CEp.1MOUNTING and OPERATING MANUALp.1Reversible Air-to-Water Heat Pumpp.1for Outdoor Installationp.1LA 16ASRp.1Order No.: 452158.66.21 FD 8 5 07p.1CONTENTSp.21 READ IMMEDIATELY 3p.22 PURPOSE OF HEAT PUMP 4p.23 SCOPE OF DELIVERY 4/5p.24 TRANSPORT 5p.25 INSTALLATION 6p.26 MOUNTING 6/7p.27 COMMISSIONING 7/8p.28 CLEANING / MAINTENANCE 8/9p.29 MALFUNCTIONS, TROUBLESHOOTING 9p.210 DECOMMISSIONING 9p.211 APPENDIX FFp.2READ IMMEDIATELYp.31.2 Legal Provisions and Guidelinesp.31.3 Energy-Efficient Use of the Heat Pumpp.3PURPOSE OF HEAT PUMP SCOPE OF DELIVERYp.4PURPOSE OF HEAT PUMPp.42.1 Applicationp.4SCOPE OF DELIVERYp.43.1 Baseline Unitp.42.2 Principle of Operationp.4TRANSPORTp.53.3 Heat Pump Controllerp.5INSTALLATION MOUNTINGp.66 INSTALLATIONp.6MOUNTINGp.65.1 Generalp.66.1 Generalp.66.2 Heating and Hot Water Connectionp.65.2 Condensate Linep.6MOUNTING COMMISSIONINGp.76.3 Electrical Connectionp.7COMMISSIONINGp.77.1 Generalp.77.2 Preparatory Stepsp.77.3 Procedure During Heating Seasonp.7COMMISSIONING CLEANING / MAINTENANCEp.8CLEANING / MAINTENANCEp.88.1 Maintenancep.87.4 Procedure During Cooling Seasonp.88.2 Cleaning of Heating Sidep.8CLEANING / MAINTENANCE MALFUNCTIONS / TROUBLESHOOTINGp.9DECOMMISSIONINGp.9MALFUNCTIONS / TROUBLESHOOTINGp.910.1 Placing Out of Service in Summerp.98.3 Cleaning of Air Sidep.910.2 End-of-Life Decommissioning / Disposalp.9APPENDIXp.1011.1 DIMENSION DRAWING 11p.1011.2 EQUIPMENT DATA 12p.1011.3 SCHEMATICSp.1011.4 WIRING DIAGRAMSp.1011.5 HYDRAULIC BLOCK DIAGRAM 19p.1011.6 EC DECLARATION OF CONFORMITY 20p.1011.7 WARRANTY CERTIFICATE AFTER-SALES SERVICE 21p.10APPENDIX: 11.1 DIMENSION DRAWINGp.11Dimension Drawingp.11APPENDIX: 11.2 EQUIPMENT DATAp.12Equipment Datap.12APPENDIX: 11.3 SCHEMATICSp.1311.3.1 Heating Modep.1311.3.2 Cooling Modep.14APPENDIX: 11.4 WIRING DIAGRAMSp.1511.4.1 Controlp.1511.4.2 Loadp.1611.4.3 Terminal Diagramp.17Klemmenplan und Steckverbinderbelegung im reversiblen Luft/Wasser-Außengerät LA 16 ASRp.1711.4.4 Legendp.18APPENDIX: 11.5 HYDRAULIC BLOCK DIAGRAMp.19Hydraulic Block Diagramp.19APPENDIX: 11.6 EC DECLARATION OF CONFORMITYp.20EC Declaration of Conformityp.20Declaration of Conformityp.20Notesp.21
Page 1 of the Dimplex LA16ASR user manual — Order No.: 452158.66.21 FD 8 5 07
Page 1 · click to enlarge
Page 1

CE

MOUNTING and OPERATING MANUAL

Reversible Air-to-Water Heat Pump

for Outdoor Installation

LA 16ASR

Dimplex LA16ASR — CE diagram (page 1)
Fig. 1

Order No.: 452158.66.21 FD 8 5 07

Page 2 of the Dimplex LA16ASR user manual — Table of Contents
Page 2 · Contents
Contents

Contents

CEp.1MOUNTING and OPERATING MANUALp.1Reversible Air-to-Water Heat Pumpp.1for Outdoor Installationp.1LA 16ASRp.1Order No.: 452158.66.21 FD 8 5 07p.1CONTENTSp.21 READ IMMEDIATELY 3p.22 PURPOSE OF HEAT PUMP 4p.23 SCOPE OF DELIVERY 4/5p.24 TRANSPORT 5p.25 INSTALLATION 6p.26 MOUNTING 6/7p.27 COMMISSIONING 7/8p.28 CLEANING / MAINTENANCE 8/9p.29 MALFUNCTIONS, TROUBLESHOOTING 9p.210 DECOMMISSIONING 9p.211 APPENDIX FFp.2READ IMMEDIATELYp.31.2 Legal Provisions and Guidelinesp.31.3 Energy-Efficient Use of the Heat Pumpp.3PURPOSE OF HEAT PUMP SCOPE OF DELIVERYp.4PURPOSE OF HEAT PUMPp.42.1 Applicationp.4SCOPE OF DELIVERYp.43.1 Baseline Unitp.42.2 Principle of Operationp.4TRANSPORTp.53.3 Heat Pump Controllerp.5INSTALLATION MOUNTINGp.66 INSTALLATIONp.6MOUNTINGp.65.1 Generalp.66.1 Generalp.66.2 Heating and Hot Water Connectionp.65.2 Condensate Linep.6MOUNTING COMMISSIONINGp.76.3 Electrical Connectionp.7COMMISSIONINGp.77.1 Generalp.77.2 Preparatory Stepsp.77.3 Procedure During Heating Seasonp.7COMMISSIONING CLEANING / MAINTENANCEp.8CLEANING / MAINTENANCEp.88.1 Maintenancep.87.4 Procedure During Cooling Seasonp.88.2 Cleaning of Heating Sidep.8CLEANING / MAINTENANCE MALFUNCTIONS / TROUBLESHOOTINGp.9DECOMMISSIONINGp.9MALFUNCTIONS / TROUBLESHOOTINGp.910.1 Placing Out of Service in Summerp.98.3 Cleaning of Air Sidep.910.2 End-of-Life Decommissioning / Disposalp.9APPENDIXp.1011.1 DIMENSION DRAWING 11p.1011.2 EQUIPMENT DATA 12p.1011.3 SCHEMATICSp.1011.4 WIRING DIAGRAMSp.1011.5 HYDRAULIC BLOCK DIAGRAM 19p.1011.6 EC DECLARATION OF CONFORMITY 20p.1011.7 WARRANTY CERTIFICATE AFTER-SALES SERVICE 21p.10APPENDIX: 11.1 DIMENSION DRAWINGp.11Dimension Drawingp.11APPENDIX: 11.2 EQUIPMENT DATAp.12Equipment Datap.12APPENDIX: 11.3 SCHEMATICSp.1311.3.1 Heating Modep.1311.3.2 Cooling Modep.14APPENDIX: 11.4 WIRING DIAGRAMSp.1511.4.1 Controlp.1511.4.2 Loadp.1611.4.3 Terminal Diagramp.17Klemmenplan und Steckverbinderbelegung im reversiblen Luft/Wasser-Außengerät LA 16 ASRp.1711.4.4 Legendp.18APPENDIX: 11.5 HYDRAULIC BLOCK DIAGRAMp.19Hydraulic Block Diagramp.19APPENDIX: 11.6 EC DECLARATION OF CONFORMITYp.20EC Declaration of Conformityp.20Declaration of Conformityp.20Notesp.21
Page 3 of the Dimplex LA16ASR user manual — 1.3 Energy-Efficient Use of the Heat Pump
Page 3 · click to enlarge
Page 3

READ IMMEDIATELY

READ IMMEDIATELY

1.2 Legal Provisions and Guidelines

This heat pump was designed and built in compliance with all relevant EU directives, DIN and VDE regulations (see CE Declaration of Conformity).

1.1 Important Information AUTION! Prior to opening the unit it must be ensured that all electrical circuits are disconnected from the power source. AUTION! During transport, the heat pump must not be tilted more than 45° (in either direction). AUTION! Heat pump and transport pallet are only connected by the packaging film. AUTION! The intake and outlet duct openings must not be restricted nor obstructed. AUTION! Clockwise phase sequence to be observed: Damage to the compressor may be incurred if it is operated in the wrong sense of rotation. AUTION! Do not use any cleaning agents containing sand, soda, acid or chloride as these may attack the surface. AUTION! To prevent consequential damage it is imperative that the water circuit be neutralized after cleaning using appropriate agents. AUTION! The unit is not suitable for operation with a frequency converter. AUTION! Work on the refrigeration circuit may be performed by qualified persons only. CAUTION! CAUTION! CAUTION! CAUTION! CAUTION! CAUTION! CAUTION! CAUTION! CAUTION!

The electrical connection of the heat pump must be performed according to and conforming with all relevant VDE, EN and IEC standards. Beyond that, all technical connection requirements of the local electrical utility company have to be observed.

On connecting the heating and cooling system, all relevant regulations have to be complied wit.

1.3 Energy-Efficient Use of the Heat Pump

By purchasing this heat pump you contribute to the protection of the environment. A prerequisite for energy-efficient operation is the proper design of the heat source system and the heat utilization/cooling system.

One of the most important factors of heat pump efficiency is keeping the temperature difference between the heating water and the heat source as small as possible. It is therefore strongly recommended that the design of both the heat source system and the heat distribution system be carried out with great care. A 1 Kelvin (1°C) higher temperature difference corresponds to an increase in power consumption of approx. 2.5%. When designing the heating system care must be taken that special applications such as domestic water heating are taken into consideration and dimensioned for low temperature operation. Heat pumps are optimally suited for underfloor heating (surface/radiant heating) applications due to the low supply temperatures (30 °C to 40 °C).

During operation it is essential that the heat exchanger is not contaminated as this would increase the temperature difference resulting in an inferior coefficient of performance.

A considerable contribution to the economical operation is made by the heat pump controller provided it is set correctly. For more detailed information refer to the operating manual of the heat pump controller.

Page 4 of the Dimplex LA16ASR user manual — 6 5 4 3
Page 4 · click to enlarge
Page 4

PURPOSE OF HEAT PUMP SCOPE OF DELIVERY

PURPOSE OF HEAT PUMP

valve as well as the low-noise compressor, a desuperheater, a condenser and the electric control unit.

In the case of low ambient temperatures, air humidity may accumulate on the evaporator in the form of frost impairing the heat transfer. The evaporator is automatically defrosted by the heat pump, if required.

2.1 Application

The air-to-water heat pump is designed for use in existing or newly built heating systems.

Cooling In the "cooling" mode, the operating process of evaporator and condenser is reversed..

The heat pump is designed exclusively for the heating and cooling of heating water!

The heating water transfers the heat to the refrigerant via the condenser that is now working as the evaporator. In the compressor the temperature of the refrigerant is raised, and the heat is rejected to the ambient air via the condenser (in the heating mode the evaporator).

In the heating mode, the heat pump is suitable both for mono-energetic and bivalent operation at outdoor air temperatures down to -20 oC.

In the continuous mode of operation, a heating water return temperature of more than 18 °C must be maintained in order to ensure proper defrosting of the evaporator.

Via the additional heat exchanger, the waste heat can also be used for hot water consumers such as domestic hot water, swimming pool or bathroom heating applications.

The heat pump is not designed for any increased heat demand during the drying phase of new buildings; the additional heat demand must be met by special appliances to be supplied on site. For the structural drying of new buildings in the autumn or winter it is recommended that an additional electric heating element (available as accessory) be installed.

SCOPE OF DELIVERY

3.1 Baseline Unit

In the cooling mode, the heat pump is suited for air temperatures ranging from +15 °C ... +40 °C.

The heat pump is delivered as a compact unit containing the components listed below.

It can be used for passive and dynamic cooling applications alike. The minimum water temperature is +7 °C.

The refrigerant used is R404A.

The unit is not suited for operation with a frequency converter.

Dimplex LA16ASR — 3.1 Baseline Unit diagram (page 4)
Fig. 2 · 3.1 Baseline Unit

2.2 Principle of Operation

Heating Ambient air is drawn in by the fan and passed over the evaporator (heat exchanger). The evaporator cools the air, i.e. it extracts the heat it contains. In the evaporator, the heat removed is transferred to the working fluid (refrigerant).

With the aid of an electrically driven compressor, the absorbed heat is "pumped" to a higher temperature level through pressure increase and given off to the heating water via the condenser (heat exchanger).

The desuperheater, mounted upstream, enables domestic hot water to be produced simultaneously or separately.

In so doing, electrical energy is used to raise the heat of the environment to a higher temperature level. Due to the fact that the energy extracted from the air is transferred to the heating water, this type of appliance is referred to a air-to-water heat pump.

6 5 4 3

1. Evaporator 4) Pressostats (heating mode) 5) Condenser 2) Fan (heating mode) 3) Control box 6) Compressor

The air-to-water heat pump consists of the following main components: evaporator, fan and expansion

Page 5 of the Dimplex LA16ASR user manual — 3.3 Heat Pump Controller
Page 5 · click to enlarge
Page 5

SCOPE OF DELIVERY

TRANSPORT

3.2 Control Box The control box is integrated in the heat pump. It can be folded downward after removing the lower front panel and loosening the fastening screws located at the top on the right.

TRANSPORT

During transport, the heat pump must not be tilted more than 45° (in either direction).

The control box houses the mains terminals as well as the power contactors and the soft start unit.

The plug connector for the control lead is located at the bottom of the unit in the immediate vicinity of the line feed-through through the bottom of the unit.

The unit should be transported to the final installation site on a wooden pallet. The baseline unit can be transported either by means of a lift truck, a sack trolley, or the like, or using 3/4" pipes to be put through the openings provided in the base plate or the frame.

3.3 Heat Pump Controller

For the operation of your reversible air-to-water heat pump, the reversible heat pump controller included in the scope of delivery is to be used.

he heat pump controller is a comfortable electronic regulating and control unit. It controls and monitors the entire heating/cooling system as a function of the outdoor air temperature, the hot water preparation and the safety devices.

The external temperature sensor, to be mounted by the customer, incl. fastening hardware is shipped with the controller.

Method of functioning and operation of the heat pump controller are described in the enclosed operating manual.

The heat pump and transport pallet are only connected by the packaging film.

It is necessary to remove the lower cover panel to be able to access the transport openings in the frame. For this purpose, loosen two screws each in the base, retract the panels and disengage them at the

Opening the cover Closing the cover

top. When reinstalling the panels, they should be pushed upward by exerting slight pressure.

When slipping the carrying pipes through the frame, care must be taken that no components are damaged.

Page 6 of the Dimplex LA16ASR user manual — 5.2 Condensate Line
Page 6 · click to enlarge
Page 6

INSTALLATION MOUNTING

6 INSTALLATION

MOUNTING

5.1 General

6.1 General

The unit should always be installed on a permanently level, smooth and horizontal floor. The entire base frame surface should thereby make close contact with the floor in order to ensure adequate sound insulation and to prevent water-carrying parts from cooling out. If this is not the case, additional insulation measures may become necessary. It must be possible to carry out servicing work without any problems. This is ensured if a clearance of 1.2 m to solid walls is maintained.

The following connections need to be established on the heat pump:

- supply/return flow of heating system - supply/return flow of hot water circuit - condensate drain - control lead to the heat pump controller - power supply

6.2 Heating and Hot Water Connection

The connections on the heating side of the heat pump are provided with 1"external thread. The hoses to be connected exit the unit through its bottom. When carrying out the connections, use a wrench to counterhold at the transitions.

1,2 m 1,2 m1,2 m 1,2 m

Before completing the heat pump connections on the heating water side, the heating installation must be flushed in order to remove any impurities that may be present and to ensure trouble-free operation of the heat pump. On systems equipped with heating water flow shut-off devices such as radiator or thermostat valves, an overflow valve to be provided by the customer needs to be installed behind the heating pump in a heating system bypass. This guarantees a minimum heating water flow through the heat pump and prevents any malfunctions from occurring.

Once the installation on the heating side has been completed, the heating system must be filled, de- aerated and pressure-tested.

The intake and discharge openings must not be restricted nor obstructed.

Frost Protection As a precaution against frost, manual drain valves should be provided. If the heat pump is placed out of service or in the event of a power failure, the system has to be drained at three points (see figure) and blown out. In heat pump installations where a power failure cannot be readily detected (holiday house), the heating circuit must contain a suitable antifreeze product.

5.2 Condensate Line

The condensation water that may collect during operation must be drained in a place protected from frost. The heat pump must be positioned horizontally so that proper discharge can be ensured. The condensation water pipe must have a minimum diameter of 50 mm and should be discharged to the sewer drain in a frost-proof location.

Dimplex LA16ASR — 5.2 Condensate Line diagram (page 6)
Fig. 3 · 5.2 Condensate Line
Page 7 of the Dimplex LA16ASR user manual — 7.3 Procedure During Heating Season
Page 7 · click to enlarge
Page 7

MOUNTING COMMISSIONING

6.3 Electrical Connection

COMMISSIONING

The power connection of the heat pump is effected via a commercially available 4-core cable.

7.1 General

The cable has to be supplied by the client and the wire cross-section to be selected according to the power consumption of the heat pump (see Equip- ment Data in the appendix) as well as the relevant VDE (EN) and VNB regulations.

To ensure proper commissioning it should be carried out by an after-sales service authorized by the manufacturer. Only then can an extended warranty period of 3 years in total be granted (cf. Warranty service).

The power supply of the heat pump must be equipped with an all-pole disconnecting device with a contact gap of at least 3 mm (e.g. utility company shut-off contactor, power contactor) as well as a 3- pole circuit breaker with simultaneous tripping of all external conductors (tripping current as stated on the device data plate).

7.2 Preparatory Steps

Prior to commissioning, the following items need to be checked:

- All connections of the heat pump must have been

made as described in Chapter 6.

When making the electrical connection, the clockwise phase sequence of the power supply must be ensured.

- In the heating circuit all valves that could impair

the proper heating water flow must be open.

- The air intake/discharge path must be

Phase sequence: L1, L2, L3.

unobstructed.

- The sense of rotation of the fan must correspond

to the direction of the arrow.

Clockwise phase sequence to be observed: Damage to the compressor may be incurred if it is operated in the wrong sense of rotation.

- The settings of the heat pump controller must be

adapted to the heating installation in accordance with the instructions contained in its instruction manual.

The control voltage is supplied via the heat pump controller.

- Proper condensate drainage must be ensured.

The 230V AC-50 Hz power supply of the heat pump controller is effected as described in its instruction manual (fusing 16 A).

7.3 Procedure During Heating Season

The start-up of the heat pump is effected via the heat pump controller. The settings must be made in accordance with its instruction manual.

The control lead (not included in the scope of delivery) is connected to the heat pump controller via a multi-pole plug connector. In the heat pump, the plug connector located at the bottom of the unit in the immediate vicinity of the line feed-through through the base of the unit. More detailed instructions are contained in the instruction manual of the heat pump controller.

Malfunctions during operation are displayed on the heat pump controller and may be corrected as described in the heat pump controller's instruction manual.

n the case of outdoor temperatures below 10 °C and heating water temperatures below 16 °C, the buffer tank has to be heated to at least 30 °C using the second heat generator.

For more detailed information refer to the wiring diagrams in the appendix.

The following procedure has to be observed so that the commissioning activities can be carried out without any problems:

a) Close all heating circuits.

b) Open the overflow valve all the way.

c) Select the automatic mode on the controller.

d) Wait until the buffer tank has reached a temperature of 25-30 °C.

e) Subsequently, slowly reopen the valves of the heating circuits, one after the other, in such a way that the heating water flow rate is continually increased by slightly opening the related heating circuit valve. When so doing, the heating water temperature in the buffer tank must not fall below 25 °C so that the heat pump can be defrosted at any time.

Page 8 of the Dimplex LA16ASR user manual — 8.2 Cleaning of Heating Side
Page 8 · click to enlarge
Page 8

COMMISSIONING CLEANING / MAINTENANCE

f) Once all heating circuit are fully open and a heating water temperature of approx. 25 °C is maintained in the buffer tank, the minimum flow rate must be set on the overflow valve and the heating circulating pump.

CLEANING / MAINTENANCE

8.1 Maintenance

g) New buildings have an increased heat demand due to the energy required for structural drying. This increased heat demand may result in insufficiently dimensioned heating installations not attaining the desired room temperature at all times. In this case it is therefore recommended that the second heat generator be kept ready for operation in the first heating season. The limit temperature on the heat pump controller should therefore be raised to 15°C.

To protect the paint finish, avoid placing objects against or on the unit. The external parts of the heat pump can be wiped with a damp cloth and commercially available cleaning agents.

Do not use any cleaning agents containing sand, soda, acid or chloride as these may damage the surface.

7.4 Procedure During Cooling Season

To prevent malfunctions in the heat exchanger of the heat pump caused by dirt deposits, care must be taken that the heat exchanger cannot become contaminated in the heating installation. In the event that operating malfunctions due to contamination occur nevertheless, the system should be cleaned as described below.

In this case, all heating circuits can be fully opened.

The setting described in 7.3 f) must be carried out during the heating season.

8.2 Cleaning of Heating Side

The ingress of oxygen into the heating water may result in the formation of oxidation products. An ad- ditional contamination of the heating water caused by residues of lubricating and sealing agents occurs in many cases.

Both of the above causes may lead to a reduction in the performance of the heat pump condenser. In these cases the installer needs to clean the condenser. Based on information known to date we recommend cleaning with a 5% phosphoric acid solution or, in the case that cleaning needs to be performed more frequently, with a 5% formic acid solution. In both cases the

cleaning fluid should be at room temperature. Thorough flushing is necessary to ensure that all cleaning agent residues are removed from the system. It is recommended that the heat exchanger is cleaned in the direction opposite to the normal flow direction. Owing to their acid content flushing agents must be used with caution. To prevent acidic flushing agents from entering the heating installation when cleaning the condenser, we recommend that the flushing device should be mounted directly to

Page 9 of the Dimplex LA16ASR user manual — 10.2 End-of-Life Decommissioning / Disposal
Page 9 · click to enlarge
Page 9

CLEANING / MAINTENANCE MALFUNCTIONS / TROUBLESHOOTING

DECOMMISSIONING

the supply and return line of the heat pump. The regulations of the trade associations must be adhered to. If in doubt, contact the manufacturers of the chemicals!

MALFUNCTIONS / TROUBLESHOOTING

This heat pump is a quality product and is designed for troublefree and maintenance-free operation. In the event that a malfunction occurs nevertheless, you will be able to correct the problem easily yourself. Simply consult the Malfunctions and Troubleshooting table in the operating manual of the controller. Malfunctions can be interrogated at the heat pump controller. If the problem cannot be corrected by the user, please contact the after-sales service in charge (see Warranty Card).

To prevent consequential damage it is imperative that the water circuit be neutralized after cleaning using appropriate agents.

Depending on the water quality and quantity, in particular in the case of mixed installations and plastic pipes, mineral deposits (rust sludge, lime) may form impairing the proper functioning of the heating installation. A cause of this is the water hardness as well as oxygen dissolved in the filling water as well as additional oxygen from the air which may penetrate via valves, fittings and plastic pipes (oxygen diffusion). As a preventive measure it is recommended that a physical water conditioner such as ELYSATOR be used.

Any work on the heat pump may only be performed by an authorized and qualified after- sales service.

DECOMMISSIONING

10.1 Placing Out of Service in Summer

8.3 Cleaning of Air Side

Placing the heat pump out of service in summer can be effected by switching the heat pump controller to the "Summer" operating mode.

Evaporator, fan and condensate drain should be cleaned of debris (leaves, branches, etc.) from time to time. To this end, the front panel of the heat pump should be opened first at the bottom and then at the top.

10.2 End-of-Life Decommissioning / Disposal

Prior to opening the unit it must be ensured that all electrical circuits are disconnected from the power source.

Before removing the heat pump, disconnect the machine from the power supply and close all valves. Environment-relevant requirements regarding the recovery, recycling and disposal of service fuels and components in accordance with all relevant standards must be adhered to. In this context, particular attention must be paid to the proper disposal of refrigerants and refrigeration oils.

The removal and reinstallation of the panel assemblies to be performed as described in Chapter 4.

When cleaning do not use any sharp or hard objects so as to prevent any damage to the evaporator and the condensate pan.

Page 10 of the Dimplex LA16ASR user manual — 11.5 HYDRAULIC BLOCK DIAGRAM 19
Page 10 · click to enlarge
Page 10

APPENDIX

APPENDIX

11.1 DIMENSION DRAWING 11

11.2 EQUIPMENT DATA 12

11.3 SCHEMATICS

11.3.1 Heating Mode 13 11.3.2 Cooling Mode 14

11.4 WIRING DIAGRAMS

11.4.1 Control 15 11.4.2 Load 16 11.4.3 Terminal Diagram 17 11.4.4 Legend 18

11.5 HYDRAULIC BLOCK DIAGRAM 19

11.6 EC DECLARATION OF CONFORMITY 20

11.7 WARRANTY CERTIFICATE AFTER-SALES SERVICE 21

Page 11 of the Dimplex LA16ASR user manual — APPENDIX: 11.1 DIMENSION DRAWING
Page 11 · click to enlarge
Page 11

APPENDIX: 11.1 DIMENSION DRAWING

Dimension Drawing

Dimplex LA16ASR — APPENDIX: 11.1 DIMENSION DRAWING diagram (page 11)
Fig. 4
Page 12 of the Dimplex LA16ASR user manual — APPENDIX: 11.2 EQUIPMENT DATA
Page 12 · click to enlarge
Page 12

APPENDIX: 11.2 EQUIPMENT DATA

Equipment Data

Dimplex LA16ASR — APPENDIX: 11.2 EQUIPMENT DATA diagram (page 12)
Fig. 5
Page 13 of the Dimplex LA16ASR user manual — APPENDIX: 11.3 SCHEMATICS
Page 13 · click to enlarge
Page 13

APPENDIX: 11.3 SCHEMATICS

11.3.1 Heating Mode

Dimplex LA16ASR — APPENDIX: 11.3 SCHEMATICS diagram (page 13)
Fig. 6
Page 14 of the Dimplex LA16ASR user manual — APPENDIX: 11.3 SCHEMATICS
Page 14 · click to enlarge
Page 14

APPENDIX: 11.3 SCHEMATICS

11.3.2 Cooling Mode

Dimplex LA16ASR — APPENDIX: 11.3 SCHEMATICS diagram (page 14)
Fig. 7
Page 15 of the Dimplex LA16ASR user manual — APPENDIX: 11.4 WIRING DIAGRAMS
Page 15 · click to enlarge
Page 15

APPENDIX: 11.4 WIRING DIAGRAMS

11.4.1 Control

Dimplex LA16ASR — APPENDIX: 11.4 WIRING DIAGRAMS diagram (page 15)
Fig. 8

Alle Querschnitte 0,75mm2 /2.4 /2.4 /2.4 1 3 5 4 6

Page 16 of the Dimplex LA16ASR user manual — APPENDIX: 11.4 WIRING DIAGRAMS
Page 16 · click to enlarge
Page 16

APPENDIX: 11.4 WIRING DIAGRAMS

11.4.2 Load

Dimplex LA16ASR — APPENDIX: 11.4 WIRING DIAGRAMS diagram (page 16)
Fig. 9
Page 17 of the Dimplex LA16ASR user manual — Klemmenplan und Steckverbinderbelegung im reversiblen Luft/Wasser-Außengerät LA 16 ASR
Page 17 · click to enlarge
Page 17

APPENDIX: 11.4 WIRING DIAGRAMS

11.4.3 Terminal Diagram

Dimplex LA16ASR — APPENDIX: 11.4 WIRING DIAGRAMS diagram (page 17)
Fig. 10

Terminal connection diagram and connector assignment in the reversible air-to-water outdoor unit

Klemmenplan und Steckverbinderbelegung im reversiblen Luft/Wasser-Außengerät LA 16 ASR

X1 PE L1 L2 L3

Page 18 of the Dimplex LA16ASR user manual — APPENDIX: 11.4 WIRING DIAGRAMS
Page 18 · click to enlarge
Page 18

APPENDIX: 11.4 WIRING DIAGRAMS

11.4.4 Legend

E1 Crankcase heater, compressor E2 Fan for nozzle ring heater E3 Defrost end pressostat E4 Condensing pressure pressostat

F2 High-pressure pressostat F3 Low-pressure pressostat F5 Thermostat HG F23 Winding shield, fan

K1 Compressor contactor K2 Fan contactor

M1 Compressor M2 Fan

N1 Heat pump controller N3 Soft start control

R9 Frost protection sensor for heating water R10 Heating water return flow sensor R11 Coding resistor (5k6)

X1 Terminal strip: load terminal X2 Terminal strip: internal wiring X3 Terminal strip: heaters X4 Plug connector, heat pump controller X5 Plug connector, control lead X6 Plug connector, control lead X7 Plug connector, heat pump

Y1 4-way reversing valve

Page 19 of the Dimplex LA16ASR user manual — APPENDIX: 11.5 HYDRAULIC BLOCK DIAGRAM
Page 19 · click to enlarge
Page 19

APPENDIX: 11.5 HYDRAULIC BLOCK DIAGRAM

Hydraulic Block Diagram

Dimplex LA16ASR — APPENDIX: 11.5 HYDRAULIC BLOCK DIAGRAM diagram (page 19)
Fig. 11

2nd heating circuit return sensor Swimming pool pump

Page 20 of the Dimplex LA16ASR user manual — LA 16ASR
Page 20 · click to enlarge
Page 20

APPENDIX: 11.6 EC DECLARATION OF CONFORMITY

EC Declaration of Conformity

Dimplex LA16ASR — APPENDIX: 11.6 EC DECLARATION OF CONFORMITY diagram (page 20)
Fig. 12

Declaration of Conformity

KKW Kulmbacher Klimageräte-Werk GmbH, Geschäftsbereich Dimplex Am Goldenen Feld 18 D-95326 Kulmbach

hereby confirm that the design and construction of the product(s) listed below, in the version(s) placed on the market by us, conform to the relevant requirements of the applicable EC directives.

This declaration becomes invalidated if any modifications are made to the product(s) without our prior authorization.

Designation of the product(s): EC Directives: Air-to-water heat pumps EC Directive for Low Voltage for outdoor installation, (73/23/EEC) containing R404A EC Directive for Electromagnetic Compatibility (EMC) (89/336/EEC) Pressure Equipment Directive (97/23/EEC)

Type(s)Harmonized EN Standards:

LA 16ASR

Requirements of category II

Order No.: National Standard/Directives:

Kulmbach, 25.07.2003

General Manager Technical Director

The undersigned · 342 070

Page 21 of the Dimplex LA16ASR user manual — Notes
Page 21 · click to enlarge
Page 21

Notes

Page 22 of the Dimplex LA16ASR user manual — Notes
Page 22 · click to enlarge
Page 22

Notes

Page 23 of the Dimplex LA16ASR user manual — Notes
Page 23 · click to enlarge
Page 23

Notes

Page 24 of the Dimplex LA16ASR user manual — Notes
Page 24 · click to enlarge
Page 24

KKW Kulmbacher Klimageräte-Werk GmbH Technical data subject to change without notice Geschäftsbereich Dimplex Fax +49 (0) 92 21 709-589 Am Goldenen Feld 18 www.dimplex.de D-95326 Kulmbach

Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the Dimplex LA16ASR

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Dimplex LA16ASR

Be the first to ask — other owners or our team will answer.

Original document

Dimplex LA16ASR manual PDF

24 pages·3 MB·Heat Pump·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…