NATURAL GAS “VICTORIAN” MODEL (V)V36EN,
(V)V42EN SERIES PROPANE/LP GAS “VICTORIAN” MODEL (V)V36EP,
(V)V42EP SERIES
FOR YOUR SAFETY Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
— Installation and service must be performed by a qualified installer, service agency, or the gas supplier.
— This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.
This appliance may be installed in an aftermarket* manufactured (mobile) home, where not prohibited by state or local codes.
*Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer.
Save this manual for future reference. Save this manual for future reference.



PRODUCT IDENTIFICATION
5. This fireplace reaches high temperatures. Keep children and adults away from hot surfaces to avoid burns or clothing igni- tion. Fireplace will remain hot for a time after shutdown. Al- low surfaces to cool before touching. 6. Carefully supervise young children when they are in the room with fireplace. 7. Do not modify this fireplace under any circumstances. Any parts removed for servicing must be replaced prior to operat- ing fireplace. 8. Turn fireplace off and let cool before servicing, installing, or repairing. Only a qualified service person should install, ser- vice, or repair this fireplace. Have fireplace inspected annu- ally by a qualified service person. 9. You must keep control compartments, burners, and circulat- ing air passages clean. More frequent cleaning may be needed due to excessive lint and dust from carpeting, bedding mate- rial, etc. Turn off the gas valve and pilot light before cleaning fireplace. 10. Have venting system inspected annually by a qualified service person. If needed, have venting system cleaned or repaired. See Cleaning and Maintenance, page 27. 11. Keep the area around your fireplace clear of combustible ma- terials, gasoline, and other flammable vapor and liquids. Do not run fireplace where these are used or stored. Do not place items such as clothing or decorations on or around fireplace. 12. Do not use this fireplace to cook food or burn paper or other objects. 13. Do not use any solid fuels (wood, coal, paper, cardboard, etc.) in this fireplace. Use only the gas type indicated on fireplace nameplate. 14. This appliance, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70, or the Ca- nadian Electrical Code, CSA C22.1. 15. Do not use fireplace if any part has been exposed to or under water. Immediately call a qualified service person to arrange for replacement of the unit. 16. Do not operate fireplace if any log is broken. 17. Do not use a blower insert, heat exchanger insert, or other ac- cessory not approved for use with this fireplace. 18. Do not operate fireplace with glass door removed, cracked, or broken. 19. Provide adequate clearances around air openings.

ON/OFF/REMOTE Switch (Optional Installation)
Blower Switch (Optional Installation)
Figure 1 - Victorian Direct-Vent Fireplace with Electronic Ignition
LOCAL CODES Install and use fireplace with care. Follow all local codes. In the absence to local codes, use the current National Fuel Gas Code ANSI Z223.1/NFPA 54* (USA) or the current CSA-B149.1 Instal- lation Code (Canada). *Available from: American National Standards Institute, Inc.
1430 Broadway New York, NY 10018 National Fire Protection Association, Inc.
Batterymarch Park Quincy, MA 02269
108862-01D For more information, visit www.desatech.com For more information, visit www.desatech.com



Determine the safest and most efficient location for your DESA International direct-vent fireplace. Make sure that rafters and wall studs are not in the way of the venting system. Choose a location where the heat output is not affected by drafts, air conditioning ducts, windows or doors. Figure 2 shows some common locations. Be aware of all restrictions and precautions before deciding the exact location for your fireplace and termination cap.
Figure 2 - Common Fireplace Locations

Figure 3 - Fireplace Bottom Dimensions
108862-01D For more information, visit www.desatech.com For more information, visit www.desatech.com
Corner installation


CLEARANCES Minimum clearances to combustibles for the fireplace are as follows: Back, and sides 0"/mm Perpendicular walls 6" (152mm) Floor 0"/mm Ceiling to louver opening 42" (1067mm) Front 36" (914mm) Top 0"/mm Vent (See venting instructions for specific venting clearances.) Combustible material with a maximum thickness of 5/8" may be flush with the top front of fireplace .

36" Models 42" Models A 35 3/4" 41 5/8" B 15" 21 5/8" C 49 5/8" 58 1/2" D 10 3/8" 13 1/2" E 13 3/4" 16 3/4" F 41" 48" G 41 1/4" 48 1/4" H 68 1/2" 81 1/2"
NOTICE: This fireplace is intended for use as supple- mental heat. Use this fireplace along with your pri- mary heating system. Do not install this fireplace as your primary heat source. If you have a central heat- ing system, you may run system’s circulating blower while using fireplace. This will help circulate the heat throughout the house. In the event of a power outage, you can use this fireplace as a heat source.
Figure 5 - Framing Clearances for Corner Installation
FRAMING AND FINISHING Figure 4 shows typical framing of this fireplace. Figure 5 shows framing for corner installation. All minimum clearances must be met.
For available accessories for this fireplace, see Accessories on page 31. If you are using a separate combustible mantel piece, refer to Figure 6 for proper installation height. You can install noncombus- tible mantels at any height above the fireplace. Note: Noncombus- tible mantels may discolor!
B
D
E
F
36" Models 42" Models A 36 1/8" 40 1/8" B 41 1/4" 48 1/4" C 23 1/2" 25 5/8"
Top of Louver Opening
Ref. Mantel Depth Ref. Mantel from Top
of Louver Opening 1 14" (356mm) A 16" (406mm) 2 12" (305mm) B 14" (356mm) 3 10" (254mm) C 12" (305mm) 4 8" (203mm) D 10" (254mm) 5 6" (152mm) E 8" (203mm) 6 4" (101mm) F 6" (152mm) 7 2" (51mm) G 4" (101mm)
B C
Figure 4 - Framing Clearances for Installation Against an Exterior Wall
Figure 6 - Clearances for Combustible Mantels
108862-01D For more information, visit www.desatech.com For more information, visit www.desatech.com
Nailing Tabs · Wall



TERMINATION CAP AIR SUPPLY INLET GAS METER RESTRICTED AREA (TERMINATION PROHIBITED) A = clearance above grade, veranda, porch, deck, or balcony
I = clearance to service regulator vent outlet [*72 inches (1829mm)
[*12 inches (305mm) minimum] B = clearance to window or door that may be opened
minimum] J = clearance to non-mechanical air supply inlet to building or the
[12 inches (305mm) minimum] C = clearance to permanently closed window [minimum 12 inches
combustion air inlet to any other fireplace [*12 inches (305mm) minimum] K = clearance to a mechanical air supply inlet [*72 inches (1829mm)
(305mm) recommended to prevent condensation on window] D = vertical clearance to ventilated soffit located above the terminal
minimum] L = † clearance above paved side-walk or a paved driveway located on
within a horizontal distance of 24 inches (610mm) from the center-line of the terminal [18 inches (457mm) minimum] E = clearance to unventilated soffit [12 inches (305mm) minimum] F = clearance to outside corner (see below) G = clearance to inside corner (see below) H = *not to be installed above a meter/regulator assembly within
public property [*84 inches (2133mm) minimum] M = clearance under veranda, porch, deck [*12 inches (305mm) minimum ‡] N = clearance above a roof shall extend a minimum of 24 inches (610mm)
above the highest point when it passes through the roof surface and any other obstruction within a horizontal distance of 18 inches (457mm)
36 inches (914mm) horizontally from the center-line of the regulator
† vent shall not terminate directly above a side-walk or paved driveway which is located between two
single family dwellings and serves both dwellings* ‡ only permitted if veranda, porch, deck or balconey is fully open on a minimum of 2 sides beneath the floor* * as specified in CAN/CSA B149 (.1 or .2) Installation Codes (1991) for Canada and U.S.A. Note: Local codes or regulations may require different clearances
Termination Clearances for Buildings with Combustible and Noncombustible Exteriors
Outside Corner Recessed Location


Balcony with No Side Wall
Balcony with Perpendicular Side Wall

recessed location D = Minimum width for back wall of
recessed location - Combustible - 38" (965mm) Noncombustible - 24" (610mm) E = Clearance from corner in
Combustible & Noncombustible H = 24" (610mm) J = 20" (508mm)
recessed location- Combustible - 6" (152mm) Noncombustible - 2" (51mm)
G = 12" (305mm) minimum clearance
Figure 7 - Minimum Clearances for Termination Cap
108862-01D For more information, visit www.desatech.com For more information, visit www.desatech.com
Inside Corner


These models are tested and approved for use with DESA Interna- tional (direct-vent) pipe components and terminations.
The venting system must terminate on the outside of the structure and can not be attached to a chimney or flue system serving a separate solid fuel or gas burning appliance. A direct-vent appliance must have its own venting system. DO NOT common vent this appliance.
108862-01D For more information, visit www.desatech.com For more information, visit www.desatech.com



IMPORTANT: Horizontal square terminations require only inner portion of wall firestop. Horizontal installations using round termi- nation require exterior portion of wall firestop available only in vent kit 01491 (see Figure 14, page 10). 1. Set the fireplace in its desired location and determine the route your horizontal venting will take. Do not secure the fireplace until all venting has been installed. Some installations require sliding the fireplace in and out of position to make final vent- ing connections. Figures 14 through 18 on pages 10 through 12 show different configurations for venting with horizontal termination that will help you decide which application best suits your installation. Check to see if wall studs or roof rafters are in the path of your desired venting route. If they are, you may want to adjust the location of the fireplace. 2. Direct vent pipe sections and components are designed with special twist-lock connections. Twist-Lock Procedure: The female ends of the pipes have locking lugs (indentations). These lugs will slide straight into matching slots on the male ends of adjacent pipes. Push pipe sections together and twist one section clockwise approxi- mately one-quarter turn until the sections are fully locked (see Figure 8). Note: Horizontal runs of vent must be sup- ported every three feet. Use wall straps for this purpose. 3. Use a 45° elbow to connect venting system to fireplace flue col- lar. The elbow is designed to be twist-locked onto the flue collar as described in step 2. IMPORTANT: Do not attempt to alter the configuration of the elbow by cutting, twisting, bending, etc. 4. Assemble the desired combination of pipe and elbows to the fireplace flue collar. If there are long portions of venting run, pre-assembled pipe sections may be installed as subassemblies for convenience. 5. Carefully determine the location where the vent pipe assembly will penetrate the outside wall. The center of the hole should line up with the center-line of the horizontal vent pipe. Mark the wall for a 10 3/4" x 10 3/4" square hole. Cut and frame the square hole in the exterior wall where the vent will be terminated. If the wall being penetrated is constructed of noncombustible material, such as masonry block or concrete, a 8 1/2" hole with zero clearance is acceptable (see Figure 9).
Figure 8 - Vent Pipe Connections
Vent Opening Combustible Wall

Figure 9 - Vent Opening Requirements
108862-01D For more information, visit www.desatech.com For more information, visit www.desatech.com
Female Locking Lugs · Male Slots



6. Noncombustible Exterior Wall: Position the horizontal vent cap in the center of the 8 1/2" round hole and attach to the exte- rior wall with four wood screws provided. Before attaching the vent cap to exterior wall, run a bead of non-hardening mastic (pliable sealant) around the outside edges to make a seal be- tween it and the outside wall. Note: The four wood screws provided should be replaced with appropriate fasteners for stucco, brick, concrete, or other types of sidings.
Combustible Exterior Wall: For vinyl siding, stucco, or wood exteriors, a siding standoff must be installed between the vent cap and exterior wall. The siding standoff prevents excessive heat from damaging the siding materials. Siding material must be cut to accommodate standoff. Bolt the vent cap to the stand- off. Apply non-hardening mastic around outside edge of stand- off. Position the standoff/cap assembly in the center of the 10 3/4" square hole and attach to exterior wall with wood screws provided (see Figure 11). The siding standoff must sit flush against the exterior fascia material. 7. Slide the wall firestop over the vent pipe before connecting horizontal run to vent cap (see Figure 12). 8. Carefully move fireplace, with vent assembly attached, toward wall and insert vent pipe into horizontal termination. The pipe overlap should be a minimum of 11/4".
Figure 11 - Installing Siding Standoff

Vent Cap (Horizontal Termination)

Figure 12 - Connecting Vent Cap with Horizontal Vent Pipe
Figure 10 - Installing Horizontal Vent Cap
108862-01D For more information, visit www.desatech.com For more information, visit www.desatech.com





Maintain 1" Minimum Air Space Around Outer Pipe When Penetrating a Wall
Vertical (V) Horizontal (H)
V36 Series 32 3/4" 17" max.
V42 Series 36 3/4" 17" max.
10 3/4" x 10 3/4" Framed Opening

Figure 13 - Typical Horizontal Termination Cap Mounting with Additional Siding Standoff Installed
Figures 14 through 18 show different configurations and alternatives for venting with horizontal termination. Each figure includes a chart with critical minimum and maximum dimensions which MUST be met. IMPORTANT: Remember that a horizontal run of venting must have a 1/4" rise for every 12" of run toward the termination.
Figure 14 - Horizontal Termination Configuration for Square or Round Termination
108862-01D For more information, visit www.desatech.com For more information, visit www.desatech.com
45° Elbow · Horizontal Round Termination


Vertical (V) Required 36" 42" Vertical Pipe Horizontal (H) (36"/42") *43 1/2" min. 46 1/4" min. None 30" max. 54 1/2" min. 57 1/4" min. 1 ft. 48" max. 66 1/2" min. 69 1/4" min. 2 ft. 60" max. 78 1/2" min. 81 1/4" min. 3 ft. 84" max. 90 1/2" min. 93 1/4" min. 4 ft. 20' max.
* Ground Floor Corner Venting


As Required for (V) See Chart for Pipe Section Required
Figure 15 - Horizontal Termination Configuration for Corner Installation Using One 90° Elbow
Snorkel terminations are available for installations requiring a vertical rise on the exterior of the building. If installing snorkel termination below grade, you must provide proper drainage to prevent water from entering snorkel termination (see Figure 16). Do not back fill around snorkel termination.

Figure 16 - Snorkel Termination Configurations for Below Ground Installation
108862-01D For more information, visit www.desatech.com For more information, visit www.desatech.com
Square Termination · Snorkel Termination



The following configurations show the minimum vertical rise requirements for a horizontal system using two 90° elbows.
Vertical (V) Horizontal (H1) Horizontal (H1) +
5' min. 2' max. 6' max. 6' min. 4' max. 12' max. 7' min. 6' max. 18' max. 8' min. 8' max. 20' max. 20' max. 8' max. 20' max.
Figure 17 - Horizontal Termination Configuration for Venting Using Two 90° Elbows

Venting with Two 90° Elbows
Vertical (V) Horizontal (H1) +
Horizontal (H2)
5' min. 6' max. 6' min. 12' max. 7' min. 18' max. 8' min. 20' max. 20' max. 20' max.
Figure 18 - Horizontal Termination Configuration for Venting Using Two 90° Elbows with Termination at 90° with Fireplace
108862-01D For more information, visit www.desatech.com For more information, visit www.desatech.com


2. Assemble the desired lengths of pipe and elbows necessary to reach from the fireplace flue up through the firestop. Be sure all pipe and elbow connections are fully twist-locked (see Fig- ure 8, page 8). 3. Cut a hole in the roof using the locating hole as a center point. (Cover any exposed open vent pipes before cutting hole in roof.) The 10 3/4"x10 3/4" hole must be measured on the horizontal; actual length may be larger depending on the pitch of the roof. There must be a 1" clearance from the vent pipe to combustible materials. Frame the opening as shown in Figure 9, page 8. 4. Connect a section of pipe and extend up through the hole. Note: If an offset is needed to avoid obstructions, you must support the vent pipe every 3 feet. Use wall straps for this purpose (see Figure 19). Whenever possible, use 45° elbows instead of 90° elbows. The 45° elbow offers less restriction to the flow of the flue gases and intake air. 5. Place the flashing over the pipe section(s) extending through the roof. Secure the base of the flashing to the roof and fram- ing with roofing nails. Be sure roofing material overlaps the top edge of the flashing as shown in Figure 19. There must be a 1" clearance from the vent pipe to combustible materials. 6. Continue to add pipe sections until the height of the vent cap meets the minimum building code requirements described in Figure 7 on page 6. Note: You must increase vent height for steep roof pitches. Nearby trees, adjoining rooflines, steep pitched roofs, and other similar factors may cause poor draft or down-drafting in high winds. Increasing the vent height may solve this problem. 7. Twist-lock the vent cap onto the last section of vent pipe. Note: If the vent pipe passes through any occupied areas above the first floor, including storage spaces and closets, you must enclose pipe. You may frame and sheetrock the enclosure with standard construction material. Make sure and meet the minimum allowable clearances to combustibles. Do not fill any of the required air spaces with insulation.
Note: Vertical restrictor must be installed in all vertical installations. 1. Determine the route your vertical venting will take. If ceiling joists, roof rafters, or other framing will obstruct the venting system, consider an offset (see Figure 19) to avoid cutting load bearing members. Note: Pay special attention to these instal- lation instructions for required clearances (air space) to com- bustibles when passing through ceilings, walls, roofs, enclo- sures, attic rafters, etc. Do not pack air spaces with insulation. Also note maximum vertical rise of the venting system and any maximum horizontal offset limitations. 2. Set the fireplace in desired location. Drop a plumb line down from the ceiling to the position of the fireplace exit flue. Mark the center point where the vent will penetrate the ceiling. Drill a small locating hole at this point. Drop a plumb line from the inside of the roof to the locating hole in the ceiling. Mark the center point where the vent will penetrate the roof. Drill a small locating hole at this point.

Figure 19 - Offset with Wall Strap and 45° Elbows
If area above is not a room, install firestop below framed hole. If area above is a room, install firestop above framed hole.
Flat Ceiling Installation 1. Cut a 10 3/4" square hole in the ceiling using the locating hole as a center point. The opening should be framed to 10 3/4"x10 3/4" (273 mm x 273 mm) inside dimensions, as shown in Figure 9 on page 8 using framing lumber the same size as the ceiling joists. If the area above the ceiling is an insulated ceiling or a room, nail firestop from the top side. This prevents loose insula- tion from falling into the required clearance space. Otherwise, install firestop below the framed hole. The firestop should be installed with no less than three nails per side (see Figure 20).

Figure 20 - Installing Firestop
108862-01D For more information, visit www.desatech.com For more information, visit www.desatech.com
Roof Flashing · Wall Strap


Venting with One 90° Elbow
Figures 21 through 24 show four different configurations for verti- cal termination.

Vertical (V) Horizontal (H)
5' min. 2' max. 6' min. 4' max. 7' min. 6' max. 8' min. 8' max. 20' max. 8' max.

5' min. 2' max. 6' min. 4' max. 7' min. 6' max. 8' min. 8' max. 20' max. 8' max.
Figure 22 - Vertical Venting Configuration Using One 90° Elbow (Vertical Round High Wind Termination Shown)

Venting with Two 90° Elbows
Vertical (V1) Horizontal (H)
5' min. 6' max. 6' min. 12' max. 7' min. 18' max. 8' min. 20' max.
Figure 21 - Vertical Venting Configuration Using Two 90° Elbows with Two Horizontal Runs (Vertical Round High Wind Termination Shown)
Figure 23 - Vertical Venting Configuration Using Two 90° Elbows (Vertical Round High Wind Termination Shown)
108862-01D For more information, visit www.desatech.com For more information, visit www.desatech.com



Your DESA International direct-vent fireplace has been CSA tested and approved for elevations from 0-2000 feet (USA) and elevations from 0-4500 feet (Canada) . When installing this fireplace at an elevation above 2000 feet (in the USA), you may need to decrease the input rating by changing the existing burner orifice to a smaller size. Reduce input 4% for each 1000 feet above sea level. Check with your local gas company for proper orifice size identification. When installing this fireplace at an elevation above 4500 feet (in Canada), check with local authorities. Consult your local gas company to help determine the proper orifice for your location. For assistance with any high altitude installation contact DESA International’s Customer Service Department at 1-866-672-6040.
Figure 24 - Vertical Venting Configuration With No Horizontal Run (Vertical Round High Wind Termination Shown)
108862-01D For more information, visit www.desatech.com For more information, visit www.desatech.com


Parts Lists for Venting Kits and Components FIREPLACE INSTALLATION
PARTS LISTS FOR VENTING KITS AND COMPONENTS DESA International (5/8") Pipe & Vent Kits
Number Description 01504 Firestop Plate (4) 01505 Adjustable Roof Flashing 0 to 8/12 - Galvanized (6) 01506 Steep Pitch Flashing 9/12 to 12/12 - Galvanized (6) 01507 Storm Collar - Galvanized (4) 01508 Wall Strap (4) 01514 Combustible Siding Standoff - Galvanized (1) 01607 Wall Firestop - Galvanized (4) VR-58 Vertical Restrictor - Galvanized
Number Description 01492 Horizontal Square Termination Kit Includes: 45° Elbow (Through 5" Wall), Wall Firestop, Horizontal Square Termination 01493 Basic Vertical Termination Kit Includes: Vertical Termination, Adjustable Flashing, Storm Collar 01491 Horizontal Round Termination Kit Includes: Round Termination, Wall Firestop, and 45° Elbow (Through 5" Wall)
01497 12" Section Coaxial Pipe - Galvanized (4) 01498 18" Section Coaxial Pipe - Galvanized (4)
Use proper gas type for the fireplace unit you are installing. If you have conflicting gas types, do not install fireplace. See retailer where you purchased the fireplace for proper fireplace according to your gas type.
01499 24" Section Coaxial Pipe - Galvanized (4)
01500 36" Section Coaxial Pipe - Galvanized (4)
01501 48" Section Coaxial Pipe - Galvanized (4)
01513 6" Section Coaxial Pipe - Galvanized (4) 01606 Adjustable 17"-24" Section Coaxial Pipe - Galvanized (4)
F8030 Adjustable 7"-12" Section Coaxial Pipe - Galvanized (6)
D1032 Adjustable 7"-12" Section Coaxial Pipe - Galvanized (1)
01502 45° Elbow - Galvanized (4)
01503 90° Elbow - Galvanized (4)
Model BK Installation
01494 Vertical Round Termination - Galvanized (1)
Follow all instructions provided in the blower accessory kit. 1. Attach the power cord to the blower motor by firmly pushing the two female terminals at the end of the power cord onto the two spade terminals on the blower motor (see Figure 25, page 17). 2. Attach green ground wire from power cord to blower hous- ing using screw provided (see Figure 25, page 17). Tighten screws securely. 3. Place the blower against the lower rear wall of the firebox outer wrapper with the exhaust port directed upward. The blower will fit inside the back opening and be held in position against the back wall by the magnets (see Figure 25, page 17).
01495 Horizontal Round Termination - Galvanized (1)
01496 Horizontal Square Termination - Galvanized (1) 01798 Vertical Round High Wind Termination (1) 01800 Horizontal Square High Wind Termination (1) 01801 14" Snorkel Termination - Galvanized (1)
01802 36" Snorkel Termination - Galvanized (1)
108862-01D For more information, visit www.desatech.com For more information, visit www.desatech.com
Number Description · Number Description


4. Be certain that all wire terminals are securely attached to ter- minals on blower motor and that the screw retaining the green ground wire is tight. 5. Mount speed control box to switch bracket by placing the plastic control shaft forward through the opening in the switch bracket (see Figure 26). 6. While supporting speed control, secure control shaft with lock nut by pushing and turning lock nut with pliers clockwise until it is tight against front panel. Place control knob provided on shaft. 7. Turn on power to duplex outlet if previously turned off per the warning in column 2, page 16. 8. Plug in blower power cord. a. If your firebox is installed as a freestanding unit with an

Duplex Outlet (Located underneath firebox floor against lower right outside wall)
accessory mantel, determine whether the power cord will exit the left side or the right side of the firebox. Route power cord through exit hole and plug the power cord into a wall receptacle near the firebox. b. If your firebox installation is recessed and/or pre-wired,
plug the power cord into the duplex outlet provided. Refer to your firebox owner’s manual for instructions on wiring the duplex outlet.
Figure 27 - Location of Wiring Diagram Decal (Model May Vary From Illustration)

108862-01D For more information, visit www.desatech.com For more information, visit www.desatech.com
Speed Control · Control Knob


Note: When installing the BKT thermostatically-controlled blower, you must first secure the thermal switch bracket to the blower if it has not already been factory installed. 1. Place the green ground wire with ring terminal between the bottom hole on the thermal switch bracket and the top ear hole on the blower assembly. Insert the phillips screw into all three pieces and tighten securely (see Figure 28, page 18). 2. Connect wire harness and power cord terminals. Connect the blue jumper wire to the blower motor terminal and the right side terminal of the thermal switch. Connect the black wire to the left side of the thermal switch and the white wire to the other remaining blower motor terminal.
5. Mount the speed control box against the mounting plate pro- vided in the lower fireplace cavity by placing the plastic control shaft forward through the round hole (see Figure 26, page 17). 6. While supporting speed control, secure control shaft with lock nut by pushing and turning lock nut with pliers clockwise un- til it is tight against mounting plate. Place control knob pro- vided on shaft (see Figure 26, page 17). 7. Check to make sure that the power cord is completely clear of the blower wheel and that there are no other foreign objects in blower wheel. Also double check all wire leads and make sure wire rout- ing is not pinched or in a precarious position. Correct accordingly. 8. Turn on power to duplex outlet if previously turned off per the warning in column 2, page 16. 9. Plug in blower power cord to duplex outlet. 10. The blower will only run when the speed control knob is in the ON position and the thermal switch senses temperature after the fireplace begins to heat up. The blower speed can be ad- justed by rotating the control knob. To turn off, turn knob fully counterclockwise until it clicks off. If the blower is ON and has been running with the fireplace operating, the blower will continue to run for a short time after the fireplace has been turned off. As the thermal switch cools down, the blower shuts down automatically. 11. Peel off the backing paper and stick the supplied wiring dia- gram decal on the firebox bottom approximately 12" in front of the blower (see Figure 27, page 17). .
Note: The power cord outer insulation sleeve may have to be stripped slightly to allow enough wire length to reach and make all connections. DO NOT trim excessive length away. Just enable enough to make all connections securely. 3. Place the blower against the lower rear wall of the firebox outer wrapper with the exhaust port directed upward and the thermodisc positioned up near the fireplace bottom. The thermodisc must be oriented near the fireplace bottom as shown in Figure 28 in order to sense temperature and properly operate. The blower will be held in position against the back wall by the magnets incorpo- rated onto the blower housing (see Figure 28). 4. Be certain that all wire terminals are securely attached to ter- minals on blower motor and thermal switch, and that the screw for the thermodisc bracket and green ground wire is tight.


Variable Fan Switch Fan Switch

Route BKT Blower Through This Area
Blower Location Side View Firebox Bottom
Figure 29 - Blower Wiring Diagram for Thermostat-Controlled Models
Figure 28 - Blower Model BKT
108862-01D For more information, visit www.desatech.com For more information, visit www.desatech.com




Installation must include an equipment shutoff valve, union, and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from fireplace (see Figure 31).
Check your building codes for any special requirements for locating equipment shutoff valve to fireplaces.
Apply pipe joint sealant lightly to male NPT threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged fireplace valves.
We recommend that you install a sediment trap/drip leg in supply line as shown in Figure 31. Locate sediment trap/drip leg where it is within reach for cleaning. Install in piping system between fuel supply and fireplace. Locate sediment trap/drip leg where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into fireplace gas con- trols. If sediment trap/drip leg is not installed or is installed wrong, fireplace may not run properly.
* A CSA design-certified equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Purchase the CSA design-certified equipment shutoff valve from your retailer.
For propane/LP connection only, the installer must supply an external regulator. The external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 11 and 14 inches of water. If you do not reduce incoming gas pressure, fireplace regulator damage could occur. Install external regulator with the vent pointing down as shown in Figure 31. Pointing the vent down protects it from freezing rain or sleet.
CSA Design-Certified Equipment Shutoff Valve with 1/8" NPT Tap*
Natural - From Gas Meter (5.5" W.C. to 10.5" W.C. Pressure) Propane/LP From External Regulator (11" W.C. to 14" W.C. Pressure)
Approved Flexible Gas Line
Propane/LP Supply Tank External Regulator
Cap Pipe Nipple Tee Joint
Figure 31 - Gas Connection
* The CSA design-certified equipment shutoff valve may be sup- plied with the appliance or you can purchase it from your retailer.
Figure 30 - External Regulator with Vent Pointing Down (Propane/LP Only)
108862-01D For more information, visit www.desatech.com For more information, visit www.desatech.com


Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa) 1. Close equipment shutoff valve (see Figure 33). 2. Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas fireplace or opening main gas valve located on or near gas meter for natural gas fire- place, or using compressed air. 3. Check all joints from propane/LP supply tank or gas meter to equipment shutoff valve (see Figure 34 for propane/LP or Figure 35 for natural gas). Apply noncorrosive leak detection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.
Red Surface Indicates For Propane/LP Use Only


1/2" NPT Incoming Gas Line Inlet Pressure Tap Outlet Pressure Tap
Figure 32 - Connecting Flexible Gas Line to Electronic Valve
Figure 34 - Checking Gas Joints for Propane/LP Gas Fireplace
Test Pressures In Excess Of 1/2 PSIG (3.5 kPa) 1. Disconnect fireplace and its individual equipment shutoff valve from gas supply piping system. Pressures in excess of 1/2 psig (3.5 kPa) will damage fireplace gas regulator. 2. Cap off open end of gas pipe where equipment shutoff valve was connected. 3. Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas fireplace or opening main gas valve located on or near gas meter for natural gas fire- place, or using compressed air.
Figure 35 - Checking Gas Joints for Natural Gas Fireplace
108862-01D For more information, visit www.desatech.com For more information, visit www.desatech.com
Equipment Shutoff Valve · Gas Meter · Gas Valve


Pressure Testing Fireplace Gas Connections 1. Open equipment shutoff valve (see Figure 33, page 20). 2. Open propane/LP supply tank valve for propane/LP fireplace or main gas valve located on or near gas meter for natural gas fireplace. 3. Make sure control knob of fireplace is in the OFF position. 4. Check all joints from equipment shutoff valve to gas valve (see Figure 34 for propane/LP or Figure 35 for natural gas, page 20). Apply noncorrosive leak detection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once. 5. Light fireplace (see Operating Fireplace, pages 25 and 26). Check all other internal joints for leaks. 6. Turn off fireplace (see To Turn Off Gas to Appliance, page 25).
If replacement of glass is necessary, the entire assembly, glass and frame, must be replaced. If glass is broken, wear gloves and tape the remaining fragments onto the frame. 1. Remove screen assembly by pushing the rod either left or right and then down and forward to remove screen/rod assembly from the firebox. Set assembly aside. 2. Lift up on latches to unlock. There are two on top of firebox and two below firebox that hold glass door in place (see Figure 37). 3. While holding glass door to prevent it from falling and caus- ing injury, remove the five screws from the hinge located on the left side of door frame assembly (see Figure 37). 4. Remount the new frame at the hinge with five new screws before closing door. This will ensure seating of the gasket. 5. Close glass door frame. Lock latches by placing the bar under the tab on door and pushing down and back on latch (see Figure 37). 6. Replace screen/rod assembly by reversing step 1. 7. Replace louvers by reversing procedure under Removing Lou- ver Panels.

Remove the top and bottom louver panels by simultaneously pulling both top end spring latches towards the center of the appliance until they are disengaged from the locating holes (see Figure 36). Repeat for bottom spring latches and pull the louvers outward. To install or replace items removed, simply reverse the procedures above.
Figure 37 - Removing/Replacing Glass Door
See Cleaning and Maintenance on page 27.
Figure 36 - Removing Louver Panel
108862-01D For more information, visit www.desatech.com For more information, visit www.desatech.com


Installing Optional Brick Liner Models BL36D(S), BL36DH(S), BL42D(S), BL42DH(S)
This brick liner kit is optional. You may purchase brick liner from your local retailer or see Accessories, page 31.

1. Remove top and bottom louvers to allow access to door latches. 2. Remove screen, unlock door latches and open glass door. See Removing/Replacing Glass Door, steps 1 and 2, page 21. 3. If installing brick liner in new fireplace, go to step 4. If install- ing brick liner in an existing fireplace, carefully remove logs, lava rock, and ember material. 4. Remove three screws from deflector shield on the inside top of firebox. Set shield and screws aside. 5. Install rear brick panel first. Rest bottom edge of panel on back edge of grate (see Figure 38). 6. Install top brick panel by resting on the top of the rear panel. Hold the top brick panel in place and install left side brick panel by sliding it between the grate and the side of the fire- box, securing top panel (see Figure 39). 7. Install the right brick panel using the same method described in step 6 for left brick panel. 8. Replace deflector shield using screws removed in step 4.
Figure 39 - Installing Left Side and Top Brick Panels
Each log is marked with a number. These numbers will help you identify the log when installing. It is very important to install these logs exactly as instructed. Do not modify logs. Only use logs supplied with fireplace.
Open louvers, remove screen, unlock door latches, and open glass door. See Removing/Replacing Glass Door, steps 1 and 2, page 21. Install logs according to instructions for fireplace model numbers. 1. Place log #1 (base log) onto pin on left front side of grate as shown in Figure 40.


Figure 38 - Installing Rear Brick Panel
Figure 40 - Installing Log No. 1
108862-01D For more information, visit www.desatech.com For more information, visit www.desatech.com


FIREPLACE INSTALLATION Installing Logs, Lava Rock, and Glowing Embers
2. Rest left side of log #2 (front log) onto top of log #1. Place right side of log onto second pin located on right side of grate (see Figure 41). 3. Place log #3 (rear log) onto pins on rear of grate as shown in Figure 42. 4. Place log #4 (crossover log) onto pins from both logs #2 and #3 as shown in Figure 43. 5. Place log #5 (top log) onto right pin of front log (#2) and the smooth surface of crossover log (#4) as shown in Figure 44. Make sure it is seated properly. 6. Place log #6 (left log) onto left pin of front log (#2) and the smooth surface of rear log (#3) as shown in Figure 45. Make sure it is seated properly. 7. For (V)V42 series only, place log #7 onto right pin of top log (#5) as shown in Figure 45. Make sure it is seated properly 8. Place lava rock along sides and front of firebox bottom in ar- eas that are visible only. It is not necessary to use all of the lava rock provided.
9. Pull ember material apart into pieces no larger than a dime. Place these pieces loosely and sparingly directly onto the ex- posed section of the front burner and along the space between the burner and grate prongs (see Figure 46). This will create the glowing ember appearance as the flame touches the ember material. Do not block air slots by using too much ember ma- terial in one area. It is not necessary to use all of the ember material provided. 10. Close glass door, lock door latches, replace screen, and close louvers (see Removing/Replacing Glass Door, steps 5 through 7, page 21).


Figure 44 - Installing Log No. 5

Figure 41- Installing Log No. 2

Figure 45 - Installing Log No. 6 (36" and 42" Series) and Log No. 7 (42" Series Only)
Figure 42 - Installing Log No. 3
Figure 43 - Installing Log No. 4
Ember Material Figure 46 - Placing Ember Material on Burner
108862-01D For more information, visit www.desatech.com For more information, visit www.desatech.com
42" Series Only


Wall Switch Installation Optional Remote Control Installation WIRING DIAGRAM
The installation of a wall switch allows you to activate the gas control valve and turn the fireplace on and off. The wall switch is to be connected to the incoming 120 volt regular household wiring that supplies the electricity to the fireplace. Refer to wiring diagram below.

Note: If using optional wireless hand-held remote control, the wall switch must be in the ON position to be operational. The remote control then becomes the switching mechanism for fireplace operation. 1. Open lower louver panel. 2. The WRC model receiver does not require a battery. The re- ceiver can be installed by first plugging the short extension cord into the fireplace receptacle. Then plug the receiver unit into the extension cord. Finally plug the ignition module plug into the receiver unit (see Figure 47). 3. Activate the remote handset battery by removing the insulat- ing tab on the back of the handset (see Figure 48). The battery is included pre-installed. 4. Once the battery is activated the unit is ready to use. 5. Close lower louver panel.
Pull to Remove Insulation Tab
Figure 48 - Installing Battery into Back of Handset

108862-01D For more information, visit www.desatech.com For more information, visit www.desatech.com




Figure 49 - Turning Equipment Shutoff Valve to the OFF Position
TO APPLIANCE 1. Turn off the wall switch. 2. Turn off all electric power to the appliance if service is to be performed. 3. Open lower louver panel. 4. Remove front hearth brick and control access panel. 5. Turn equipment shutoff valve clockwise Clockwise to OFF. Do not force. 6. Close lower louver panel.

Sensing Rod Pilot Burner
1. STOP! Read the safety information, above. 2. Turn off all electric power to the appliance. 3. Turn wall switch to the OFF position. 4. Open lower louver panel. 5. Turn equipment shutoff valve clockwise Clockwise to the OFF position (see Figure 49). Do not force. 6. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Fol- low “B” in the safety information above. If you don’t smell gas, go to the next step. 7. Turn equipment shutoff valve counterclockwise C-clockwise to the ON position. Do not force. 8. Close lower louver panel. 9. Turn on all electric power to the appliance. 10. Turn the wall switch to the ON position.
Figure 50 - Pilot
OPERATION
Note: The WRC receiver and hand-held remote control kit must be purchased separately (see Accessories, page 31). Follow installation instructions on page 24. 1. Turn equipment shutoff valve to ON position. You can now turn the burner on and off with the hand-held remote control unit. IMPORTANT: Be sure to press the ON/OFF buttons on the hand-held remote control unit for up to 3 seconds to assure proper operation. 2. Press the ON/OFF button to turn the burner on and off.
108862-01D For more information, visit www.desatech.com For more information, visit www.desatech.com
Adjustment Screw · Equipment Shutoff Valve · Ignitor


INSPECTING BURNERS Check pilot flame pattern and burner flame patterns often.
OPERATING OPTIONAL
BLOWER ACCESSORY
The pilot assembly is factory preset for the proper flame. Alterations may have occurred during shipping and handling. The pilot is located on the back right hand side of the burner.
Locate the blower controls by opening the lower louver panel on the fireplace. Blower controls are located on the left side of the switch bracket to the left just inside the louver panel.
The flame must envelope 1/4" of top of the ignitor/sensor and grounding stem.
The BK manual blower and the BKT thermostatically-con- trolled blower have an ON setting and an OFF setting. The blower will only run when the switch is in the ON position. In the OFF position, the blower will not operate.
Note for BKT Only: If you are using BKT blower with optional thermostat (wall mounted or remote control) for the fireplace, your fireplace and blower will not turn on and off at the same time. The fireplace may run for several minutes before the blower turns on. After the heater modulates to the pilot position, the blower will continue to run. The blower will shut off after the firebox temperature decreases.
The blower helps distribute heated air from the fireplace. Periodically check the louvers of the firebox and remove any dust, dirt, or other obstructions that will hinder the flow of air.
Figure 51 - Correct Pilot Flame Pattern
Burner flames will be steady; not lifting or floating. Flame patterns will be different from unit to unit and will vary depending on installation type and weather conditions.
If the vent configuration is installed incorrectly, the flames will lift or "ghost". This can be dangerous. Inspect the flames after installa- tion to ensure proper installation and performance.
Figure 52 shows a typical flame pattern for (V)V36E and (V)V42E series models.
Figure 52 - Typical Flame Pattern for (V)V36E and (V)V42E Series Models
108862-01D For more information, visit www.desatech.com For more information, visit www.desatech.com
Pilot Burner · Sensing Rod · Ignitor/Sensor



Use only the tempered glass door replacement intended for this fireplace (see Replacement Parts, page 30 for detail on ordering). No substitutions may be made. See Removing/Replacing Glass Door, page 21 for instructions for replacing glass door.

Glass must be cleaned periodically. During start-up it is normal for condensation to form on the inside of the glass causing lint, dust, and other airborne particles to cling to the glass surface. During initial start-up a slight film may form on the glass due to paint curing. The glass should be cleaned several times with a non-ammonia, non- abrasive household cleaner and warm water after the first two weeks of operation. Thereafter, clean the glass two or three times during each heating season, depending on the usage and circumstances present. Refer to Removing/Replacing Glass Door on page 21 of this manual when removing glass door for cleaning.
VENTING SYSTEM Conduct annual inspection of the venting system following these guidelines: 1. Check areas of venting system that are exposed to the weather for corrosion (rust spots or streaks and, in extreme cases, holes). Have these items replaced immediately by a qualified service person. 2. Remove the vent cap and shine a flashlight into the vent. Re- move any foreign material. 3. Check for evidence of excessive condensation. Continuous condensation can cause corrosion of caps, pipes, and fittings and can be caused by having excessive lateral runs, too many elbows, or exterior portions of the system being exposed to cold weather. 4. Inspect joints to verify that no pipe section or fitting has been disturbed and loosened. Check mechanical supports such as wall straps for rigidity.

If glass has been broken, carefully remove glass door (see Remov- ing/Replacing Glass Door, page 21). Vacuum all glass pieces with a shop vac.
108862-01D For more information, visit www.desatech.com For more information, visit www.desatech.com


The two most common causes of a malfunctioning gas appliance are: 1. Loose wiring connections 2. Construction debris clogging the pilot and/or gas control valve filter
POSSIBLE CAUSE
REMEDY
Ignitor will not spark or pilot will not light
1. Check to see if you have gas supply and that equipment shutoff valve is opened 2. Repeat lighting procedure several times to purge all air out of lines. If after re- peated attempts appliance does not light, call for qualified service and repair. 3. Remove debris and dirt, inspect and clean any other possible obstructions 4. Contact your gas supplier to check pressure 5. Have a qualified technician replace pi- lot line 6. Replace control valve (Refer to Replace- ment Parts, page 30) 7. Check that main power is on and that all wire connections are made correctly to the ignition model (see Wiring Diagram, page 24). Check for 24 VAC at the sec- ondary side of the transformer. If 24 VAC is present, and the module does not oporate, have the module replaced oth- erwise have the transformer replaced. 8. Open vent damper until fully locked in OPEN position
Pilot will not stay lit
No gas to burner, although wall switch and valve are set to the ON position
108862-01D For more information, visit www.desatech.com For more information, visit www.desatech.com
Frequent pilot outage



POSSIBLE CAUSE
REMEDY
Fireplace produces a clicking/ticking noise just after burner is lit or shut off
Slight smoke or odor during initial operation
Gas odor even when control knob is in OFF position
Gas odor during combustion
Dark residue on logs or inside of fireplace
108862-01D For more information, visit www.desatech.com For more information, visit www.desatech.com
Glass soots


SERVICE HINTS
You may feel your gas pressure is too low. If so, contact your local gas supplier.
You may have further questions about installation, operation, or troubleshooting. If so, contact DESA International’s Customer Service Department at 1-866-672-6040. When calling, please have your model and serial numbers of your heater ready.
You can also visit DESA International’s technical service web site at www.desatech.com.
(V)V36EN Series (V)V42EN Series (V)V36EP Series (V)V42EP Series
Btu 22,000/31,000 Btu/hr 25,000/35,000 Btu/hr 21,000/30,000 Btu/hr 23,000/33,000 Btu/hr
Gas Type Natural Natural Propane/LP Propane/LP
Ignition Electronic
Manifold Pressure 3.5" w.c. 3.5" w.c. 10.0" w.c. 10.0" w.c.
Minimum Inlet Supply Pressure 5.5" w.c. 5.5" w.c. 11.0" w.c. 11.0" w.c.
Fireplace (Actual size of firebox. Measurements do not 36" x 41" x 21 1/8" 40" x 48" x 23 1/2" 36" x 41" x 21 1/8" 40" x 48" x 23 1/2" include nailing flanges or 914 x 1041 x 537 mm 1016 x 1219 x 599 mm 914 x 1041 x 537 mm 1016 x 1219 x 599 mm standoffs).
Carton 38" x 44" x 22" 41" x 51" x 24" 38" x 44" x 22" 41" x 51" x 24" 965 x 1118 x 559 mm 1041 x 1295 x 610 mm 965 x 1118 x 559 mm 1041 x 1295 x 610 mm
Fireplace 120 lbs/55 kg 145 lbs/55 kg 120 lbs/55 kg 145 lbs/55 kg Shipping 123 lbs/56 kg 148 lbs/56 kg 123 lbs/56 kg 148 lbs/56 kg
*For refractory lined models add 60 pounds for 36" models and 70 pounds for 42" models.
108862-01D For more information, visit www.desatech.com For more information, visit www.desatech.com
Dimension, Inches/mm (HxWxD) · Weight, lbs/kg*


LOUVER TRIM KIT (Rolled Louvers Only) (Not Shown) LT36B - 36" Rolled Louver Trim Kit - Brushed Brass LT36P - 36" Rolled Louver Trim Kit - Platinum LT36PB - 36" Rolled Louver Trim Kit - Polished Brass LT42B - 42" Rolled Louver Trim Kit - Brushed Brass LT42P - 42" Rolled Louver Trim Kit - Platinum LT42PB - 42" Rolled Louver Trim Kit - Polished Brass
Purchase these fireplace accessories from your local retailer. If they can not supply these accessories, call DESA International’s Sales Department at 1-866-672-6040. for information. You can also write to the address listed on the back page of this manual.
BRICK LINER (Not Shown) BL36D - 36" Textured Refractory Brick Liner Kit BL36DS - 36" Standard Refractory Brick Liner Kit BL36DH - 36" Textured Refractory Herringbone Brick Liner Kit BL36DHS - 36" Standard Refractory Herringbone Brick Liner Kit BL42D - 42" Textured Refractory Brick Liner Kit BL42DS - 42" Standard Refractory Brick Liner Kit BL42DH - 42" Textured Refractory Herringbone Brick Liner Kit BL42DHS - 42" Standard Refractory Herringbone Brick Liner Kit
DEFLECTION HOODS (Not Shown) HD36 - 36" Hood - Black (2" Brow) HD42 - 42" Hood - Black (2" Brow)
PERIMETER TRIM KIT (Not Shown) PT36 - 36" Perimeter Trim Kit - Black PT36B - 36" Perimeter Trim Kit - Brushed Brass PT36P - 36" Perimeter Trim Kit - Platinum PT36PB - 36" Perimeter Trim Kit - Polished Brass PT42 - 42" Perimeter Trim Kit - Black PT42B - 42" Perimeter Trim Kit - Brushed Brass PT42P - 42" Perimeter Trim Kit - Platinum PT42PB - 42" Perimeter Trim Kit - Polished Brass
This brick liner adds a touch of style to your direct-vent fireplace. Complete installation and operation instructions included in this manual.
FLEXIBLE GAS LINE CONNECTOR - GA5081 (Not Shown) For all models.
PROPANE/NATURAL GAS CONVERSION KIT (Not Shown) PCDE-36V - Propane/LP Gas Conversion Kit for 36" Victorian Direct-Vent Electronic Fireplace PCDE-42V - Propane/LP Gas Conversion Kit for 42" Victorian Direct-Vent Electronic Fireplace NCDE-36V - Natural Gas Conversion Kit for 36" Victorian Direct- Vent Electronic Fireplace NCDE-42V - Natural Gas Conversion Kit for 42" Victorian Direct- Vent Electronic Fireplace
Manual variable control blower accessory provides better heat distribution. Complete installation and operation instructions in- cluded in this manual.
FACE/LOUVER PANEL KIT (Not Shown) RLD36 - 36" Rolled Louver Panels - Black FPD36 - 36" Filligree Panel Kit - Black FPD36B - 36" Filligree Panel Kit - Brushed Brass FPD36P - 36" Filligree Panel Kit - Platinum FPD36PB - 36" Filligree Panel Kit - Polished Brass RLD42 - 42" Rolled Louver Panels - Black FPD42 - 42" Filligree Panel Kit - Black FPD42B - 42" Filligree Panel Kit - Brushed Brass FPD42P - 42" Filligree Panel Kit - Platinum FPD42PB - 42" Filligree Panel Kit - Polished Brass
Provides better heat distribution. Blower turns off and on automatically, as needed. Complete installation and operation instruc- tions included in this manual.
Standard ON/OFF electronic remote control kit.
108862-01D For more information, visit www.desatech.com For more information, visit www.desatech.com



108862-01D For more information, visit www.desatech.com For more information, visit www.desatech.com


PARTS LIST
This list contains replaceable parts used in your fireplace. When ordering parts, follow the instructions listed under Replacement Parts on page 30 of this manual.
KEY (V)V36EN (V)V36ENS (V)V36ENH NO. (V)V36EP (V)V36EPS (V)V36EPH DESCRIPTION QTY.
1 ** ** ** Firebox Assembly 1 2 ** ** ** Face Weldment 1 3 108010-01 108010-01 108010-01 Door Assembly (V Models Only) 1 108010-02 108010-02 108010-02 Door Assembly (VV Models Only) 4 108011-01 108011-01 108011-01 Top Panel Louver Assy 1 5 108011-02 108011-02 108011-02 Bottom Panel Louver Assy 1 6 ** ** ** Fireplace Top 1 7 ** ** ** Fireplace Top Insulation 1 8 ** ** ** Fireplace Surround 1 9 109082-01 109082-01 109082-01 Heat Shield 1 10 ___ See Below See Below Top Refractory Brick Panel 1 11 ___ See Below See Below Left Refractory Brick Panel 1 12 ___ See Below See Below Rear Refractory Brick Panel 1 13 ___ See Below See Below Right Refractory Brick Panel 1 14 108076-01 108076-01 108076-01 Burner Base Gasket 1 15 108719-01 108719-01 108719-01 Screen Rod 1 16 12105 12105 12105 Screen 2 17 11418 11418 11418 Push-On Nut 2 18 14123 14123 14123 Strain Relief 1 19 21171 21171 21171 Gas Knock-Out Cover 2 20 24353 24353 24353 Handy Box Assembly 1 21 24460 24460 24460 Gas Conduit Assembly 1 22 108760-03 108760-03 108760-03 Burner Assembly (Natural Gas) 1 108760-04 108760-04 108760-04 Burner Assembly (Propane/LP Gas) 1 23 108032-01 108032-01 108032-01 Log Set 1 23-1 109128-01 109128-01 109128-01 Front Log (Log 1) 1 23-2 109129-01 109129-01 109129-01 Rear Log (Log 2) 1 23-3 109130-01 109130-01 109130-01 Crossover Log (Log 3) 1 23-4 109131-01 109131-01 109131-01 Top Log (Log 4) 1 23-5 109132-01 109132-01 109132-01 Left Log (Log 5) 1 23-6 109133-01 109133-01 109133-01 Base Log (Log 6) 1
25487 25487 25487 Lava Rock/Bag Assy 1 27253 27253 27253 Notice Label 1 55240 55240 55240 Vent Label 1
V36ENS, V36EPS VV36ENS, VV36EPS V36ENH, V36EPH VV36ENH, VV36EPH DESCRIPTION QTY
108081-02 108081-01 108175-02 108175-01 Top Refractory Brick Panel 1 108083-02 108083-01 108177-02 108177-01 Left Refractory Brick Panel 1 108080-02 108080-01 108174-02 108174-01 Rear Refractory Brick Panel 1 108082-02 108082-01 108176-02 108176-01 Right Refractory Brick Panel 1
** Part not available for field replacement.
108862-01D For more information, visit www.desatech.com For more information, visit www.desatech.com


Burner Assembly for Models (V)V36EN, (V)V36ENS, (V)V36ENH, (V)V36EP, (V)V36EPS, (V)V36EPH
BURNER ASSEMBLY FOR MODELS (V)V36EN, (V)V36ENS, (V)V36ENH, (V)V36EP, (V)V36EPS, AND (V)V36EPH 4 3

108862-01D For more information, visit www.desatech.com For more information, visit www.desatech.com


PARTS LIST Burner Assembly for Models (V)V36EN, (V)V36ENS, (V)V36ENH, (V)V36EP, (V)V36EPS, (V)V36EPH
This list contains replaceable parts used in your fireplace. When ordering parts, follow the instructions listed under Replacement Parts on page 30 of this manual.
KEY PART NO. NUMBER DESCRIPTION QTY.
1 108075-02 Burner Assembly Base 1 2 108759-01 Burner Pan Assembly 1 3 11165 Screw #10 x 5/8 MD TR BLK 12 4 108763-01 Tube Burner 1 5 104506-25 Pan Burner Orifice (Natural Gas) 1 14514 Pan Burner Orifice (Propane/LPGas) 1 6 108866-01 Pilot Assembly (Natural Gas) 1 108866-02 Pilot Assembly (Propane/LP Gas) 1 7 11102 Screw #8-32 x 3/8 PPH Zinc 2 8 108755-01 Pilot Bracket 1 9 14546 Tube Burner Orifice (Natural Gas) 1 14544 Tube Burner Orifice (Propane/LPGas) 1 10 14528 Brass Elbow Fitting 1 11 14554 Tubing Assembly 1 12 14500 Brass Fitting 2 13 14569 Electronic Valve (Natural Gas) 1 14570 Electronic Valve (Propane/LP Gas) 1 14 14253 Flexible Gas Line 1 15 11107 Screw #10-32 x 1/4 PPH Zinc 4 16 26808 Valve Bracket 1 17 26827 Switch Bracket 1 18 11147 Screw #10-24 x 1/2 PPH Zinc 2 19 11186 Screw #8-32 x 1 Zinc 4 20 14115 Spade Tongue Connector 1 21 14120 Spade 1/4 Female Connector 4 22 14126 16 GA Green Wire (Ground) 1 23 14129 Transformer, 24V 1 24 14134 18 GA Black Wire 5 25 14149 Spade 1/4 Right Angle Connector 4 26 14301 Ignition Module SP745 1 27 17223 Magnet 2 28 23416 Electronic Components Board 1 29 108863-01 24" Supply Connect Plug 1 30 11201 Nut #8-32 Hex Zinc 4 31 109144-01 Air Baffle, 36" (Natural Gas Only) 2 32 108761-01 Grate Assembly 1 33 108754-01 Grate Base 1
108862-01D For more information, visit www.desatech.com For more information, visit www.desatech.com



108862-01D For more information, visit www.desatech.com For more information, visit www.desatech.com


This list contains replaceable parts used in your fireplace. When ordering parts, follow the instructions listed under Replacement Parts on page 30 of this manual.
KEY (V)V42EN (V)V42ENS (V)V42ENH NO. (V)V42EP (V)V42EPS (V)V42EPH DESCRIPTION QTY.
1 ** ** ** Firebox Assembly 1 2 ** ** ** Face Weldment 1 3 108328-01 108328-01 108328-01 Door Assembly (V Models Only) 1 108328-02 108328-02 108328-02 Door Assembly (VV Models Only) 1 4 108331-01 108331-01 108331-01 Top Panel Louver Assy 1 5 108331-02 108331-02 108331-02 Bottom Panel Louver Assy 1 6 ** ** ** Fireplace Top 1 7 ** ** ** Fireplace Top Insulation 1 8 ** ** ** Fireplace Surround 1 9 109082-02 109082-02 109082-02 Heat Shield 1 10 ___ See Below See Below Top Refractory Brick Panel 1 11 ___ See Below See Below Left Refractory Brick Panel 1 12 ___ See Below See Below Rear Refractory Brick Panel 1 13 ___ See Below See Below Right Refractory Brick Panel 1 14 108374-01 108374-01 108374-01 Burner Base Gasket 1 15 108455-01 108455-01 108455-01 Screen Rod 1 16 108740-01 108740-01 108740-01 Screen 2 17 11418 11418 11418 Push-On Nut 2 18 14123 14123 14123 Strain Relief 1 19 21171 21171 21171 Gas Knock-Out Cover 2 20 24353 24353 24353 Handy Box Assembly 1 21 24460 24460 24460 Gas Conduit Assembly 1 22 108329-03 108329-03 108329-03 Burner Assembly (Natural Gas) 1 108329-04 108329-04 108329-04 Burner Assembly (Propane/LP Gas) 1 23 108778-01 108778-01 108778-01 Log Set 1 23-1 109396-01 109396-01 109396-01 Front Log (Log 1) 1 23-2 109397-01 109397-01 109397-01 Rear Log (Log 2) 1 23-3 109398-01 109398-01 109398-01 Crossover Log (Log 3) 1 23-4 109399-01 109399-01 109399-01 Top Log (Log 4) 1 23-5 109400-01 109400-01 109400-01 Left Log (Log 5) 1 23-6 109401-02 109401-02 109402-02 Right Log (Log 6) 1 23-7 109401-01 109401-01 109401-01 Base Log (Log 7) 1
25487 25487 25487 Lava Rock/Bag Assy 1 27253 27253 27253 Notice Label 1 55240 55240 55240 Vent Label 1
V42ENS, V42EPS VV42ENS, VV42EPS V42ENH, V42EPH VV42ENH, VV42EPH DESCRIPTION QTY
108352-02 108352-01 108356-02 108356-01 Top Refractory Brick Panel 1 108354-02 108354-01 108358-02 108358-01 Left Refractory Brick Panel 1 108351-02 108351-01 108355-02 108355-01 Rear Refractory Brick Panel 1 108353-02 108353-01 108357-02 108357-01 Right Refractory Brick Panel 1
108862-01D For more information, visit www.desatech.com For more information, visit www.desatech.com


Burner Assembly for Models (V)V42EN, (V)V42ENS, (V)V42ENH, (V)V42EP, (V)V42EPS, (V)V42EPH
BURNER ASSEMBLY FOR MODELS (V)V42EN, (V)V42ENS, (V)V42ENH, (V)V42EP, (V)V42EPS, AND (V)V42EPH 4 3

108862-01D For more information, visit www.desatech.com For more information, visit www.desatech.com


PARTS LIST Burner Assembly for Models (V)V42EN, (V)V42ENS, (V)V42ENH, (V)V42EP, (V)V42EPS, (V)V42EPH
This list contains replaceable parts used in your fireplace. When ordering parts, follow the instructions listed under Replacement Parts on page 30 of this manual.
KEY PART NO. NUMBER DESCRIPTION QTY.
1 108373-01 Burner Assembly Base 1 2 108330-01 Burner Pan Assembly 1 3 11165 Screw #10 x 5/8 MD TR BLK 12 4 108376-01 Tube Burner 1 5 104506-24 Pan Burner Orifice (Natural Gas) 1 104506-20 Pan Burner Orifice (Propane/LPGas) 1 6 108866-01 Pilot Assembly (Natural Gas) 1 108866-02 Pilot Assembly (Propane/LP Gas) 1 7 11102 Screw #8-32 x 3/8 PPH Zinc 2 8 108755-01 Pilot Bracket 1 9 104506-25 Tube Burner Orifice (Natural Gas) 1 104506-20 Tube Burner Orifice (Propane/LPGas) 1 10 14528 Brass Elbow Fitting 1 11 14554 Tubing Assembly 1 12 14500 Brass Fitting 2 13 14569 Electronic Valve (Natural Gas) 1 14570 Electronic Valve (Propane/LP Gas) 1 14 14253 Flexible Gas Line 1 15 11107 Screw #10-32 x 1/4 PPH Zinc 4 16 26808 Valve Bracket 1 17 26827 Switch Bracket 1 18 11147 Screw #10-24 x 1/2 PPH Zinc 2 19 11186 Screw #8-32 x 1 Zinc 4 20 14115 Spade Tongue Connector 1 21 14120 Spade 1/4 Female Connector 4 22 14126 16 GA Green Wire (Ground) 1 23 14129 Transformer, 24V 1 24 14134 18 GA Black Wire 5 25 14149 Spade 1/4 Right Angle Connector 4 26 14301 Ignition Module SP745 1 27 17223 Magnet 2 28 23416 Electronic Components Board 1 29 108863-01 24" Supply Connect Plug 1 30 11201 Nut #8-32 Hex Zinc 4 31 109144-02 Air Baffle, 42" (Natural Gas Only) 2 32 108761-02 Grate Assembly 1 33 108346-01 Grate Base 1 34 11429 Pin 2
108862-01D For more information, visit www.desatech.com For more information, visit www.desatech.com



Always specify model and serial numbers when communicating with the factory.
We reserve the right to amend these specifications at any time without notice. The only warranty applicable is our standard written warranty. We make no other warranty, expressed or implied.
DESA International warrants this product to be free from defects in materials and components for two (2) years from the date of first purchase, provided that the product has been properly installed, operated and maintained in accordance with all applicable instructions. To make a claim under this warranty the Bill of Sale or cancelled check must be presented.
This warranty is extended only to the original retail purchaser. This warranty covers the cost of part(s) required to restore this heater to proper operating condition and an allowance for labor when provided by a DESA Authorized Service Center. Warranty part(s) MUST be obtained through authorized retailers of this product and/or DESA International who will provide original factory replacement parts. Failure to use original factory replacement parts voids this warranty. The heater MUST be installed by a qualified installer in accordance with all local codes and instructions furnished with the unit.
This warranty does not apply to parts that are not in original condition because of normal wear and tear, or parts that fail or become damaged as a result of misuse, accidents, lack of proper maintenance or defects caused by improper installation. Travel, diagnostic cost, labor, transportation and any and all such other costs related to repairing a defective heater will be the responsibility of the owner.
TO THE FULL EXTENT ALLOWED BY THE LAW OF THE JURISDICTION THAT GOVERNS THE SALE OF THE PRODUCT; THIS EXPRESS WARRANTY EXCLUDES ANY AND ALL OTHER EXPRESSED WARRANTIES AND LIMITS THE DURATION OF ANY AND ALL IMPLIED WARRANTIES, INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE TO TWO (2) YEARS ON ALL COMPONENTS FROM THE DATE OF FIRST PURCHASE; AND DESA INTERNATIONAL’S LIABILITY IS HEREBY LIMITED TO THE PURCHASE PRICE OF THE PRODUCT AND DESA INTERNATIONAL SHALL NOT BE LIABLE FOR ANY OTHER DAMAGES WHATSOEVER INCLUDING INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES.
Some states do not allow a limitation on how long an implied warranty lasts or an exclusion or limitation of incidental or consequential damages, so the above limitation on implied warranties, or exclusion or limitation on damages may not apply to you.
This warranty gives you specific legal rights, and you may also have other rights that vary from state to state.
For information about this warranty write:
2701 Industrial Drive P.O. Box 90004 Bowling Green, KY 42102-9004 www.desatech.com
108862-01 Rev. D 08/02
108862-01D For more information, visit www.desatech.com For more information, visit www.desatech.com
108862 01