INSTALLATION and OPERATING INSTRUCTIONS
Brine-to-Water Heat Pump
for Indoor Installation
SI 11KS SI 14KS SI 7KS SI 9KS
Order No.: 452231.67.01 FD 8504


READ IMMEDIATELY
CAUTION!
The supplied strainer is to be fitted in the heat source inlet of the heat pump in order to protect the evaporator against contamination.
CAUTION!
The heat pump is not secured to the wooden pallet.
Any work on the heat pump may only be performed by authorised and qualified customer service agents.
The heat pump must not be tilted more than max. 45° (in either direction).
Do not lift unit by the holes in the panel assemblies!
This heat pump conforms to all relevant DIN/VDE regulations and EU directives. For details refer to the EC Declaration of Conformity in the appendix.
In the case of large-capacity heating circuits, the installed expansion vessel (24 litres, 1.0 bar admission pressure) must be supplemented by an additional vessel.
The electrical connection of the heat pump must be performed according to and conforming with all re- levant VDE, EN and IEC standards. Beyond that, the connection requirements of the local utility compa- nies have to be observed.
The brine solution must contain at least 25 % of an antifreeze and corrosion protection agent on a monoethylene glycol or propylene glycol basis.
The heat pump is to be connected to the heat source and heat distribution systems in accordance with all applicable provisions.
On connecting the electrical load lines, the clockwise phase sequence must be observed (in the case of an incorrect phase sequence the heat pump will deliver no output and generate a lot of noise).
By operating this heat pump you contribute to the protection of our environment. A prerequisite for an efficient operation is the proper design and sizing of the heating system and the heat source system. In particular, it is important to keep water flow temperatures as low as possible. All energy consumers connected should therefore be suitable for low flow temperatures. A 1 K higher heating water temperature corresponds to an increase in power consumption of approx. 2.5 %. Underfloor heating systems with flow temperatures between 30 °C and 40 °C are optimally suited for energy-efficient operation.
Commissioning of the heat pump must be performed in accordance with the installation and operating manual of the heat pump controller.
Caution - Heating Contractors ! Depending on the filling water quality and quantity, in particular in the case of mixed installations and plastic pipes, mineral deposits (rust sludge, lime) may form, impairing the pro- per functioning of the heating installation. A reason for this is the water hardness and oxygen dissolved in the filling water as well as additional oxygen from the air, which may penetrate via valves, fittings and plastic pipes (oxygen diffusion). As a preventive measure it is recommended that a physical water conditio- ner such as ELYSATOR be used.

PURPOSE OF THE HEAT PUMP
BASELINE UNIT
The baseline unit consists of a heat pump of compact design, ready for connection. In addition to the control panel with integrated controller, the unit also contains essential components of the heating and brine circuits:
The brine-to-water heat pump is designed for use in existing or newly built heating systems. Brine is used as the heat carrier in the heat source system. Ground coils, ground collectors or similar systems can be used as the heat source.
- expansion vessels - circulating pumps - pressure relief valves - pressure gauges - overflow valve (heating circuit)
The refrigeration cycle contains the refrigerant R407C. Refrigerant R407C is CFC-free, non-ozone depleting and non-combustible.
The heat generated by the sun, wind and rain is stored in the ground. This heat stored in the ground is collected at low temperature by the brine circulating in the ground collector, ground coil or similar device. A circulating pump then conveys the warmed brine to the evaporator of the heat pump. There, the heat is given off to the refrigerant in the refrigeration cycle. When so doing, the brine cools so that it can again take up heat energy in the brine circuit.
All components required for the operation of the heat pump are provided on the control panel. The power feed for load and control current must be field- installed by the customer.
The collector loops including brine manifold must be provided by the customer.
The refrigerant, however, is drawn in by the electrically driven compressor, is compressed and "pumped" to a higher temperature level. The electrical power needed to run the compressor is not lost in this process, but most of the generated heat is trans- ferred to the refrigerant as well.

Subsequently, the refrigerant is passed through the condenser where it transfers its heat energy to the heating water. Based on the thermostat setting, the heating water is thus heated to up to 55 °C.
3 4 5 6

TRANSPORT
5 4 ACCESSORIES
TRANSPORT
4.1 Brine Manifold
A lift truck is suited for transporting the unit on a level surface. If the heat pump needs to be transported on an uneven surface or carried up or down stairs, carrying straps may be used for this type of transport. These straps may be passed directly underneath the wooden pallet.
The brine manifold ties the individual collector loops of the heat source system into a single main line which is connected to the heat pump. Integrated ball valves allow individual brine circuits to be shut off for venting purposes.
The heat pump is not secured to the wooden pallet.
The heat pump must not be tilted more than max. 45° (in either direction).
Where this is a legal requirement, a low-pressure brine pressostat may be installed in the unit. In this case, the connection provided above the brine expansion vessel should be used.
For lifting the unit without pallet, the holes provided in the sides of the frame should be used. The side panel assemblies must be removed for this purpose. A commercially available pipe can be used as a carrying aid.
Do not use the holes in the panel assemblies for lifting the unit!

INSTALLATION
MOUNTING
6.1 General Information
7.1 General
As a rule, the unit must be installed indoors on a level, smooth and horizontal surface. The entire base frame should thereby make close contact with the surface in order to ensure adequate sound insulation. Failing this, additional sound insulation measures may become necessary.
The following connections need to be established on the heat pump:
- supply/return flow of the brine system - supply/return flow of the space heating and
water heating system - common return of space heating and water
The heat pump should be located to allow safe and easy maintenance/service access. This is ensured if a clearance of approx. 1 m in front of and to each side of the heat pump is maintained.
heating system - return, overflow valve - connection for additional expansion vessel
(as required) - drain lines of overflow valves - condensate drain - power supply
The heat pump features separate outlets for the space heating and water heating circuit.
In cases where the heat pump has no water heating mode, the hot water outlet has to be permanently sealed.
Prior to establishing the heat pump connections on the heating water side, the heating installation must be flushed in order to remove any impurities that may be present , as well as residues of sealing material, or the like. Any accumulation of deposits in the condenser may result in a total failure of the heat pump.
The heat pump offers silent operation due to efficient sound insulation. Noise transmission to the foundation or the heating system is largely prevented by internal decoupling measures.
In systems equipped with heating water flow shut- off devices such as radiator or thermostat valves, an overflow valve is installed. This assures a minimum heating water flow through the heat pump and prevents any malfunctions for occurring.
Once the installation on the heating side has been completed, the heating system must be filled, deaerated and pressure-tested.
Frost Protection for Installations Prone to Frost Provided the controller and the heating circulating pumps are ready for operation, the frost protection function of the controller is always activated. If the heat pump is taken out of service or in the event of a power failure, the system must be drained. In heat

pump installations where a power failure cannot readily be detected (e.g. holiday houses), the heating circuit must contain a suitable antifreeze product.
The following electrical connections must be established on the heat pump.
The integrated expansion vessel has a capacity of 24 litres.This capacity is appropriate for buildings with a heated living space floor area of up to 200 m2.
- Connection of the load wire to the control panel of the heat pump.
- Connection of the control voltage wire to the control panel of the heat pump.
The planner of the heating system should verify that the capacity of the expansion vessel is adequate. An additional expansion vessel may have to be installed, if required (as per DIN 4751 Part 1). Charts in manufacturer catalogues facilitate the proper selection of the proper size according to the amount of water in the system.
All electrical components required for the operation of the heat pump are located on the control panel..
For detailed instructions concerning the connection of external components and the operation of the heat pump controller refer to the heat pump terminal dia- gram and the operating manual of the controller.
With large-capacity heating circuits, the installed expansion vessel (24 litres, 1.0 bar admission pressure) must be supplemented by an additional vessel.
Connection of the load wire to the control panel via terminals X1: L1/L2/L3/PE.

COMMISSIONING
Close all of the heating circuits that may also be closed during operation (depending on the type of heat pump usage) so that the least favourable operating state - with respect to the water flow rate - is achieved. Normally, these are the heating circuits of the rooms located on the south and west sides of buildings. At least one heating circuit must remain open (e.g. bathroom).
To ensure proper commissioning it should be carried out by an after-sales service authorised by the manufacturer. Only then can an extended warranty period of 3 years in total be granted (cf. Warranty service).
The overflow valve is to be opened to such an extent that based on the current heat source tem- perature the maximum temperature difference between heating supply and return flow tem- perature is obtained, as indicated in the table below. The temperature difference should be measured as closely to the heat pump as possible. In mono-energetic systems, the electric heating element is to be deactivated.
Prior to commissioning, the following items need to be checked:
- All connections of the heat pump must have been made as described in Chapter 7.
- The heat source system and the heating circuit must be filled and tested.
- Strainer and vent must be fitted in the brine inlet of the heat pump.
Any malfunctions occurring during operation are indicated on the display of the heat pump controller and can be corrected as described in the operating manual of the heat pump controller.
- All valves that could impair the proper water flow must be open in the brine and heating circuits.
- The heat pump controller must be adapted to the heating installation in accordance with the instructions contained in its operating manual.
- Proper condensate drainage must be ensured.
- Drainage of the liquid emerging from the brine and heating water overflow valves must be ensured.
The heat pump is designed for maintenance-free operation. To prevent operating malfunctions caused by dirt deposits in the heat exchangers, care must be taken that no contamination whatsoever can enter the heat source and heating systems. In the event that operating malfunctions due to contamination occur nevertheless, the system should be cleaned as described below.
The start-up of the heat pump is effected via the heat pump controller.
Commissioning of the heat pump must be carried out in accordance with the installation and operating manual of the heat pump controller.
The ingress of oxygen into the heating water circuit may result in the formation of oxidation products (rust). It is therefore important - in particular with respect to the piping of the underfloor heating systems - that the installation is executed in a diffusion-proof manner.
The delivery rate of the circulating pump must be adapted to the heating system.
The setting of the overflow valve must be adapted to the requirements of the heating system. An incorrect setting may result in various error symptoms and an increased electric power consumption. To correctly set the overflow valve, the following procedure is recommended:
Also residues of lubricating and sealing agents may contaminate the heating water.
In the case of severe contamination leading to a reduction in the performance of the condenser in the heat pump, the system must be cleaned by a heating technician.

DECOMMISSIONING
According to current knowledge, we recommend cleaning with a 5% phosphoric acid solution or, in the case that cleaning needs to be performed more frequently, with a 5% formic acid solution.
In either case, the cleaning fluid should be at room temperature. It is recommended that the heat exchanger be cleaned in the direction opposite to the normal flow direction.
This heat pump is a quality product and is designed for trouble-free operation. In the event that a malfunction occurs nevertheless, you will be able to correct the problem yourself in most of the cases. Simply consult the Malfunctions and Trouble- shooting table contained in the operating manual of the heat pump controller.
To prevent acidic cleaning agents from entering the circuit of the heating installation we recom- mend that the flushing device be fitted directly to the supply and return lines of the condenser. To prevent any damage caused by cleaning agent residues that may be present in the system it is important that the system be thoroughly flushed using appropriate neutralising agents.
Additional malfunctions can be interrogated at the heat pump controller.
If you cannot correct the malfunction yourself, please contact the after-sales service agent in charge (see Warranty Certificate).
The acids must be used with great care, all rele- vant regulations of the employers' liability insurance associations must be adhered to.
If in doubt, contact the manufacturer of the chemicals!
All work on the heat pump may only be performed by an authorised and qualified after-sales service.
Caution - Heating Technicians ! Depending on the filling water quality and quantity, in particular in the case of mixed installations and plastic pipes, mineral deposits (rust sludge, lime) may form, impairing the pro- per functioning of the heating installation. A reason for this is the water hardness and oxygen dissolved in the filling waters as well as additional oxygen from the air, which may penetrate via valves, fittings and plastic pipes (oxygen diffusion). As a preventive measure it is recommended that a physical water conditio- ner such as ELYSATOR be used.
Shutting down the heating system in summer is effected by switching the heat pump controller to the "Summer" operating mode.
9.3 Cleaning of Heat Source Side
Before removing the heat pump, disconnect the machine from the power source and close all valves. Environment-relevant requirements regarding the recovery, recycling and disposal of service fuels and components in accordance with all relevant standards must be adhered to. Particular attention must hereby be paid to the proper disposal of refrigerants and refrigeration oils.
The supplied strainer is to be install- ed in the heat source inlet of the heat pump in order to protect the evaporator against conta- mination.
The filter screen of the strainer should be cleaned one day after commissioning, thereafter every week. If no more contamination can be noticed any more, the strainer filter can be removed in order to reduce pressure losses.

APPENDIX 12
12.1 DIMENSIONED DRAWING 11
12.2 EQUIPMENT DATA 12
12.3 SCHEMATICS 12.3.1 Characteristics .. 7KS 13 12.3.2 Characteristics .. 9KS 14 12.3.3 Characteristics .. 11KS 15 12.3.4 Characteristics .. 14KS 16
12.4 WIRING DIAGRAMS 12.4.1 Control .. 7KS to .. 14KS 17 12.4.2 Load .. 7KS to .. 14KS 18 12.4.3 Terminal Diagram .. 7KS to .. 14KS 19 12.4.4 Legend .. 7KS to .. 14KS 20
12.6 EC DECLARATION OF CONFORMITY 22
12.7 WARRANTY CERTIFICATE/ AFTER-SALES SERVICE 23



Equipment Data

12.3.1 Characteristics .. 7KS

-10 -5 0 5 10 15 20 25 30 Brine inlet temperature in [°C]
-10 -5 0 5 10 15 20 25 30 Brine inlet temperature in [°C]
0 1 2 3 4 5 6 7 8
-10 -5 0 5 10 15 20 25 30

12.3.2 Characteristics .. 9KS

-10 -5 0 5 10 15 20 25 30 Brine inlet temperature in [°C]
-10 -5 0 5 10 15 20 25 30 Brine inlet temperature in [°C]
0 1 2 3 4 5 6 7 8
-10 -5 0 5 10 15 20 25 30

12.3.3 Characteristics .. 11KS

-10 -5 0 5 10 15 20 25 30 Brine inlet temperature in [°C]
-10 -5 0 5 10 15 20 25 30 Brine inlet temperature in [°C]
0 1 2 3 4 5 6 7 8
-10 -5 0 5 10 15 20 25 30

12.3.4 Characteristics .. 14KS

-10 -5 0 5 10 15 20 25 30 Brine inlet temperature in [°C]
-10 -5 0 5 10 15 20 25 30 Brine inlet temperature in [°C]
0 1 2 3 4 5 6 7 8
-10 -5 0 5 10 15 20 25 30

12.4.1 Control .. 7KS to .. 14KS


12.4.2 Load .. 7KS to .. 14KS


12.4.3 Terminal Diagram .. 7KS to .. 14KS

can be selected 2nd disable input Contact open = HP disabled

12.4.4 Legend .. 7KS to .. 14KS
A1 Wire jumper, must be inserted if no utility company disable contactor is required A2 Wire jumper, must be removed if 2nd disable input is used
B3* Thermostat, hot water B4* Thermostat, swimming pool water
E9* Electric immersion heater, hot water E10* Back-up heater (boiler or electric heating element)
F2 Load fuse for N1 relay outputs across J12 and J13 4,0 ATr F3 Load fuse for N1 relay outputs across J15 to J18 4,0 ATr F4 Pressostat, high pressure F5 Pressostat, low pressure
H5* Lamp, remote fault indicator
J1...J18 Terminal connectors at N1
K1 Contactor, compressor K11* Electron. relay for remote fault indicator (on relay module) K12* Electron. relay for swimming pool water circulating pump (on relay module) K20* Contactor, back-up heater K21* Contactor, electr. immersion heater, hot water K22* Utility company disable contactor K23* SPR auxiliary relay
M1 Compressor M11 Primary circulating pump (brine) M13 Heating circulating pump M15* Heating circulating pump, heating circuit 2 M16* Suppl. circulating pump M18* Hot water circulating pump M19* Swimming pool water circulating pump M21* Mixer, primary circuit M22* Mixer, heating circuit 2
N1 Heat pump controller N7 Soft starter N10* Remote control station N11* Relay module
R1 External sensor R2 Return sensor R3 Hot water sensor (as an alternative to the hot water thermostat) R5 Sensor for heating circuit 2 R6 Freeze protection sensor R7 Coding resistor 8.2 kOhm
T1 Safety isolating transformer 230/24 VAC-28VA
X1 Terminal strip, mains-load 3L/PE-400 VAC-50 Hz/ Mains-control L/N/PE-230 VAC-50Hz / fuses/N- and PE-terminal block X2 Terminal strip 24 VAC-terminal block X3 Terminal strip GND terminal block for analog inputs at J2 and J6
Abbreviations:
EVS Utility company disable input SPR Supplementary disable input, configurable
MA* Mixer OPEN MZ Mixer CLOSED
* Components to be supplied by the customer

Hydraulic Block Diagram


EC Declaration of Conformity

Glen Dimplex Deutschland GmbH Division Dimplex Am Goldenen Feld 18 D-95326 Kulmbach
hereby confirm that the design and construction of the product(s) listed below, in the version(s) placed on the market by us, conform to the relevant requirements of the applicable EC directives.
This declaration becomes invalidated if any modifications are made to the product(s) without our prior authorization.
Designation of the product(s): EC Directives: Brine-to-water heat pumps EC Low Voltage Directive for indoor installation, (73/23/EEC) containing R407C EC EMC Directive (89/336/EEC) Pressure Equipment Directive (97/23/EEC)
Requirements of category II
Order No.: National Standard/Directives:
341 860 341 870 341 880 341 890
Kulmbach, 25.04.2005
General Manager Technical Director
CE09W09G.doc
The undersigned


Glen Dimplex Deutschland GmbH Subject to technical modifications Division Dimplex Fax +49 92 21/709-589 Am Goldenen Feld 18 www.dimplex.de D-95326 Kulmbach