure, heating circulating pump (stage 3) Pa47500435006550064500 3.7 Brine flow rate at internal pressure difference (heat source) m³/h / Pa1,7 / 100002,3 / 160003,0 / 130003,5 / 13000 3.8 Free pressure, brine pump (stage 3) Pa55000440004000034000 3.9 Refrigerant; total charge weight type / kgR407C / 1,5R407C / 1,8R407C / 2,0R407C / 2,3 4 DIMENSIONS, CONNECTIONS AND WEIGHT 4.1 Equipment dimensions without connections 4) H x W x L mm1110 × 652 × 6531110 × 652 × 6531110 × 652 × 6531110 × 652 × 653 4.2 Equipment connections for heating system inchesR 1¼" ext.R 1¼" ext.R 1¼" ext.R 1¼" ext. 4.3 Equipment connections for heat source inchesR 1¼" ext.R 1¼" ext.R 1¼" ext.R 1¼" ext. 4.4 Weight of transport unit(s) incl. packaging kg179180191203 5 ELECTRICAL CONNECTION 5.1 Nominal voltage; fusing V / A400 / 16400 / 16400 / 16400 / 16 5.2 Nominal power consumption 1) B0 W35 kW1,62,072,663,22 5.3 Starting current with soft starter A30 (no soft starter)152626 5.4 Nominal current B0 W35 / cosϕ A / ---2,893,774,845,81 6 COMPLIES WITH EUROPEAN SAFETY REGULATIONS3)3)3)3) 7 OTHER DESIGN CHARACTERISTICS 7.1 Water inside equipment protected against freezing 2)yesyesyesyes 7.2 Performance settings1111 7.3 Controller internal / externalinternalinternalinternalinternal 1) These data characterize the size and performance capability of the system. For economic and energetic reasons, additional factors such as balance point and control need to be taken into consideration. Abbreviations have the following meaning, e.g. B10 / W55: heat source temperature 10 °C and heating water supply temperature 55 °C. 2) The heating circulating pump and the controller of the heat pump must be ready for operation at all times. 3) s. EC Declaration of Conformity 4) Please keep in mind that more space is required for pipe connection, operation and maintenanc. Subject to technical modifications Issued: 23.04.2004
Page 13 of the Dimplex S1 7KS user manual — APPENDIX: 12.3 SCHEMATICS
Page 13 · click to enlarge
Page 13

APPENDIX: 12.3 SCHEMATICS

12.3.1 Characteristics .. 7KS

Dimplex S1 7KS — APPENDIX: 12.3 SCHEMATICS diagram (page 13)
Fig. 3

-10 -5 0 5 10 15 20 25 30 Brine inlet temperature in [°C]

-10 -5 0 5 10 15 20 25 30 Brine inlet temperature in [°C]

0 1 2 3 4 5 6 7 8

-10 -5 0 5 10 15 20 25 30

Page 14 of the Dimplex S1 7KS user manual — APPENDIX: 12.3 SCHEMATICS
Page 14 · click to enlarge
Page 14

APPENDIX: 12.3 SCHEMATICS

12.3.2 Characteristics .. 9KS

Dimplex S1 7KS — APPENDIX: 12.3 SCHEMATICS diagram (page 14)
Fig. 4

-10 -5 0 5 10 15 20 25 30 Brine inlet temperature in [°C]

-10 -5 0 5 10 15 20 25 30 Brine inlet temperature in [°C]

0 1 2 3 4 5 6 7 8

-10 -5 0 5 10 15 20 25 30

Page 15 of the Dimplex S1 7KS user manual — APPENDIX: 12.3 SCHEMATICS
Page 15 · click to enlarge
Page 15

APPENDIX: 12.3 SCHEMATICS

12.3.3 Characteristics .. 11KS

Dimplex S1 7KS — APPENDIX: 12.3 SCHEMATICS diagram (page 15)
Fig. 5

-10 -5 0 5 10 15 20 25 30 Brine inlet temperature in [°C]

-10 -5 0 5 10 15 20 25 30 Brine inlet temperature in [°C]

0 1 2 3 4 5 6 7 8

-10 -5 0 5 10 15 20 25 30

Page 16 of the Dimplex S1 7KS user manual — APPENDIX: 12.3 SCHEMATICS
Page 16 · click to enlarge
Page 16

APPENDIX: 12.3 SCHEMATICS

12.3.4 Characteristics .. 14KS

Dimplex S1 7KS — APPENDIX: 12.3 SCHEMATICS diagram (page 16)
Fig. 6

-10 -5 0 5 10 15 20 25 30 Brine inlet temperature in [°C]

-10 -5 0 5 10 15 20 25 30 Brine inlet temperature in [°C]

0 1 2 3 4 5 6 7 8

-10 -5 0 5 10 15 20 25 30

Page 17 of the Dimplex S1 7KS user manual — APPENDIX: 12.4 WIRING DIAGRAMS
Page 17 · click to enlarge
Page 17

APPENDIX: 12.4 WIRING DIAGRAMS

12.4.1 Control .. 7KS to .. 14KS

Dimplex S1 7KS — APPENDIX: 12.4 WIRING DIAGRAMS diagram (page 17)
Fig. 7
Page 18 of the Dimplex S1 7KS user manual — APPENDIX: 12.4 WIRING DIAGRAMS
Page 18 · click to enlarge
Page 18

APPENDIX: 12.4 WIRING DIAGRAMS

12.4.2 Load .. 7KS to .. 14KS

Dimplex S1 7KS — APPENDIX: 12.4 WIRING DIAGRAMS diagram (page 18)
Fig. 8
Page 19 of the Dimplex S1 7KS user manual — APPENDIX: 12.4 WIRING DIAGRAMS
Page 19 · click to enlarge
Page 19

APPENDIX: 12.4 WIRING DIAGRAMS

12.4.3 Terminal Diagram .. 7KS to .. 14KS

Dimplex S1 7KS — APPENDIX: 12.4 WIRING DIAGRAMS diagram (page 19)
Fig. 9

can be selected 2nd disable input Contact open = HP disabled

Page 20 of the Dimplex S1 7KS user manual — APPENDIX: 12.4 WIRING DIAGRAMS
Page 20 · click to enlarge
Page 20

APPENDIX: 12.4 WIRING DIAGRAMS

12.4.4 Legend .. 7KS to .. 14KS

A1 Wire jumper, must be inserted if no utility company disable contactor is required A2 Wire jumper, must be removed if 2nd disable input is used

B3* Thermostat, hot water B4* Thermostat, swimming pool water

E9* Electric immersion heater, hot water E10* Back-up heater (boiler or electric heating element)

F2 Load fuse for N1 relay outputs across J12 and J13 4,0 ATr F3 Load fuse for N1 relay outputs across J15 to J18 4,0 ATr F4 Pressostat, high pressure F5 Pressostat, low pressure

H5* Lamp, remote fault indicator

J1...J18 Terminal connectors at N1

K1 Contactor, compressor K11* Electron. relay for remote fault indicator (on relay module) K12* Electron. relay for swimming pool water circulating pump (on relay module) K20* Contactor, back-up heater K21* Contactor, electr. immersion heater, hot water K22* Utility company disable contactor K23* SPR auxiliary relay

M1 Compressor M11 Primary circulating pump (brine) M13 Heating circulating pump M15* Heating circulating pump, heating circuit 2 M16* Suppl. circulating pump M18* Hot water circulating pump M19* Swimming pool water circulating pump M21* Mixer, primary circuit M22* Mixer, heating circuit 2

N1 Heat pump controller N7 Soft starter N10* Remote control station N11* Relay module

R1 External sensor R2 Return sensor R3 Hot water sensor (as an alternative to the hot water thermostat) R5 Sensor for heating circuit 2 R6 Freeze protection sensor R7 Coding resistor 8.2 kOhm

T1 Safety isolating transformer 230/24 VAC-28VA

X1 Terminal strip, mains-load 3L/PE-400 VAC-50 Hz/ Mains-control L/N/PE-230 VAC-50Hz / fuses/N- and PE-terminal block X2 Terminal strip 24 VAC-terminal block X3 Terminal strip GND terminal block for analog inputs at J2 and J6

Abbreviations:

EVS Utility company disable input SPR Supplementary disable input, configurable

MA* Mixer OPEN MZ Mixer CLOSED

* Components to be supplied by the customer

Page 21 of the Dimplex S1 7KS user manual — APPENDIX: 12.5 HYDRAULIC BLOCK DIAGRAM
Page 21 · click to enlarge
Page 21

APPENDIX: 12.5 HYDRAULIC BLOCK DIAGRAM

Hydraulic Block Diagram

Dimplex S1 7KS — APPENDIX: 12.5 HYDRAULIC BLOCK DIAGRAM diagram (page 21)
Fig. 10
Page 22 of the Dimplex S1 7KS user manual — SI 7KS SI 9KS SI 11KS SI 14KS
Page 22 · click to enlarge
Page 22

APPENDIX: 12.6 EC DECLARATION OF CONFORMITY

EC Declaration of Conformity

Dimplex S1 7KS — APPENDIX: 12.6 EC DECLARATION OF CONFORMITY diagram (page 22)
Fig. 11

Declaration of Conformity

Glen Dimplex Deutschland GmbH Division Dimplex Am Goldenen Feld 18 D-95326 Kulmbach

hereby confirm that the design and construction of the product(s) listed below, in the version(s) placed on the market by us, conform to the relevant requirements of the applicable EC directives.

This declaration becomes invalidated if any modifications are made to the product(s) without our prior authorization.

Designation of the product(s): EC Directives: Brine-to-water heat pumps EC Low Voltage Directive for indoor installation, (73/23/EEC) containing R407C EC EMC Directive (89/336/EEC) Pressure Equipment Directive (97/23/EEC)

Type(s)Harmonized EN Standards:

SI 7KS SI 9KS SI 11KS SI 14KS

Requirements of category II

Order No.: National Standard/Directives:

341 860 341 870 341 880 341 890

Kulmbach, 25.04.2005

General Manager Technical Director

CE09W09G.doc

The undersigned

Page 23 of the Dimplex S1 7KS user manual — APPENDIX: 12.5 HYDRAULIC BLOCK DIAGRAM
Page 23 · click to enlarge
Page 23
Page 24 of the Dimplex S1 7KS user manual — APPENDIX: 12.5 HYDRAULIC BLOCK DIAGRAM
Page 24 · click to enlarge
Page 24

Glen Dimplex Deutschland GmbH Subject to technical modifications Division Dimplex Fax +49 92 21/709-589 Am Goldenen Feld 18 www.dimplex.de D-95326 Kulmbach

Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the Dimplex S1 7KS

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.