DIRECT-VENT FIREPLACE OWNER’S OPERATION AND INSTALLATION MANUALp.1For more information, visit www.desatech.com For more information, visit www.desatech.comp.1NATURAL GAS MODEL (V)K42EN SERIES PROPANE/LP GAS MODEL (V)K42EP SERIESp.1TABLE OF CONTENTSp.2SAFETY INFORMATION ............................................................ 2p.2CLEANING AND MAINTENANCE ............................................ 26p.2PRODUCT IDENTIFICATION ..................................................... 3p.2TROUBLESHOOTING .............................................................. 27p.2LOCAL CODES........................................................................... 3p.2REPLACEMENT PARTS .......................................................... 29p.2PRODUCT FEATURES .............................................................. 4p.2SPECIFICATIONS .................................................................... 29p.2PRE-INSTALLATION PREPARATION ........................................ 4p.2SERVICE HINTS....................................................................... 29p.2LOCATION OF TERMINATION CAP .......................................... 6p.2TECHNICAL SERVICE ............................................................. 29p.2VENTING INSTALLATION INSTRUCTIONS .............................. 7p.2ILLUSTRATED PARTS BREAKDOWN AND PARTS LIST ....... 30p.2FIREPLACE INSTALLATION .................................................... 16p.2ACCESSORIES ........................................................................ 34p.2WIRING DIAGRAM ................................................................... 23p.2OWERNER’S REGISTRATION FORM ..................................... 35p.2OPERATING FIREPLACE ........................................................ 24p.2INSPECTING BURNERS.......................................................... 25p.2SAFETY INFORMATIONp.2SAFETY INFORMATION Continuedp.3PRODUCT IDENTIFICATIONp.3PRODUCT FEATURESp.4PRE-INSTALLATION PREPARATIONp.4LOCATION AND SPACE REQUIREMENTSp.4RWp.4FWp.4PRE-INSTALLATION PREPARATION Continuedp.5VENTING INSTALLATION INSTRUCTIONSp.7VENTING INSTALLATION INSTRUCTIONS Continuedp.8INSTALLATION PLANNINGp.8Horizontal Termination Installationp.8Horizontal Termination Configurationsp.10CORNER INSTALLATIONp.11SNORKEL TERMINATION INSTALLATIONp.11INSTALLATION FOR VERTICAL TERMINATIONp.13Vertical Termination Configurationsp.14FIREPLACE INSTALLATIONp.16CHECK GAS TYPEp.16INSTALLING OPTIONAL BLOWER ACCESSORYp.16Model BK Installationp.16FIREPLACE INSTALLATION Continuedp.17Model BKT Installationp.17Blower Wiring Diagramp.18INSTALLING GAS PIPING TO FIREPLACE LOCATIONp.18CHECKING GAS CONNECTIONSp.19Pressure Testing Gas Supply Piping Systemp.19CONNECTING FIREPLACE TO GAS SUPPLYp.19Installation Items Neededp.19REMOVING/REPLACING GLASS DOORp.20Removing Louver Panelsp.20Removing Glass Doorp.21INSTALLING BRICK LINER MODELS BL42DA(SA), BL42DHA(SA)p.21Cleaning Glass Doorp.21INSTALLING LOGS, LAVA ROCK AND GLOWING EMBERSp.22WALL SWITCH INSTALLATIONp.22OPTIONAL REMOTE CONTROL INSTALLATION (Model WRC)p.23WIRING DIAGRAMp.23(SUPPLIED) WALL SWITCHp.23INCOMING MAINp.23(NOT SUPPLIED)p.23GAS SUPPLYp.23ONp.23OFFp.23BLACKp.23INCOMINGp.23PV GND PV/MV TR MV TH IGNp.23WHITEp.23120V AC (FUSE BOX OR BREAKER)p.23GREENp.23EV1p.23ELECTRICAL RATING:p.23EV2p.2324V ACp.23STEP DOWN TRANSFORMERp.23
Page 1 of the Desa (V)K42EN user manual — NATURAL GAS MODEL (V)K42EN SERIES PROPANE/LP GAS MODEL (V)K42EP SERIES
Page 1 · click to enlarge
Page 1

DIRECT-VENT FIREPLACE OWNER’S OPERATION AND INSTALLATION MANUAL

For more information, visit www.desatech.com For more information, visit www.desatech.com

Desa (V)K42EN — For more information, visit www.desatech.com For more information, visit www.desatech.com diagram (page 1)
Fig. 1 · For more information, visit www.desatech.com For mor…

NATURAL GAS MODEL (V)K42EN SERIES PROPANE/LP GAS MODEL (V)K42EP SERIES

FOR YOUR SAFETY Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.

  • FOR YOUR SAFETY WHAT TO DO IF YOU SMELL GAS
  • Do not try to light any appliance.
  • Do not touch any electrical switch
  • Do not use any phone in your building.
  • Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
  • If you cannot reach your gas supplier, call the fire department.

Installation and service must be performed bay a qualified installer, service agency, or the gas supplier.

This appliance may be installed in an aftermarket*, permanently located, manufactured (mobile) home, where not prohibited by state or local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.

*Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer.

Save this manual for future reference. Save this manual for future reference.

Page 2 of the Desa (V)K42EN user manual — Table of Contents
Page 2 · Contents
Contents

Contents

DIRECT-VENT FIREPLACE OWNER’S OPERATION AND INSTALLATION MANUALp.1For more information, visit www.desatech.com For more information, visit www.desatech.comp.1NATURAL GAS MODEL (V)K42EN SERIES PROPANE/LP GAS MODEL (V)K42EP SERIESp.1TABLE OF CONTENTSp.2SAFETY INFORMATION ............................................................ 2p.2CLEANING AND MAINTENANCE ............................................ 26p.2PRODUCT IDENTIFICATION ..................................................... 3p.2TROUBLESHOOTING .............................................................. 27p.2LOCAL CODES........................................................................... 3p.2REPLACEMENT PARTS .......................................................... 29p.2PRODUCT FEATURES .............................................................. 4p.2SPECIFICATIONS .................................................................... 29p.2PRE-INSTALLATION PREPARATION ........................................ 4p.2SERVICE HINTS....................................................................... 29p.2LOCATION OF TERMINATION CAP .......................................... 6p.2TECHNICAL SERVICE ............................................................. 29p.2VENTING INSTALLATION INSTRUCTIONS .............................. 7p.2ILLUSTRATED PARTS BREAKDOWN AND PARTS LIST ....... 30p.2FIREPLACE INSTALLATION .................................................... 16p.2ACCESSORIES ........................................................................ 34p.2WIRING DIAGRAM ................................................................... 23p.2OWERNER’S REGISTRATION FORM ..................................... 35p.2OPERATING FIREPLACE ........................................................ 24p.2INSPECTING BURNERS.......................................................... 25p.2SAFETY INFORMATIONp.2SAFETY INFORMATION Continuedp.3PRODUCT IDENTIFICATIONp.3PRODUCT FEATURESp.4PRE-INSTALLATION PREPARATIONp.4LOCATION AND SPACE REQUIREMENTSp.4RWp.4FWp.4PRE-INSTALLATION PREPARATION Continuedp.5VENTING INSTALLATION INSTRUCTIONSp.7VENTING INSTALLATION INSTRUCTIONS Continuedp.8INSTALLATION PLANNINGp.8Horizontal Termination Installationp.8Horizontal Termination Configurationsp.10CORNER INSTALLATIONp.11SNORKEL TERMINATION INSTALLATIONp.11INSTALLATION FOR VERTICAL TERMINATIONp.13Vertical Termination Configurationsp.14FIREPLACE INSTALLATIONp.16CHECK GAS TYPEp.16INSTALLING OPTIONAL BLOWER ACCESSORYp.16Model BK Installationp.16FIREPLACE INSTALLATION Continuedp.17Model BKT Installationp.17Blower Wiring Diagramp.18INSTALLING GAS PIPING TO FIREPLACE LOCATIONp.18CHECKING GAS CONNECTIONSp.19Pressure Testing Gas Supply Piping Systemp.19CONNECTING FIREPLACE TO GAS SUPPLYp.19Installation Items Neededp.19REMOVING/REPLACING GLASS DOORp.20Removing Louver Panelsp.20Removing Glass Doorp.21INSTALLING BRICK LINER MODELS BL42DA(SA), BL42DHA(SA)p.21Cleaning Glass Doorp.21INSTALLING LOGS, LAVA ROCK AND GLOWING EMBERSp.22WALL SWITCH INSTALLATIONp.22OPTIONAL REMOTE CONTROL INSTALLATION (Model WRC)p.23WIRING DIAGRAMp.23(SUPPLIED) WALL SWITCHp.23INCOMING MAINp.23(NOT SUPPLIED)p.23GAS SUPPLYp.23ONp.23OFFp.23BLACKp.23INCOMINGp.23PV GND PV/MV TR MV TH IGNp.23WHITEp.23120V AC (FUSE BOX OR BREAKER)p.23GREENp.23EV1p.23ELECTRICAL RATING:p.23EV2p.2324V ACp.23STEP DOWN TRANSFORMERp.23
Page 3 of the Desa (V)K42EN user manual — SAFETY INFORMATION Continued
Page 3 · click to enlarge
Page 3
Desa (V)K42EN — SAFETY INFORMATION Continued diagram (page 3)
Fig. 2 · SAFETY INFORMATION Continued

SAFETY INFORMATION Continued

PRODUCT IDENTIFICATION

5. This fireplace reaches high temperatures. Keep children and adults away from hot surfaces to avoid burns or clothing igni- tion. Fireplace will remain hot for a time after shutdown. Al- low surfaces to cool before touching. 6. Carefully supervise young children when they are in the room with fireplace. 7. Do not modify this fireplace under any circumstances. Any parts removed for servicing must be replaced prior to operat- ing fireplace. 8. Turn fireplace off and let cool before servicing, installing, or repairing. Only a qualified service person should install, ser- vice, or repair this fireplace. Have fireplace inspected annu- ally by a qualified service person. 9. You must keep control compartments, burners, and circulat- ing air passages clean. More frequent cleaning may be needed due to excessive lint and dust from carpeting, bedding mate- rial, etc. Turn off the gas valve and pilot light before cleaning fireplace. 10. Have venting system inspected annually by a qualified service person. If needed, have venting system cleaned or repaired. See Cleaning and Maintenance, page 26. 11. Keep the area around your fireplace clear of combustible ma- terials, gasoline, and other flammable vapor and liquids. Do not run fireplace where these are used or stored. Do not place items such as clothing or decorations on or around fireplace. 12. Do not use this fireplace to cook food or burn paper or other objects. 13. Do not use any solid fuels (wood, coal, paper, cardboard, etc.) in this fireplace. Use only the gas type indicated on fireplace nameplate. 14. This appliance, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70, or the Ca- nadian Electrical Code, CSA C22.1. 15. Do not use fireplace if any part has been exposed to or under water. Immediately call a qualified service person to arrange for replacement of the unit. 16. Do not operate fireplace if any log is broken. 17. Do not use a blower insert, heat exchanger insert, or other ac- cessory not approved for use with this fireplace. 18. Do not operate fireplace with glass door removed, cracked, or broken. 19. Provide adequate clearances around air openings.

Desa (V)K42EN — SAFETY INFORMATION Continued diagram (page 3)
Fig. 3 · SAFETY INFORMATION Continued

Switch Bracket for Optional Remote and Blower

Figure 1 - Direct-Vent Fireplace with Electronic Ignition

LOCAL CODES Install and use fireplace with care. Follow all local codes. In the absence to local codes, use the current National Fuel Gas Code ANSI Z223.1/NFPA 54* (USA) or the current CSA-B149.1 Instal- lation Code (Canada). *Available from: American National Standards Institute, Inc.

1430 Broadway New York, NY 10018 National Fire Protection Association, Inc.

Batterymarch Park Quincy, MA 02269

111922-01A For more information, visit www.desatech.com For more information, visit www.desatech.com

Upper Louver Panel · Flue Collar

Page 4 of the Desa (V)K42EN user manual — D
Page 4 · click to enlarge
Page 4
Desa (V)K42EN — PRODUCT FEATURES diagram (page 4)
Fig. 4

PRODUCT FEATURES

  • These are a few facts that can help you understand and enjoy your direct-vent fireplace:
  • The venting system may be routed to the outside of your home in several ways. It may vent through the roof (vertical) or it may vent to an outside/exterior wall (horizontal). The vent pipe installation is very important to allow for proper operation. You must follow the venting instructions very carefully for either vertical or horizontal applications.
  • This fireplace may be installed in any room of your house provided all local codes and these installation instructions are followed.
  • This fireplace does not require electricity to operate.
  • Only the blower requires electricity if installed and if you plan to install the blower at a later date, do not forget to wire the outlet at the bottom of the fireplace when framing.
  • A piezo ignitor and ceramic electrode create spark to ignite the pilot light. It does not require any matches, batteries or any other sources of ignition to light the pilot.
  • Each time you turn on your fireplace, you may notice some amount of condensation on the inside of the fireplace glass. This is normal and will disappear after 10-20 minutes of operation.
  • Your direct-vent gas fireplace system (fireplace and venting) is a balanced and sealed gas operating unit. It requires approximately 10-20 minutes of operating time before the flame pattern stabilizes.
  • Your fireplace is designed to be used in zero clearance installations. Wall or framing material can be placed directly against any exterior surface on the back, sides, or top of your fireplace, except where standoff spacers are integrally attached. If standoff spacers are attached to your fireplace, these spacers can be placed directly against wall or framing material. See framing details on page 5.
  • If you plan on installing a television or entertainment center recessed above your fireplace, it is recommended that you maintain a minimum 18" above top of louver opening.
  • When locating termination cap, it is important to observe the minimum clearances shown in Figure 7, page 6.
  • If recessing into a wall, you can avoid extra framing by positioning your fireplace against an already existing framing member.
  • Do not recess termination cap into a wall or siding.
  • You may paint the termination cap with 450ºF (232ºC) heatresistant paint to coordinate with the exterior finish.
  • There must not be any obstruction such as bushes, garden sheds, fences, decks, or utility buildings within 24" from the front of the termination cap.
  • Do not locate termination cap where excessive snow or ice build up may occur. Be sure to clear vent termination area after snow falls to prevent accidental blockage of venting system. When using snow blowers, do not direct snow towards vent termination area.

PRE-INSTALLATION PREPARATION

Desa (V)K42EN — PRE-INSTALLATION PREPARATION diagram (page 4)
Fig. 5

LOCATION AND SPACE REQUIREMENTS

Determine the safest and most efficient location for your DESA direct-vent fireplace. Make sure that rafters and wall studs are not in the way of the venting system. Choose a location where the heat output is not affected by drafts, air conditioning ducts, windows or doors. Figure 2 shows some common locations. Be aware of all restrictions and precautions before deciding the exact location for your fireplace and termination cap.

  • When deciding the location of your fireplace, follow these rules:
  • Do not connect this fireplace venting to a chimney flue serving a separate solid-fuel burning fireplace or appliance.
  • Due to high temperatures, do not locate this fireplace in high traffic areas, windy or drafty areas, or near furniture or draperies.
  • Proper clearances must be maintained.
  • If your fireplace is to be installed directly on carpeting, vinyl tile, or any combustible material other than wood, it must be installed on a metal or wood panel extending the full width and depth of the fireplace. See Figure 3.

Figure 2 - Common Fireplace Locations

36 1/4"

RW

23 1/4"

D

FW

Figure 3 - Fireplace Bottom Dimensions

111922-01A For more information, visit www.desatech.com For more information, visit www.desatech.com

Corner installation · 48"

Page 5 of the Desa (V)K42EN user manual — PRE-INSTALLATION PREPARATION Continued
Page 5 · click to enlarge
Page 5
Desa (V)K42EN — PRE-INSTALLATION PREPARATION Continued diagram (page 5)
Fig. 6 · PRE-INSTALLATION PREPARATION Continued

PRE-INSTALLATION PREPARATION Continued

CLEARANCES Minimum clearances to combustibles for the fireplace are as follows: Back, and sides 0"/mm Perpendicular walls 6" (152mm) Floor 0"/mm Ceiling to louver opening 42" (1067mm) Front 36" (914mm) Top 0"/mm Vent (See venting instructions for specific venting clearances.) Combustible material with a maximum thickness of 5/8" may be flush with the top front of fireplace .

Desa (V)K42EN — PRE-INSTALLATION PREPARATION Continued diagram (page 5)
Fig. 7 · PRE-INSTALLATION PREPARATION Continued

21 5/8" 58 1/2" 13 1/2"

Figure 5 - Framing Clearances for Corner Installation

Desa (V)K42EN — PRE-INSTALLATION PREPARATION Continued diagram (page 5)
Fig. 8 · PRE-INSTALLATION PREPARATION Continued

NOTICE: This fireplace is intended for use as supple- mental heat. Use this fireplace along with your pri- mary heating system. Do not install this fireplace as your primary heat source. If you have a central heat- ing system, you may run system’s circulating blower while using fireplace. This will help circulate the heat throughout the house. In the event of a power outage, you can use this fireplace as a heat source.

Desa (V)K42EN — PRE-INSTALLATION PREPARATION Continued diagram (page 5)
Fig. 9 · PRE-INSTALLATION PREPARATION Continued

FRAMING AND FINISHING Figure 4 shows typical framing of this fireplace. Figure 5 shows framing for corner installation. All minimum clearances must be met.

For available accessories for this fireplace, see Accessories on page 34. If you are using a separate combustible mantel piece, refer to Figure 6 for proper installation height. You can install noncombustible mantels at any height above the fireplace. Note: Noncombustible mantels may discolor!

of Louver Opening 1 14" (356mm) A 16" (406mm) 2 12" (305mm) B 14" (356mm) 3 10" (254mm) C 12" (305mm) 4 8" (203mm) D 10" (254mm) 5 6" (152mm) E 8" (203mm) 6 4" (101mm) F 6" (152mm) 7 2" (51mm) G 4" (101mm)

Desa (V)K42EN — PRE-INSTALLATION PREPARATION Continued diagram (page 5)
Fig. 10 · PRE-INSTALLATION PREPARATION Continued

48 1/4" 25 5/8"

Figure 4 - Framing Clearances for Installation Against an Exterior Wall

111922-01A For more information, visit www.desatech.com For more information, visit www.desatech.com

Nailing Tabs

Page 6 of the Desa (V)K42EN user manual — G
Page 6 · click to enlarge
Page 6
Desa (V)K42EN — PRE-INSTALLATION PREPARATION Continued diagram (page 6)
Fig. 11 · PRE-INSTALLATION PREPARATION Continued
Desa (V)K42EN — PRE-INSTALLATION PREPARATION Continued diagram (page 6)
Fig. 12 · PRE-INSTALLATION PREPARATION Continued

TERMINATION CAP AIR SUPPLY INLET GAS METER RESTRICTED AREA (TERMINATION PROHIBITED) A = clearance above grade, veranda, porch, deck, or balcony

I = clearance to service regulator vent outlet [*72 inches (182.9cm)

[*12 inches (30.5mc) minimum] B = clearance to window or door that may be opened

minimum] J = clearance to non-mechanical air supply inlet to building or the

[12 inches (30.5cm) minimum] C = clearance to permanently closed window [minimum 12 inches

combustion air inlet to any other fireplace [*12 inches (30.5cm) minimum] K = clearance to a mechanical air supply inlet [*72 inches (182.9cm)

(30.5cm) recommended to prevent condensation on window] D = vertical clearance to ventilated soffit located above the terminal

minimum] L = clearance above paved side-walk or a paved driveway located on

within a horizontal distance of 24 inches (61cm) from the center-line of the terminal [18 inches (45.7cm) minimum] E = clearance to unventilated soffit [12 inches (30.5cm) minimum] F = clearance to outside corner (see below) G = clearance to inside corner (see below) H = *not to be installed above a meter/regulator assembly within

public property [*84 inches (213.3cm) minimum] M = clearance under veranda, porch, deck [*12 inches (30.5cm) minimum ] N = clearance above a roof shall extend a minimum of 24 inches (61cm)

above the highest point when it passes through the roof surface and any other obstruction within a horizontal distance of 18 inches (45.7cm)

36 inches (91.4cm) horizontally from the center-line of the regulator

vent shall not terminate directly above a side-walk or paved driveway which is located between two single family dwellings and serves both dwellings* only permitted if veranda, porch, deck or balconey is fully open on a minimum of 2 sides beneath the floor* * as specified in CAN/CSA B149 (.1 or .2) Installation Codes (1991) for Canada and U.S.A. Note: Local codes or regulations may require different clearances

Termination Clearances for Buildings with Combustible and Noncombustible Exteriors

Outside Corner Recessed Location

Desa (V)K42EN — PRE-INSTALLATION PREPARATION Continued diagram (page 6)
Fig. 13 · PRE-INSTALLATION PREPARATION Continued
Desa (V)K42EN — PRE-INSTALLATION PREPARATION Continued diagram (page 6)
Fig. 14 · PRE-INSTALLATION PREPARATION Continued

Balcony with No Side Wall

Balcony with Perpendicular Side Wall

Desa (V)K42EN — PRE-INSTALLATION PREPARATION Continued diagram (page 6)
Fig. 15 · PRE-INSTALLATION PREPARATION Continued

recessed location D = Minimum width for back wall of

G

recessed location - Combustible - 38" (965mm) Noncombustible - 24" (61cm) E = Clearance from corner in

Combustible & Noncombustible H = 24" (61cm) J = 20" (50.8cm)

recessed location- Combustible - 6" (15.2cm) Noncombustible - 2" (5.1cm)

G = 12" (30.5cm) minimum clearance

Figure 7 - Minimum Clearances for Termination Cap

111922-01A For more information, visit www.desatech.com For more information, visit www.desatech.com

Inside Corner

Page 7 of the Desa (V)K42EN user manual — VENTING INSTALLATION INSTRUCTIONS
Page 7 · click to enlarge
Page 7
Desa (V)K42EN — VENTING INSTALLATION INSTRUCTIONS diagram (page 7)
Fig. 16

VENTING INSTALLATION INSTRUCTIONS

These models are tested and approved for use with DESA (direct- vent) pipe components and terminations.

  • INSTALLATION PRECAUTIONS
  • Wear glo ves and saf ety glasses f or pr otection
  • Use extreme caution w hen using lad ders or when on r oof tops
  • Be aware of electr ical wir ing loca tions in w alls and ceilings

The venting system must terminate on the outside of the structure and can not be attached to a chimney or flue system serving a separate solid fuel or gas burning appliance. A direct-vent appliance must have its own venting system. DO NOT common vent this appliance.

  • The following actions will void the warranty on your venting system:
  • Installation of any dama ged venting component
  • Unauthorized modif ication of the v enting system (Do not cut or alter v ent components)
  • Installation of any component par t not man ufactured or a pproved b y DESA
  • Installation other than as instructed by these instructions
  • These models are approved to be vented either horizontally through an outside wall or vertically through a roof or chase enclosure using the following guidelines:
  • When venting system terminates horizontally on an outside wall, you must install a standoff if the termination cap is to be installed directly on a combustible finish such as vinyl, wood, stucco, etc.
  • Never run the vent downward as this may cause excessive temperatures which could cause a fire.
  • Vent pipe air space clearances to combustibles are 1" on all sides except on the horizontal sections, which requires 2" clearance from the top of the pipe. Where the termination cap penetrates a combustible wall, 1" air space clearance is required.
  • Snorkel terminations are required when minimum clearance to grade cannot be met (see Figure 16 on page 11).
  • Have fireplace and selected vent components on hand to help determine the exact measurements when elbowing or offsetting. Always use wall firestops when penetrating walls and firestops when penetrating ceilings or attic spaces.
  • Install horizontal venting with a 1/4" rise for every 12" of run toward the termination.

111922-01A For more information, visit www.desatech.com For more information, visit www.desatech.com

Page 8 of the Desa (V)K42EN user manual — Horizontal Termination Installation
Page 8 · click to enlarge
Page 8
Desa (V)K42EN — VENTING INSTALLATION INSTRUCTIONS Continued diagram (page 8)
Fig. 17 · VENTING INSTALLATION INSTRUCTIONS Continued

VENTING INSTALLATION INSTRUCTIONS Continued

INSTALLATION PLANNING

  • There are two basic types of direct-vent installation:
  • Horizontal Termination
  • Vertical Termination

Horizontal Termination Installation

IMPORTANT: Horizontal square terminations require only inner portion of wall firestop. Horizontal installations using round termina- tion require exterior portion of wall firestop. 1. Set the fireplace in its desired location and determine the route your horizontal venting will take. Do not secure the fireplace until all venting has been installed. Some installations require sliding the fireplace in and out of position to make final venting connections. Figures 14 through 18 on pages 10 through 12 show different configurations for venting with horizontal termination that will help you decide which application best suits your in- stallation. Check to see if wall studs or roof rafters are in the path of your desired venting route. If they are, you may want to adjust the location of the fireplace. 2. Direct vent pipe sections and components are designed with special twist-lock connections.

Figure 8 - Vent Pipe Connections

Vent Opening Combustible Wall

Desa (V)K42EN — Horizontal Termination Installation diagram (page 8)
Fig. 18 · Horizontal Termination Installation

Twist-Lock Procedure: The female ends of the pipes have locking lugs (indentations). These lugs will slide straight into matching slots on the male ends of adjacent pipes. Push pipe sections together and twist one section clockwise approxi- mately one-quarter turn until the sections are fully locked (see Figure 8). Note: Horizontal runs of vent must be sup- ported every three feet. Use wall straps for this purpose. 3. Use a 45° elbow to connect venting system to fireplace flue col- lar. The elbow is designed to be twist-locked onto the flue collar as described in step 2. IMPORTANT: Do not attempt to alter the configuration of the elbow by cutting, twisting, bending, etc. 4. Assemble the desired combination of pipe and elbows to the fireplace flue collar. If there are long portions of venting run, pre-assembled pipe sections may be installed as subassemblies for convenience. 5. Carefully determine the location where the vent pipe assembly will penetrate the outside wall. The center of the hole should line up with the center-line of the horizontal vent pipe. Mark the wall for a 10 3/4" x 10 3/4" square hole. Cut and frame the square hole in the exterior wall where the vent will be terminated. If the wall being penetrated is constructed of noncombustible material, such as masonry block or concrete, a 8 1/2" hole with zero clearance is acceptable (see Figure 9).

Figure 9 - Vent Opening Requirements

111922-01A For more information, visit www.desatech.com For more information, visit www.desatech.com

Female Locking Lugs · Male Slots

Page 9 of the Desa (V)K42EN user manual — VENTING INSTALLATION INSTRUCTIONS Continued
Page 9 · click to enlarge
Page 9
Desa (V)K42EN — VENTING INSTALLATION INSTRUCTIONS Continued diagram (page 9)
Fig. 19 · VENTING INSTALLATION INSTRUCTIONS Continued

VENTING INSTALLATION INSTRUCTIONS Continued

Desa (V)K42EN — VENTING INSTALLATION INSTRUCTIONS Continued diagram (page 9)
Fig. 20 · VENTING INSTALLATION INSTRUCTIONS Continued

6. Noncombustible Exterior Wall: Position the horizontal vent cap in the center of the 8 1/2" round hole and attach to the exte- rior wall with four wood screws provided. Before attaching the vent cap to exterior wall, run a bead of non-hardening mastic (pliable sealant) around the outside edges to make a seal be- tween it and the outside wall. Note: The four wood screws provided should be replaced with appropriate fasteners for stucco, brick, concrete, or other types of sidings.

Combustible Exterior Wall: For vinyl siding, stucco, or wood exteriors, a siding standoff must be installed between the vent cap and exterior wall. The siding standoff prevents excessive heat from damaging the siding materials. Siding material must be cut to accommodate standoff. Bolt the vent cap to the stand- off. Apply non-hardening mastic around outside edge of stand- off. Position the standoff/cap assembly in the center of the 10 3/4" square hole and attach to exterior wall with wood screws provided (see Figure 11). The siding standoff must sit flush against the exterior fascia material. 7. Combustible Exterior Wall Only: Slide the wall firestop over the vent pipe before connecting horizontal run to vent cap (see Figure 12). 8. Carefully move fireplace, with vent assembly attached, toward wall and insert vent pipe into horizontal termination. The pipe overlap should be a minimum of 11/4". 9. Combustible Exterior Wall Only: Slide wall firestop against interior wall surface and attach with screws provided (see Figure 12). See Figure 13, page 10, for horizontal termina- tion details.

Figure 11 - Installing Siding Standoff (Combustible Exterior)

Desa (V)K42EN — VENTING INSTALLATION INSTRUCTIONS Continued diagram (page 9)
Fig. 21 · VENTING INSTALLATION INSTRUCTIONS Continued

Vent Cap (Horizontal Termination)

Desa (V)K42EN — VENTING INSTALLATION INSTRUCTIONS Continued diagram (page 9)
Fig. 22 · VENTING INSTALLATION INSTRUCTIONS Continued

Figure 12 - Connecting Vent Cap with Horizontal Vent Pipe

Figure 10 - Installing Horizontal Vent Cap (Noncombustible Exterior)

111922-01A For more information, visit www.desatech.com For more information, visit www.desatech.com

Show 5 more labels / short text on this page
Screws · Wall Firestop · Horizontal Vent Pipe · Screw · Wood Screw
Page 10 of the Desa (V)K42EN user manual — Horizontal Termination Configurations
Page 10 · click to enlarge
Page 10
Desa (V)K42EN — Horizontal Termination Configurations diagram (page 10)
Fig. 23 · Horizontal Termination Configurations

VENTING INSTALLATION INSTRUCTIONS Continued

10. Place fireplace into position and shim with noncombustible material if needed. Nail or screw side flanges to framing to secure unit in place. IMPORTANT: Make sure fireplace is level before securing. If fireplace is not level it will not work properly.
Desa (V)K42EN — VENTING INSTALLATION INSTRUCTIONS Continued diagram (page 10)
Fig. 24 · VENTING INSTALLATION INSTRUCTIONS Continued
Desa (V)K42EN — VENTING INSTALLATION INSTRUCTIONS Continued diagram (page 10)
Fig. 25 · VENTING INSTALLATION INSTRUCTIONS Continued
  • Recommended Applications:
  • Installation using cabinet surrounds
  • Through the wall using round or square termination (up to 12" horizontal pipe)
  • NOT FOR CORNER INSTALLATION
Desa (V)K42EN — VENTING INSTALLATION INSTRUCTIONS Continued diagram (page 10)
Fig. 26 · VENTING INSTALLATION INSTRUCTIONS Continued

Maintain 1" Minimum Air Space Around Outer Pipe When Penetrating a Wall

Vertical (V) Horizontal (H) 36 3/4" 17" max.

10 3/4" x 10 3/4" Framed Opening

Desa (V)K42EN — VENTING INSTALLATION INSTRUCTIONS Continued diagram (page 10)
Fig. 27 · VENTING INSTALLATION INSTRUCTIONS Continued

Figure 13 - Typical Horizontal Termination Cap Mounting with Additional Siding Standoff Installed

Horizontal Termination Configurations

Figures 14 through 18 show different configurations and alternatives for venting with horizontal termination. Each figure includes a chart with critical minimum and maximum dimensions which MUST be met. IMPORTANT: Remember that a horizontal run of venting must have a 1/4" rise for every 12" of run toward the termination.

Figure 14 - Horizontal Termination Configuration for Square or Round Termination

111922-01A For more information, visit www.desatech.com For more information, visit www.desatech.com

45° Elbow · Horizontal Round Termination

Page 11 of the Desa (V)K42EN user manual — SNORKEL TERMINATION INSTALLATION
Page 11 · click to enlarge
Page 11
Desa (V)K42EN — CORNER INSTALLATION diagram (page 11)
Fig. 28

VENTING INSTALLATION INSTRUCTIONS Continued

CORNER INSTALLATION

Required Vertical (V) Vertical Pipe Horizontal (H) *46 1/4" min. None 30" max. 57 1/4" min. 1 ft. 48" max. 69 1/4" min. 2 ft. 60" max. 81 1/4" min. 3 ft. 84" max. 93 1/4" min. 4 ft. 20' max.

  • Recommended Applications:
  • Corner ground floor installation
  • Ground floor installation where pipe vents horizontally through wall (over 12" horizontal pipe)
  • Basement installation where one foot clearance from ground to termination is possible

* Ground Floor Corner Venting

Desa (V)K42EN — CORNER INSTALLATION diagram (page 11)
Fig. 29
Desa (V)K42EN — CORNER INSTALLATION diagram (page 11)
Fig. 30

As Required for (V) See Chart for Pipe Section Required

Figure 15 - Horizontal Termination Configuration for Corner Installation Using One 90° Elbow

SNORKEL TERMINATION INSTALLATION

  • Recommended Applications:
  • Installations requiring a vertical rise on building exterior
  • Any installation using snorkel termination to achieve one foot above ground

Snorkel terminations are available for installations requiring a vertical rise on the exterior of the building. If installing snorkel termination below grade, you must provide proper drainage to prevent water from entering snorkel termination (see Figure 16). Do not back fill around snorkel termination.

Desa (V)K42EN — SNORKEL TERMINATION INSTALLATION diagram (page 11)
Fig. 31

Figure 16 - Snorkel Termination Configurations for Below Ground Installation

111922-01A For more information, visit www.desatech.com For more information, visit www.desatech.com

Square Termination · Snorkel Termination

Page 12 of the Desa (V)K42EN user manual — VENTING INSTALLATION INSTRUCTIONS Continued
Page 12 · click to enlarge
Page 12
Desa (V)K42EN — CORNER INSTALLATION diagram (page 12)
Fig. 32

VENTING INSTALLATION INSTRUCTIONS Continued

Desa (V)K42EN — VENTING INSTALLATION INSTRUCTIONS Continued diagram (page 12)
Fig. 33 · VENTING INSTALLATION INSTRUCTIONS Continued

The following configurations show the minimum vertical rise requirements for a horizontal system using two 90° elbows.

Horizontal (H1) + Vertical (V) Horizontal (H1) Horizontal (H2)

5' min. 2' max. 6' max. 6' min. 4' max. 12' max. 7' min. 6' max. 18' max. 8' min. 8' max. 20' max. 20' max. 8' max. 20' max.

Figure 17 - Horizontal Termination Configuration for Venting Using Two 90° Elbows

Desa (V)K42EN — VENTING INSTALLATION INSTRUCTIONS Continued diagram (page 12)
Fig. 34 · VENTING INSTALLATION INSTRUCTIONS Continued

Venting with Two 90° Elbows

Horizontal (H1) + Vertical (V) Horizontal (H2)

5' min. 6' max. 6' min. 12' max. 7' min. 18' max. 8' min. 20' max. 20' max. 20' max.

Figure 18 - Horizontal Termination Configuration for Venting Using Two 90° Elbows with Termination at 90° with Fireplace

111922-01A For more information, visit www.desatech.com For more information, visit www.desatech.com

Page 13 of the Desa (V)K42EN user manual — INSTALLATION FOR VERTICAL TERMINATION
Page 13 · click to enlarge
Page 13
Desa (V)K42EN — INSTALLATION FOR VERTICAL TERMINATION diagram (page 13)
Fig. 35

VENTING INSTALLATION INSTRUCTIONS Continued

INSTALLATION FOR VERTICAL TERMINATION

2. Assemble the desired lengths of pipe and elbows necessary to reach from the fireplace flue up through the firestop. Be sure all pipe and elbow connections are fully twist-locked (see Fig- ure 8, page 8). 3. Cut a hole in the roof using the locating hole as a center point. (Cover any exposed open vent pipes before cutting hole in roof.) The 10 3/4"x10 3/4" hole must be measured on the horizontal; actual length may be larger depending on the pitch of the roof. There must be a 1" clearance from the vent pipe to combustible materials. Frame the opening as shown in Figure 9, page 8. 4. Connect a section of pipe and extend up through the hole. Note: If an offset is needed to avoid obstructions, you must support the vent pipe every 3 feet. Use wall straps for this purpose (see Figure 19). Whenever possible, use 45° elbows instead of 90° elbows. The 45° elbow offers less restriction to the flow of the flue gases and intake air. 5. Place the flashing over the pipe section(s) extending through the roof. Secure the base of the flashing to the roof and fram- ing with roofing nails. Be sure roofing material overlaps the top edge of the flashing as shown in Figure 19. There must be a 1" clearance from the vent pipe to combustible materials. 6. Continue to add pipe sections until the height of the vent cap meets the minimum building code requirements described in Figure 7 on page 6. Note: You must increase vent height for steep roof pitches. Nearby trees, adjoining rooflines, steep pitched roofs, and other similar factors may cause poor draft or down-drafting in high winds. Increasing the vent height may solve this problem. 7. Twist-lock the vent cap onto the last section of vent pipe. Note: If the vent pipe passes through any occupied areas above the first floor, including storage spaces and closets, you must enclose pipe. You may frame and sheetrock the enclosure with standard construction material. Make sure and meet the minimum allowable clearances to combustibles. Do not fill any of the required air spaces with insulation.

Note: Vertical restrictor must be installed in all vertical installations. 1. Determine the route your vertical venting will take. If ceiling joists, roof rafters, or other framing will obstruct the venting system, consider an offset (see Figure 19) to avoid cutting load bearing members. Note: Pay special attention to these instal- lation instructions for required clearances (air space) to com- bustibles when passing through ceilings, walls, roofs, enclo- sures, attic rafters, etc. Do not pack air spaces with insulation. Also note maximum vertical rise of the venting system and any maximum horizontal offset limitations. 2. Set the fireplace in desired location. Drop a plumb line down from the ceiling to the position of the fireplace exit flue. Mark the center point where the vent will penetrate the ceiling. Drill a small locating hole at this point. Drop a plumb line from the inside of the roof to the locating hole in the ceiling. Mark the center point where the vent will penetrate the roof. Drill a small locating hole at this point.

Desa (V)K42EN — INSTALLATION FOR VERTICAL TERMINATION diagram (page 13)
Fig. 36

Figure 19 - Offset with Wall Strap and 45° Elbows

If area above is not a room, install firestop below framed hole. If area above is a room, install firestop above framed hole.

Flat Ceiling Installation 1. Cut a 10 3/4" square hole in the ceiling using the locating hole as a center point. The opening should be framed to 10 3/4"x10 3/4" (273 mm x 273 mm) inside dimensions, as shown in Figure 9 on page 8 using framing lumber the same size as the ceiling joists. If the area above the ceiling is an insulated ceiling or a room, nail firestop from the top side. This prevents loose insula- tion from falling into the required clearance space. Otherwise, install firestop below the framed hole. The firestop should be installed with no less than three nails per side (see Figure 20).

Desa (V)K42EN — INSTALLATION FOR VERTICAL TERMINATION diagram (page 13)
Fig. 37

Figure 20 - Installing Firestop

111922-01A For more information, visit www.desatech.com For more information, visit www.desatech.com

Roof Flashing · Wall Strap

Page 14 of the Desa (V)K42EN user manual — Vertical Termination Configurations
Page 14 · click to enlarge
Page 14
Desa (V)K42EN — Vertical Termination Configurations diagram (page 14)
Fig. 38 · Vertical Termination Configurations

VENTING INSTALLATION INSTRUCTIONS Continued

Vertical Termination Configurations

Desa (V)K42EN — Vertical Termination Configurations diagram (page 14)
Fig. 39 · Vertical Termination Configurations

Figures 21 through 24 show four different configurations for verti- cal termination.

5' min. 2' max. 6' min. 4' max. 7' min. 6' max. 8' min. 8' max. 20' max. 8' max.

Desa (V)K42EN — Vertical Termination Configurations diagram (page 14)
Fig. 40 · Vertical Termination Configurations

5' min. 2' max. 6' min. 4' max. 7' min. 6' max. 8' min. 8' max. 20' max. 8' max. Note: Install restrictor into inner collar of fireplace as shown. 45° Elbow

Figure 22 - Vertical Venting Configuration Using One 90° Elbow (Vertical Round High Wind Termination Shown)

Desa (V)K42EN — Vertical Termination Configurations diagram (page 14)
Fig. 41 · Vertical Termination Configurations

Venting with Two 90° Elbows

Vertical (V1) Horizontal (H)

5' min. 6' max. 6' min. 12' max. 7' min. 18' max. 8' min. 20' max.

Figure 21 - Vertical Venting Configuration Using Two 90° Elbows with Two Horizontal Runs (Vertical Round High Wind Termination Shown)

Figure 23 - Vertical Venting Configuration Using Two 90° Elbows (Vertical Round High Wind Termination Shown)

111922-01A For more information, visit www.desatech.com For more information, visit www.desatech.com

Page 15 of the Desa (V)K42EN user manual — VENTING INSTALLATION INSTRUCTIONS Continued
Page 15 · click to enlarge
Page 15
Desa (V)K42EN — Vertical Termination Configurations diagram (page 15)
Fig. 42 · Vertical Termination Configurations

High Altitude Installation Parts Lists for Venting Kits and Components

VENTING INSTALLATION INSTRUCTIONS Continued

When installing this fireplace at an elevation above 4500 feet (in Canada), check with local authorities. Consult your local gas company to help determine the proper orifice for your location. For assistance with any high altitude installation contact DESA’s Customer Service Department at 1-866-672-6040.

Desa (V)K42EN — VENTING INSTALLATION INSTRUCTIONS Continued diagram (page 15)
Fig. 43 · VENTING INSTALLATION INSTRUCTIONS Continued

PARTS LISTS FOR VENTING KITS AND COMPONENTS DESA (5/8") Pipe & Vent Kits Number Description P58-6 6" Section Double Wall Pipe, Galvanized P58-12 12" Section Double Wall Pipe, Galvanized P58-24 24" Section Double Wall Pipe, Galvanized P58-36 36" Section Double Wall Pipe, Galvanized P58-48 48" Section Double Wall Pipe, Galvanized PA58-712 Adjustable 7"-12" Section Double Wall Pipe, Galvanized FPA58-6 6" Duravent Collar to FMI Pipe Adaptor (6" Collar/Pipe

Section) DPA58-6 6" FMI Collar to Pipe Duravent Adaptor (6" Collar/Pipe

Section) E58-45 45° Elbow, Galvanized E58-90 90° Elbow, Galvanized FSE58-45 45° Starter Elbow, Galvanized (Duravent Collar to

FMI Pipe) DSE58-45 45° Starter Elbow, Galvanized (FMI Collar to Duravent

Pipe) VKG-58 Ground Floor Vent Kit VKB-58 Basement Vent Kit VKS-58 Snorkel Vent Kit VKR-58 Roof Vent Kit VKC-58 Corner Vent Kit HTK Horizontal Round Termination Kit HT-58 Horizontal Round Termination, Galvanized HTS-58 Horizontal Square Termination, Galvanized VT-58 Vertical Round Termination, Galvanized ST-58-14 14" Snorkel Termination, Galvanized ST-58-36 36" Snorkel Termination, Galvanized SC-58 Storm Collar, Galvanized WF-58 Wall Firestop, Galvanized RF-58-6 Roof Flashing - 0 to 6/12 Pitch, Galvanized RF-58-12 Roof Flashing - 6/12 to 12/12 Pitch, Galvanized VR-58 Vertical Restrictor, Galvanized S-58 Vinyl Siding Standoff, Galvanized WS-58 Wall Strap CS-58 Cathedral Ceiling Support FP-58 Firestop Plate SF-58 Stucco Flashing - For use with HTS-5

Figure 24 - Vertical Venting Configuration With No Horizontal Run (Vertical Round High Wind Termination Shown) HIGH ALTITUDE INSTALLATION

Your DESA direct-vent fireplace has been tested and approved for elevations from 0-2000 feet (USA) and elevations from 0-4500 feet (Canada). When installing this fireplace at an elevation above 2000 feet (in the USA), you may need to decrease the input rating by changing the existing burner orifice to a smaller size. Reduce input 4% for each 1000 feet above sea level. Check with your local gas company for proper orifice size identification.

111922-01A For more information, visit www.desatech.com For more information, visit www.desatech.com

Page 16 of the Desa (V)K42EN user manual — Model BK Installation
Page 16 · click to enlarge
Page 16
Desa (V)K42EN — FIREPLACE INSTALLATION diagram (page 16)
Fig. 44

FIREPLACE INSTALLATION

CHECK GAS TYPE

4. Be certain that all wire terminals are securely attached to ter- minals on blower motor and that the screw retaining the green ground wire is tight. 5. Mount speed control box to switch bracket by placing the plastic control shaft forward through the opening in the switch bracket (see Figure 26). 6. While supporting speed control, secure control shaft with lock nut by pushing and turning lock nut with pliers clockwise until it is tight against front panel. Place control knob provided on shaft. 7. Turn on power to duplex outlet if previously turned off per the warning in column 1. 8. Plug in blower power cord. a. If your firebox is installed as a freestanding unit with an

Use proper gas type for the fireplace unit you are installing. If your gas supply is not correct, do not install fireplace. See retailer where you purchased the fireplace for proper fireplace according to your gas type.

INSTALLING OPTIONAL BLOWER ACCESSORY

Desa (V)K42EN — INSTALLING OPTIONAL BLOWER ACCESSORY diagram (page 16)
Fig. 45

accessory mantel, determine whether the power cord will exit the left side or the right side of the firebox. Route power cord through exit hole and plug the power cord into a wall receptacle near the firebox. b.If your firebox installation is recessed and/or pre-wired,

Model BK Installation

plug the power cord into the duplex outlet provided. Refer to your firebox owner’s manual for instructions on wiring the duplex outlet.

Follow all instructions provided in the blower accessory kit. 1. Attach the power cord to the blower motor by firmly pushing the two female terminals at the end of the power cord onto the two spade terminals on the blower motor (see Figure 25). 2. Attach green ground wire from power cord to blower housing using screw provided (see Figure 25). Tighten screws securely. 3. Place the blower against the lower rear wall of the firebox outer wrapper with the exhaust port directed upward. The blower will fit inside the back opening and be held in position against the back wall by the magnets (see Figure 25).

9. Check to make sure that the power cord is completely clear of the blower wheel and that there are no other foreign objects in blower wheel. Turn blower on and check for operation. Turn blower off by turning knob fully counterclockwise before continuing.
Desa (V)K42EN — Model BK Installation diagram (page 16)
Fig. 46 · Model BK Installation
Desa (V)K42EN — Model BK Installation diagram (page 16)
Fig. 47 · Model BK Installation

Duplex Outlet (Located underneath firebox floor against lower right outside wall)

Figure 26 - Attaching Speed Control to Firebox

111922-01A For more information, visit www.desatech.com For more information, visit www.desatech.com

Speed Control · Control Knob · Control Shaft Locknut

Page 17 of the Desa (V)K42EN user manual — Model BKT Installation
Page 17 · click to enlarge
Page 17

FIREPLACE INSTALLATION Installing Optional Blower Accessory (Cont.)

FIREPLACE INSTALLATION Continued

10. Peel off the backing paper and stick the supplied wiring diagram decal on the firebox bottom approximately 12" in front of the blower (see Figure 27).

6. While supporting speed control, secure control shaft with lock nut by pushing and turning lock nut with pliers clockwise un- til it is tight against mounting plate. Place control knob pro- vided on shaft (see Figure 26, page 16). 7. Check to make sure that the power cord is completely clear of the blower wheel and that there are no other foreign objects in blower wheel. Also double check all wire leads and make sure wire rout- ing is not pinched or in a precarious position. Correct accordingly. 8. Turn on power to duplex outlet if previously turned off per the warning in column 1, page 16. 9. Plug in blower power cord to duplex outlet. 10. The blower will only run when the speed control knob is in the ON position and the thermal switch senses temperature after the fireplace begins to heat up. The blower speed can be ad- justed by rotating the control knob. To turn off, turn knob fully counterclockwise until it clicks off. If the blower is ON and has been running with the fireplace operating, the blower will continue to run for a short time after the fireplace has been turned off. As the thermal switch cools down, the blower shuts down automatically. 11. Peel off the backing paper and stick the supplied wiring dia- gram decal on the firebox bottom approximately 12" in front of the blower (see Figure 27). .

110/115 V.A.C.

Wiring Diagram Decal 12" in Front of Blower

Figure 27 - Location of Wiring Diagram Decal (Model May Vary From Illustration)

Model BKT Installation

Note: When installing the BKT thermostatically-controlled blower, you must first secure the thermal switch bracket to the blower if it has not already been factory installed. 1. Place the green ground wire with ring terminal between the bottom hole on the thermal switch bracket and the top ear hole on the blower assembly. Insert the phillips screw into all three pieces and tighten securely (see Figure 28). 2. Connect wire harness and power cord terminals. Connect the blue jumper wire to the blower motor terminal and the right side terminal of the thermal switch. Connect the black wire to the left side of the thermal switch and the white wire to the other remaining blower motor terminal.

Desa (V)K42EN — Model BKT Installation diagram (page 17)
Fig. 48 · Model BKT Installation

Note: The power cord outer insulation sleeve may have to be stripped slightly to allow enough wire length to reach and make all connections. DO NOT trim excessive length away. Just enable enough to make all connections securely. 3. Place the blower against the lower rear wall of the firebox outer wrapper with the exhaust port directed upward and the thermodisc positioned up near the fireplace bottom. The thermodisc must be oriented near the fireplace bottom as shown in Figure 28 in order to sense temperature and properly operate. The blower will be held in position against the back wall by the magnets incorpo- rated onto the blower housing (see Figure 28). 4. Be certain that all wire terminals are securely attached to ter- minals on blower motor and thermal switch, and that the screw for the thermodisc bracket and green ground wire is tight. 5. Mount the speed control box against the mounting plate pro- vided in the lower fireplace cavity by placing the plastic control shaft forward through the round hole (see Figure 26, page 16).

Route BKT Blower Through This Area

Blower Location Side View Firebox Bottom

Figure 28 - Blower Model BKT

111922-01A For more information, visit www.desatech.com For more information, visit www.desatech.com

Show 14 more labels / short text on this page
Blower Motor · White White Black · On · Variable Fan Switch · Green · Black · Black · Black · Off · Power Cord · Thermal Switch Bracket · Black Wire · Phillips Screw · Magnets
Page 18 of the Desa (V)K42EN user manual — INSTALLING GAS PIPING TO FIREPLACE LOCATION
Page 18 · click to enlarge
Page 18
Desa (V)K42EN — Blower Wiring Diagram diagram (page 18)
Fig. 49 · Blower Wiring Diagram

Installing Optional Blower Accessory (Cont.) Installing Gas Piping to Fireplace Location

FIREPLACE INSTALLATION Continued

Blower Wiring Diagram

For propane/LP connection only, the installer must supply an external regulator. The external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 11 and 14 inches of water. If you do not reduce incoming gas pressure, fireplace regulator damage could occur. Install external regulator with the vent pointing down as shown in Figure 30. Pointing the vent down protects it from freezing rain or sleet.

Desa (V)K42EN — Blower Wiring Diagram diagram (page 18)
Fig. 50 · Blower Wiring Diagram

Variable Fan Switch Fan Switch

Desa (V)K42EN — Blower Wiring Diagram diagram (page 18)
Fig. 51 · Blower Wiring Diagram
Desa (V)K42EN — Blower Wiring Diagram diagram (page 18)
Fig. 52 · Blower Wiring Diagram

Installation must include an equipment shutoff valve, union, and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from fireplace (see Figure 31, page 19).

Figure 29 - Blower Wiring Diagram for Thermostat-Controlled Models

INSTALLING GAS PIPING TO FIREPLACE LOCATION

Check your building codes for any special requirements for locating equipment shutoff valve to fireplaces.

Apply pipe joint sealant lightly to male NPT threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged fireplace valves.

Propane/LP Supply Tank External Regulator

  • Before installing fireplace, make sure you have the items listed below.
  • external regulator (supplied by installer)
  • piping (check local codes)
  • sealant (resistant to propane/LP gas)
  • equipment shutoff valve *
  • test gauge connection *
  • sediment trap
  • tee joint
  • pipe wrench
  • approved flexible gas line with gas connector (if allowed by local codes)

Figure 30 - External Regulator with Vent Pointing Down (Propane/LP Only)

* A CSA design-certified equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Purchase the CSA design-certified equipment shutoff valve from your retailer.

111922-01A For more information, visit www.desatech.com For more information, visit www.desatech.com

Installation Items Needed · Vent Pointing Down

Page 19 of the Desa (V)K42EN user manual — CONNECTING FIREPLACE TO GAS SUPPLY
Page 19 · click to enlarge
Page 19
Desa (V)K42EN — CHECKING GAS CONNECTIONS diagram (page 19)
Fig. 53

FIREPLACE INSTALLATION Installing Gas Piping to Fireplace Location (Cont.)

FIREPLACE INSTALLATION Continued

Red Surface Indicates For Propane/LP Use Only

Desa (V)K42EN — FIREPLACE INSTALLATION Continued diagram (page 19)
Fig. 54 · FIREPLACE INSTALLATION Continued

We recommend that you install a sediment trap/drip leg in supply line as shown in Figure 31. Locate sediment trap/drip leg where it is within reach for cleaning. Install in piping system between fuel supply and fireplace. Locate sediment trap/drip leg where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into fireplace gas con- trols. If sediment trap/drip leg is not installed or is installed wrong, fireplace may not run properly.

1/2" NPT Incoming Gas Line Inlet Pressure Tap Outlet Pressure Tap

Figure 32 - Connecting Flexible Gas Line to Electronic Valve

CSA Design-Certified Equipment Shutoff Valve with 1/8" NPT Tap*

Desa (V)K42EN — FIREPLACE INSTALLATION Continued diagram (page 19)
Fig. 55 · FIREPLACE INSTALLATION Continued

CHECKING GAS CONNECTIONS

Natural - From Gas Meter (5.5" W.C. to 10.5" W.C. Pressure) Propane/LP From External Regulator (11" W.C. to 14" W.C. Pressure)

Desa (V)K42EN — CHECKING GAS CONNECTIONS diagram (page 19)
Fig. 56

Pressure Testing Gas Supply Piping System

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa) 1. Disconnect fireplace and its individual equipment shutoff valve from gas supply piping system. Pressures in excess of 1/2 psig (3.5 kPa) will damage fireplace gas regulator. 2. Cap off open end of gas pipe where equipment shutoff valve was connected. 3. Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas fireplace or opening main gas valve located on or near gas meter for natural gas fire- place, or using compressed air. 4. Check all joints of gas supply piping system. Apply noncorro- sive leak detection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once. 5. Reconnect fireplace and equipment shutoff valve to gas sup- ply. Check reconnected fittings for leaks.

Figure 31 - Gas Connection

* The CSA design-certified equipment shutoff valve may be sup- plied with the appliance or you can purchase it from your retailer.

CONNECTING FIREPLACE TO GAS SUPPLY

Installation Items Needed

  • 5/16" hex socket wrench or nut-driver
  • sealant (resistant to propane/LP gas, not provided) 1. Open lower louver door panel by gently pulling forward. 2. Route flexible gas line (provided by installer) from equipment shutoff valve to fireplace. Route flexible gas supply line through one of the access holes on side of fireplace. 3. Attach flexible gas line from gas supply to control valve (see Figure 32). 4. Check all gas connections for leaks. See Checking Gas Connections .

111922-01A For more information, visit www.desatech.com For more information, visit www.desatech.com

Sediment Trap/Drip Leg

Page 20 of the Desa (V)K42EN user manual — Removing Louver Panels
Page 20 · click to enlarge
Page 20
Desa (V)K42EN — REMOVING/REPLACING GLASS DOOR diagram (page 20)
Fig. 57

FIREPLACE INSTALLATION Continued

Pressure Testing Fireplace Gas Connections 1. Open equipment shutoff valve (see Figure 33). 2. Open propane/LP supply tank valve for propane/LP fireplace or main gas valve located on or near gas meter for natural gas fireplace. 3. Make sure control knob of fireplace is in the OFF position. 4. Check all joints from equipment shutoff valve to gas valve (see Figure 34 for propane/LP or Figure 35 for natural gas). Apply noncorrosive leak detection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once. 5. Light fireplace (see Operating Fireplace, pages 24 and 25). Check all other internal joints for leaks. 6. Turn off fireplace (see To Turn Off Gas to Appliance, page 24).

Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa) 1. Close equipment shutoff valve (see Figure 33). 2. Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas fireplace or opening main gas valve located on or near gas meter for natural gas fire- place, or using compressed air. 3. Check all joints from propane/LP supply tank or gas meter to equip- ment shutoff valve (see Figure 34 for propane/LP or Figure 35 for natural gas). Apply noncorrosive leak detection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

REMOVING/REPLACING GLASS DOOR

Figure 33 - Equipment Shutoff Valve

Desa (V)K42EN — REMOVING/REPLACING GLASS DOOR diagram (page 20)
Fig. 58

Removing Louver Panels

Remove the top and bottom louver panels by simultaneously pulling both top end spring latches towards the center of the appliance until they are disengaged from the locating holes (see Figure 36). Repeat for bottom spring latches and pull the louvers outward. To install or replace items removed, simply reverse the procedures above.

Figure 34 - Checking Gas Joints for Propane/LP Gas Fireplace

Desa (V)K42EN — Removing Louver Panels diagram (page 20)
Fig. 59 · Removing Louver Panels

Figure 36 - Removing Louver Panel

Figure 35 - Checking Gas Joints for Natural Gas Fireplace

111922-01A For more information, visit www.desatech.com For more information, visit www.desatech.com

Show 7 more labels / short text on this page
Open · Equipment Shutoff Valve · Closed · Equipment Shutoff Valve · Equipment Shutoff Valve · Spring Latch · Louver Panel
Page 21 of the Desa (V)K42EN user manual — Cleaning Glass Door
Page 21 · click to enlarge
Page 21
Desa (V)K42EN — Removing Glass Door diagram (page 21)
Fig. 60 · Removing Glass Door

FIREPLACE INSTALLATION Removing/Replacing Glass Door (Cont.) Installing Optional Brick Liner Models BL42DA(SA), BL42DHA(SA)

FIREPLACE INSTALLATION Continued

Removing Glass Door

INSTALLING BRICK LINER MODELS BL42DA(SA), BL42DHA(SA)

If replacement of glass is necessary, the entire assembly, glass and frame, must be replaced. If glass is broken, wear gloves and tape the remaining fragments onto the frame. 1. Remove screen assembly by pushing the rod either left or right and then down and forward to remove screen/rod assembly from the firebox. Set assembly aside. 2. Lift up on latches to unlock. There are two on top of firebox and two below firebox that hold glass door in place (see Figure 37). 3. While holding glass door to prevent it from falling and caus- ing injury, remove the five screws from the hinge located on the left side of door frame assembly (see Figure 37). 4. Remount the new frame at the hinge with five new screws before closing door. This will ensure seating of the gasket. 5. Close glass door frame. Lock latches by placing the bar under the tab on door and pushing down and back on latch (see Figure 37). 6. Replace screen/rod assembly by reversing step 1. 7. Replace louvers by reversing procedure under Removing Lou- ver Panels, page 20.

You may purchase brick liner from your local retailer or see Accessories, page 34.

1. Remove top and bottom louvers to allow access to door latches. 2. Remove screen, unlock door latches and open glass door. See Removing/Replacing Glass Door, steps 1 and 2. 3. If installing brick liner in new fireplace, go to step 4. If install- ing brick liner in an existing fireplace, carefully remove logs, lava rock, and ember material. 4. Remove three screws from deflector shield on the inside top of firebox. Set shield and screws aside. 5. Install rear brick panel first. Rest bottom edge of panel on back edge of grate (see Figure 38). 6. Install left side brick panel by sliding it between the grate and the side of the firebox (see Figure 38). 7. Install the right brick panel using the same method described in step 6 for left brick panel. 8. Replace deflector shield using screws removed in step 4. 9. Install logs, lava rock and glowing embers. See Installing Logs, Lava Rock and Glowing Embers, page 22. 10. Close glass door and lock latches on top and bottom of door and replace screen. See Removing/Replacing Glass Door, steps 5 and 6. 11. Close top and bottom louvers.

Desa (V)K42EN — Removing Glass Door diagram (page 21)
Fig. 61 · Removing Glass Door

Figure 37 - Removing/Replacing Glass Door

Cleaning Glass Door

Desa (V)K42EN — Cleaning Glass Door diagram (page 21)
Fig. 62 · Cleaning Glass Door

See Cleaning and Maintenance on page 26.

Figure 38 - Installing Rear, Left and Right Brick Panels

111922-01A For more information, visit www.desatech.com For more information, visit www.desatech.com

Latch · Screw · Rear Brick Panel

Page 22 of the Desa (V)K42EN user manual — WALL SWITCH INSTALLATION
Page 22 · click to enlarge
Page 22
Desa (V)K42EN — INSTALLING LOGS, LAVA ROCK AND GLOWING EMBERS diagram (page 22)
Fig. 63

Installing Logs, Lava Rock and Glowing Embers Wall Switch Installation

FIREPLACE INSTALLATION Continued

INSTALLING LOGS, LAVA ROCK AND GLOWING EMBERS

6. Rest log #8 (left crossover log) onto log #3 and rest log #9 (right crossover log) onto logs #4 and #5 as shown in Figure 42. 7. Pull ember material apart into pieces no larger than a dime. Place these pieces loosely and sparingly directly onto the exposed front section of the burner (see Figure 44). This will create the glowing ember appearance as the flame touches the ember material. Do not block air slots by using too much ember material in one area. It is not necessary to use all of the ember material provided.

Each log is marked with a number. These numbers will help you identify the log when installing. It is very important to install these logs exactly as instructed. Do not modify logs. Only use logs supplied with fireplace.

Open louvers, remove screen, unlock door latches, and open glass door. See Removing/Replacing Glass Door, steps 1 and 2 on page 21. Install logs according to instructions for fireplace model numbers. 1. Place log #1 (left base log) onto pin on left side of burner as shown in Figure 39. 2. Place log #2 (right base log) onto pin on right side of burner as shown in Figure 39. 3. Place logs #3 (left front log) and log #4 (right front log) onto pins as shown in Figure 40. 4. Place log #5 (right rear log) onto pins on right rear of burner (see Figure 41). Rest log #6 (middle crossover log) on top of log number 2 as shown in Figure 41. 5. Place back end of log #7 (left rear log) onto pin on left rear burner and rest front onto log #1 as shown in Figure 42.

Desa (V)K42EN — INSTALLING LOGS, LAVA ROCK AND GLOWING EMBERS diagram (page 22)
Fig. 64
8. Close glass door, lock door latches, replace screen, and close louvers (see Removing/Replacing Glass Door , steps 5 through 7 on page 21).

1 2 3 4

Figure 39 - Installing Logs No. 1 and No. 2

Figure 40 - Installing Logs No. 3 and No. 4

Figure 44 - Placing Ember Material on Burner

Desa (V)K42EN — 1 2 3 4 diagram (page 22)
Fig. 65

WALL SWITCH INSTALLATION

The installation of a wall switch allows you to activate the gas control valve and turn the fireplace on and off. The wall switch is to be connected to the incoming 120 volt regular household wiring that supplies the electricity to the fireplace. Refer to wiring diagram below.

Figure 42 - Installing Log No. 7 Figure 41 - Installing Logs No. 5 and No. 6

Figure 43 - Installing Logs No. 8 and No. 9

111922-01A For more information, visit www.desatech.com For more information, visit www.desatech.com

Ember Material

Page 23 of the Desa (V)K42EN user manual — EV2
Page 23 · click to enlarge
Page 23
Desa (V)K42EN — OPTIONAL REMOTE CONTROL INSTALLATION (Model WRC) diagram (page 23)
Fig. 66 · OPTIONAL REMOTE CONTROL INSTALLATION (Model WRC)

FIREPLACE INSTALLATION Continued

OPTIONAL REMOTE CONTROL INSTALLATION (Model WRC)

Note: If using optional wireless hand-held remote control, the wall switch must be in the ON position to be operational. The remote control then becomes the switching mechanism for fireplace operation. 1. Open lower louver panel. 2. The WRC model receiver does not require a battery. The re- ceiver can be installed by first plugging the short extension cord into the fireplace receptacle. Then plug the receiver unit into the extension cord. Finally plug the ignition module plug into the receiver unit (see Figure 45). 3. Activate the remote handset battery by removing the insulat- ing tab on the back of the handset (see Figure 46). The battery is included pre-installed. 4. Once the battery is activated the unit is ready to use. 5. Close lower louver panel.

Figure 45 - Installing the WRC Remote Receiver

Battery Cover 12 Volt Battery

Pull to Remove Insulation Tab

Figure 46 - Installing Battery into Back of Handset

WIRING DIAGRAM

(SUPPLIED) WALL SWITCH

INCOMING MAIN

(NOT SUPPLIED)

GAS SUPPLY

ON

OFF

BLACK

INCOMING

PV GND PV/MV TR MV TH IGN

WHITE

120V AC (FUSE BOX OR BREAKER)

GREEN

EV1

BLACK

WHITE

GREEN

ELECTRICAL RATING:

120v, 60Hz, 0.7A

EV2

24V AC

STEP DOWN TRANSFORMER

120V AC

OPTIONAL REMOTE CONTROL

GAS LINE TO

BURNER

111922-01A For more information, visit www.desatech.com For more information, visit www.desatech.com

Show 7 more labels / short text on this page
Fireplace Receptacle · Remote Control Receiver · Ignition Module Plug · Extension Cord · Back of Handset · Pilot Burner · Pilot Gas Line
Page 24 of the Desa (V)K42EN user manual — OPTIONAL REMOTE
Page 24 · click to enlarge
Page 24
Desa (V)K42EN — OPTIONAL REMOTE CONTROL INSTALLATION (Model WRC) diagram (page 24)
Fig. 67 · OPTIONAL REMOTE CONTROL INSTALLATION (Model WRC)

For Your Safety Read Before Lighting Lighting Instructions To Turn Off Gas To Appliance Optional Remote Operation

OPERATING FIREPLACE

  • 11. Visually locate the pilot. The ignitor should be gin to spar k and the main b urner should ignite once f lame a ppears at pilot.
  • If lighting the a ppliance f or the first time eac h season, it may take several attempts before the suppl y gas can r each the pilot and main b urners.
  • If the appliance will not sta y lit after se veral attempts, follow the instr uctions To Turn Off Gas To Appliance , below, and call y our ser vice tec hnician or g as supplier .
Desa (V)K42EN — OPERATING FIREPLACE diagram (page 24)
Fig. 68
  • A. This appliance is equipped with an ignition de vice w hich automatically lights the pilot. Do not try to light the pilot by hand. B. BEFORE LIGHTING smell all ar ound the a ppliance ar ea for gas. Be sur e to smell ne xt to the floor because some g as is heavier than air and will settle on the f loor. WHAT TO DO IF YOU SMELL GAS
  • Do not try to light any appliance.
  • Do not touch any electric switch.
  • Do not use an y phone in y our b uilding .
  • Immedia tely call y our g as supplier fr om a neighbor’ s phone . Follow the gas supplier’ s instructions.
  • If you cannot r each your g as supplier , call the f ire department. C. Do not use this a ppliance if an y part has been under w ater. Immedia tely call a qualif ied ser vice tec hnician to inspect the appliance and to r eplace an y part of the contr ol system and an y gas control which has been under w ater.
Desa (V)K42EN — OPERATING FIREPLACE diagram (page 24)
Fig. 69

Figure 47 - Turning Equipment Shutoff Valve to the OFF Position

TO TURN OFF GAS

TO APPLIANCE

1. Turn off the wall switch. 2. Turn off all electr ic power to the a ppliance if ser vice is to be perf ormed. 3. Open lo wer louv er panel. 4. Remove front hear th brick and contr ol access panel. 5. Turn equipment shutof f valve c lockwise Clockwise to OFF. Do not force. 6. Close lower louv er panel.
Desa (V)K42EN — TO TURN OFF GAS diagram (page 24)
Fig. 70

Sensing Rod Pilot Burner

1. STOP! Read the saf ety information, above. 2. Turn off all electr ic po wer to the a ppliance . 3. Turn wall switch to the OFF position. 4. Open lo wer louv er panel. 5. Turn equipment shutof f valve clockwise Clockwise to the OFF position (see F igure 47). Do not f orce. 6. Wait five (5) min utes to c lear out an y gas. Then smell f or gas, inc luding near the f loor. If you smell g as, STOP! Fol- low “B” in the saf ety information above. If you don’t smell gas, go to the next step. 7. Turn equipment shutof f valve counter clockwise C-clockwise to the ON position. Do not f orce. 8. Close lower louv er panel. 9. Turn on all electr ic power to the a ppliance . 10. Turn the w all switch to the ON position.

Figure 48 - Pilot

OPTIONAL REMOTE

OPERATION

Note: The WRC receiver and hand-held remote control kit must be purchased separately (see Accessories, page 34). Follow installation instructions on page 23. 1. Turn equipment shutof f valve to ON position. You can no w turn the burner on and of f with the hand-held r emote contr ol unit. IMPORTANT: Be sur e to pr ess the ON/OFF b uttons on the hand-held r emote contr ol unit for up to 3 seconds to assur e proper oper ation. 2. Press the ON/OFF b utton to turn the b urner on and of f.

111922-01A For more information, visit www.desatech.com For more information, visit www.desatech.com

Adjustment Screw · Equipment Shutoff Valve · Ignitor

Page 25 of the Desa (V)K42EN user manual — BURNER FLAME PATTERN
Page 25 · click to enlarge
Page 25
Desa (V)K42EN — OPTIONAL REMOTE CONTROL INSTALLATION (Model WRC) diagram (page 25)
Fig. 71 · OPTIONAL REMOTE CONTROL INSTALLATION (Model WRC)

OPERATING FIREPLACE Continued

INSPECTING BURNERS Check pilot flame pattern and burner flame patterns often.

PILOT ASSEMBLY

OPERATING OPTIONAL

BLOWER ACCESSORY

The pilot assembly is factory preset for the proper flame. Alterations may have occurred during shipping and handling. The pilot is located on the back right hand side of the burner.

Locate the blower controls by opening the lower louver panel on the fireplace. Blower controls are located on the left side of the switch bracket to the left just inside the louver panel.

The flame must envelope 1/4" of top of the ignitor/sensor and grounding stem.

The BK manual blower and the BKT thermostatically-con- trolled blower have an ON setting and an OFF setting. The blower will only run when the switch is in the ON position. In the OFF position, the blower will not operate.

  • If your pilot assembly does not meet these requirements:
  • Turn the adjustment screw marked PILOT clockwise to decrease or counterclockwise to increase the flame to proper size (see Figure 47, page 24). Do not remove the adjustment screw.
  • see Troubleshooting , pages 27 and 28

Note for BKT Only: If you are using BKT blower with optional thermostat (wall mounted or remote control) for the fireplace, your fireplace and blower will not turn on and off at the same time. The fireplace may run for several minutes before the blower turns on. After the heater modulates to the pilot position, the blower will continue to run. The blower will shut off after the firebox temperature decreases.

The blower helps distribute heated air from the fireplace. Periodically check the louvers of the firebox and remove any dust, dirt, or other obstructions that will hinder the flow of air.

Figure 49 - Correct Pilot Flame Pattern

BURNER FLAME PATTERN

Burner flames will be steady; not lifting or floating. Flame patterns will be different from unit to unit and will vary depending on installation type and weather conditions.

If the vent configuration is installed incorrectly, the flames will lift or "ghost". This can be dangerous. Inspect the flames after installa- tion to ensure proper installation and performance.

Figure 50 shows a typical flame pattern.

  • If burner flame pattern differs from that described:
  • turn fireplace off (see To Turn Off Gas to Appliance , page 24)
  • see Troubleshooting , pages 27 and 28

Figure 50 - Typical Flame Pattern

111922-01A For more information, visit www.desatech.com For more information, visit www.desatech.com

Pilot Burner · Sensing Rod · Ignitor/Sensor

Page 26 of the Desa (V)K42EN user manual — GLASS DOOR
Page 26 · click to enlarge
Page 26
Desa (V)K42EN — OPTIONAL REMOTE CONTROL INSTALLATION (Model WRC) diagram (page 26)
Fig. 72 · OPTIONAL REMOTE CONTROL INSTALLATION (Model WRC)

CLEANING AND MAINTENANCE

Desa (V)K42EN — CLEANING AND MAINTENANCE diagram (page 26)
Fig. 73

Use only the tempered glass door replacement intended for this fireplace (see Replacement Parts, page 29 for detail on ordering). No substitutions may be made. See Removing/Replacing Glass Door, page 21 for instructions for replacing glass door.

  • PILOT AND BURNERS
  • Remove ember material before cleaning burners and replace when cleaning is complete.
  • Burner and controls should be cleaned with compressed air to remove dust, dirt, or lint.
  • Use a vacuum cleaner or small, soft bristled brush to remove excess dust, dirt, or lint.

GLASS DOOR

Desa (V)K42EN — GLASS DOOR diagram (page 26)
Fig. 74
  • LOGS
  • If you remove logs for cleaning, refer to Installing Logs, Lava Rock, and Glowing Embers , page 22, to properly replace logs.
  • Use a vacuum cleaner to remove any carbon buildup on logs.
  • Replace log(s) if broken. See Replacement Parts on page 29.
  • Replace ember material periodically as needed. See Replacement Parts on page 29.

Glass must be cleaned periodically. During start-up it is normal for condensation to form on the inside of the glass causing lint, dust, and other airborne particles to cling to the glass surface. During initial start-up a slight film may form on the glass due to paint curing. The glass should be cleaned several times with a non-ammonia, non- abrasive household cleaner and warm water after the first two weeks of operation. Thereafter, clean the glass two or three times during each heating season, depending on the usage and circumstances present. Refer to Removing/Replacing Glass Door on page 21 of this manual when removing glass door for cleaning.

VENTING SYSTEM Conduct annual inspection of the venting system following these guidelines: 1. Check areas of venting system that are exposed to the weather for corrosion (rust spots or streaks and, in extreme cases, holes). Have these items replaced immediately by a qualified service person. 2. Remove the vent cap and shine a flashlight into the vent. Re- move any foreign material. 3. Check for evidence of excessive condensation. Continuous condensation can cause corrosion of caps, pipes, and fittings and can be caused by having excessive lateral runs, too many elbows, or exterior portions of the system being exposed to cold weather. 4. Inspect joints to verify that no pipe section or fitting has been disturbed and loosened. Check mechanical supports such as wall straps for rigidity.

Desa (V)K42EN — GLASS DOOR diagram (page 26)
Fig. 75

If glass has been broken, carefully remove glass door (see Remov- ing/Replacing Glass Door, page 21). Vacuum all glass pieces with a shop vac.

111922-01A For more information, visit www.desatech.com For more information, visit www.desatech.com

Page 27 of the Desa (V)K42EN user manual — OBSERVED PROBLEM
Page 27 · click to enlarge
Page 27
Desa (V)K42EN — OPTIONAL REMOTE CONTROL INSTALLATION (Model WRC) diagram (page 27)
Fig. 76 · OPTIONAL REMOTE CONTROL INSTALLATION (Model WRC)

The two most common causes of a malfunctioning gas appliance are: 1. Loose wiring connections 2. Construction debris clogging the pilot and/or gas control valve filter

OBSERVED PROBLEM

POSSIBLE CAUSE

REMEDY

Ignitor will not spark or pilot will not light

1. No gas supply, or shutoff valve is OFF

1. Check to see if you have gas supply and that equipment shutoff valve is opened 2. Repeat lighting procedure several times to purge all air out of lines. If after re- peated attempts appliance does not light, call for qualified service and repair. 3. Remove debris and dirt, inspect and clean any other possible obstructions 4. Contact your gas supplier to check pressure 5. Have a qualified technician replace pi- lot line 6. Replace control valve (Refer to Replace- ment Parts, page 29) 7. Check that main power is on and that all wire connections are made correctly to the ignition model (see Wiring Diagram, page 23). Check for 24 VAC at the sec- ondary side of the transformer. If 24 VAC is present, and the module does not oporate, have the module replaced oth- erwise have the transformer replaced. 8. Open vent damper until fully locked in OPEN position

2. Air in gas line
3. Construction debris clogging pilot orifice
4. Low gas pressure
5. Kinked pilot line
6. Control valve knob is not opening
7. No power to unit or the ignition module or power transformer is bad
8. Vent damper not fully open

Pilot will not stay lit

1. Loose wiring on ignitor wire to ignition module and/or poor ground to ignition module
1. Check wiring connection. Refer to wiring diagram (see Wiring Diagram , page 23) and/or check ground wire to ignition module 2. Clean and adjust pilot burner and check gas supply and inlet pressure to unit
2. Pilot flame too low to sense

No gas to burner, although wall switch and valve are set to the ON position

1. Wall switch wires defective or too long
1. Check electrical connections
1. Pilot flame may be too low, causing safety pilot to “drop out” 2. Improper venting or excessive blockage
1. Clean and adjust pilot flame for maximum flame impingement on thermopile 2. Have the vent system inspected, including the termination cap. Remove any restriction or obstruction

111922-01A For more information, visit www.desatech.com For more information, visit www.desatech.com

Frequent pilot outage

Page 28 of the Desa (V)K42EN user manual — OBSERVED PROBLEM
Page 28 · click to enlarge
Page 28
Desa (V)K42EN — OPTIONAL REMOTE CONTROL INSTALLATION (Model WRC) diagram (page 28)
Fig. 77 · OPTIONAL REMOTE CONTROL INSTALLATION (Model WRC)

TROUBLESHOOTING Continued

Desa (V)K42EN — TROUBLESHOOTING Continued diagram (page 28)
Fig. 78 · TROUBLESHOOTING Continued
  • WARNING: If you smell gas
  • Shut off gas supply.
  • Do not try to light any appliance.
  • Do not touch any electrical switch; do not use any phone in your building.
  • Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
  • If you cannot reach your gas supplier, call the fire department.

OBSERVED PROBLEM

POSSIBLE CAUSE

REMEDY

Fireplace produces a clicking/ticking noise just after burner is lit or shut off

1. Metal expanding while heating or contracting while cooling
1. This is common with most fireplaces. If noise is excessive, contact qualified service person

Slight smoke or odor during initial operation

1. Residues from manufacturing processes and logs curing
1. Problem will stop after a few hours of operation

Gas odor even when control knob is in OFF position

1. Gas leak. See Warning statement at top of page 2. Control valve defective
1. Locate and correct all leaks (see Checking Gas Connections , pages 19 and 20) 2. Replace control valve

Gas odor during combustion

1. Foreign matter between control valve and burner 2. Gas leak. See Warning statement at top of page
1. Take apart gas tubing and remove foreign matter 2. Locate and correct all leaks (see Checking Gas Connections , pages 19 and 20)
1. Flame impingement on logs
1. Adjust the log set so that the flame does not excessively impinge on it 2. Inspect the opening at the base of the burner to see that it is NOT packed with any type of material
2. Debris around burner air mixer

Dark residue on logs or inside of fireplace

1. Improper log placement
1. Properly locate logs (see log placement sections on page 22) 2. Clean out air holes at burner inlets. Periodically repeat as needed 3. Remove blockage 4. Have the vent system inspected, including the termination cap. Remove any restrictions or obstruction 5. Clear excess embers until a minimum gap of 1/2" remains under the grate
2. Air holes at burner inlet blocked
3. Burner flame holes blocked 4. Improper venting or excessive blockage
5. Excessive amounts of embers and pan material

111922-01A For more information, visit www.desatech.com For more information, visit www.desatech.com

Glass soots

Page 29 of the Desa (V)K42EN user manual — SPECIFICATIONS
Page 29 · click to enlarge
Page 29
Desa (V)K42EN — OPTIONAL REMOTE CONTROL INSTALLATION (Model WRC) diagram (page 29)
Fig. 79 · OPTIONAL REMOTE CONTROL INSTALLATION (Model WRC)

REPLACEMENT PARTS

SERVICE HINTS

  • Note: Use only original replacement parts. This will protect your warranty coverage for parts replaced under warranty. PARTS UNDER WARRANTY Contact authorized retailers of this product. If they can not supply original replacement part(s), call DESA’s Customer Service Department at 1-866-672-6040. When calling DESA, have ready
  • your name
  • your address
  • model and serial numbers of your fireplace
  • how fireplace was malfunctioning
  • type of gas used (propane/LP or natural gas)
  • purchase date Usually, we will ask you to return the part to the factory. PARTS NOT UNDER WARRANTY
  • When Gas Pressure Is Too Low
  • pilot will not stay lit
  • burners will have delayed ignition
  • fireplace will not produce specified heat
  • propane/LP gas supply might be low (propane/LP units only)

You may feel your gas pressure is too low. If so, contact your local gas supplier.

TECHNICAL SERVICE

You may have further questions about installation, operation, or troubleshooting. If so, contact DESA’s Customer Service Depart- ment at 1-866-672-6040. When calling, please have your model and serial numbers of your heater ready.

You can also visit DESA’s technical service web site at www.desatech.com.

  • Contact authorized retailers of this product. If they can not supply original replacement part(s), call DESA at 1-866-672-6040 for referral information. When calling DESA, have ready
  • model number of your fireplace
  • the replacement part number

SPECIFICATIONS

Desa (V)K42EN — SPECIFICATIONS diagram (page 29)
Fig. 80

Fireplace (Actual size of firebox. Measurements do not 40" x 48" x 23 1/2" 40" x 48" x 23 1/2" include nailing flanges or 1016 x 1219 x 599 mm 1016 x 1219 x 599 mm standoffs).

Carton 41" x 51" x 24" 41" x 51" x 24" 1041 x 1295 x 610 mm 1041 x 1295 x 610 mm

Fireplace 197 lbs/89 kg 197 lbs/89 kg Shipping 200 lbs/91 kg 200 lbs/91 kg

111922-01A For more information, visit www.desatech.com For more information, visit www.desatech.com

Page 30 of the Desa (V)K42EN user manual — MODELS (V)K42EN, (V)K42ENH, (V)K42EP, (V)K42EPH
Page 30 · click to enlarge
Page 30
Desa (V)K42EN — OPTIONAL REMOTE CONTROL INSTALLATION (Model WRC) diagram (page 30)
Fig. 81 · OPTIONAL REMOTE CONTROL INSTALLATION (Model WRC)

ILLUSTRATED PARTS BREAKDOWN

MODELS (V)K42EN, (V)K42ENH, (V)K42EP, (V)K42EPH

Desa (V)K42EN — MODELS (V)K42EN, (V)K42ENH, (V)K42EP, (V)K42EPH diagram (page 30)
Fig. 82

111922-01A For more information, visit www.desatech.com For more information, visit www.desatech.com

Page 31 of the Desa (V)K42EN user manual — PARTS AVAILABLE - NOT SHOWN
Page 31 · click to enlarge
Page 31
Desa (V)K42EN — OPTIONAL REMOTE CONTROL INSTALLATION (Model WRC) diagram (page 31)
Fig. 83 · OPTIONAL REMOTE CONTROL INSTALLATION (Model WRC)

31 31 PARTS LIST Models (V)K42EN, (V)K42ENH, (V)K42EP, (V)K42EPH

PARTS LIST

MODELS (V)K42N, (V)K42NH, (V)K42P, (V)K42PH

This list contains replaceable parts used in your fireplace. When ordering parts, follow the instructions listed under Replacement Parts on page 29 of this manual.

KEY PART NO. NUMBER DESCRIPTION QTY.

1 ** Firebox Assembly 1 2 ** Face Weldment 1 3 108328-01 Door Assembly 1 108328-02 Door Assembly (V Models Only) 1 4 108331-01 Top Louver Assembly 1 5 108331-02 BottomLouver Assembly 1 6 ** Fireplace Top 1 7 ** Fireplace Top Insulation 1 8 ** Fireplace Surround 1 9 109082-02 Heat Shield 1 10 111925-01 Log Set 1 10-1 111933-01 Left Base Log 1 10-2 111932-01 Right Base Log 1 10-3 111928-01 Right Front Log 1 10-4 111931-01 Left Front Log 1 10-5 111926-01 Right Rear Log 1 10-6 111929-01 Middle Crossover Log 1 10-7 111934-01 Left Rear Log 1 10-8 111930-01 Left Crossover Log 1 10-9 111927-01 Right Crossover Log 1 11 See Below Left Refractory Brick Panel 1 12 See Below Rear Refractory Brick Panel 1 13 See Below Right Refractory Brick Panel 1 14 108445-01 Screen Rod 1 15 108740-01 Screen 2 16 11418 Push-On Nut 2 17 14123 Strain Relief 1 18 21171 Gas Knock-Out Cover 1 19 24353 Handy Box Assembly 1 20 24460 Gas Conduit Assembly 1 21 111919-03 Burner Assembly (Natural Gas) 1 111919-04 Burner Assembly (Propane/LP Gas) 1 (See Pages 32 and 33)

PARTS AVAILABLE - NOT SHOWN

25487 Lava Rock/Bag Assembly 1

** Part not available for field replacement.

Desa (V)K42EN — PARTS AVAILABLE - NOT SHOWN diagram (page 31)
Fig. 84

REFRACTORY BRICK PANELS K42EN VK42EN K42ENH VK42ENH K42EP VK42EP K42EPH VK42EPH DESCRIPTION QTY 111299-02 111299-01 111302-02 111302-01 Left Refractory Brick Panel 1 111297-02 111297-01 111300-02 111300-01 Rear Refractory Brick Panel 1 111298-02 111298-01 111301-02 111301-01 Right Refractory Brick Panel 1

111922-01A For more information, visit www.desatech.com For more information, visit www.desatech.com

Page 32 of the Desa (V)K42EN user manual — BURNER ASSEMBLY FOR MODELS (V)K42EN, (V)K42ENH, (V)K42EP, (V)K42EPH
Page 32 · click to enlarge
Page 32
Desa (V)K42EN — OPTIONAL REMOTE CONTROL INSTALLATION (Model WRC) diagram (page 32)
Fig. 85 · OPTIONAL REMOTE CONTROL INSTALLATION (Model WRC)

ILLUSTRATED PARTS BREAKDOWN

BURNER ASSEMBLY FOR MODELS (V)K42EN, (V)K42ENH, (V)K42EP, (V)K42EPH

Desa (V)K42EN — BURNER ASSEMBLY FOR MODELS (V)K42EN, (V)K42ENH, (V)K42EP, (V)K42EPH diagram (page 32)
Fig. 86

111922-01A For more information, visit www.desatech.com For more information, visit www.desatech.com

Page 33 of the Desa (V)K42EN user manual — BURNER ASSEMBLY FOR MODELS (V)K42N, (V)K42NH, (V)K42P, (V)K42PH
Page 33 · click to enlarge
Page 33
Desa (V)K42EN — OPTIONAL REMOTE CONTROL INSTALLATION (Model WRC) diagram (page 33)
Fig. 87 · OPTIONAL REMOTE CONTROL INSTALLATION (Model WRC)

33 33 PARTS LIST Models (V)K42EN, (V)K42ENH, (V)K42EP, (V)K42EPH

PARTS LIST

BURNER ASSEMBLY FOR MODELS (V)K42N, (V)K42NH, (V)K42P, (V)K42PH

This list contains replaceable parts used in your fireplace. When ordering parts, follow the instructions listed under Replacement Parts on page 29 of this manual.

KEY PART NO. NUMBER DESCRIPTION QTY.

1 111920-01 Pan Assembly Burner 1 2 111311-02 Grate Base 1 3 111312-02 Burner Base Bottom 1 4 26808 Valve Bracket 1 5 11107 Screw, #10-32 x 1/4 PPH Zinc 4 6 104506-27 Burner Orifice (Natural Gas) 1 104506-26 Burner Orifice (Propane/LP Gas) 1 7 11102 Screw, #8-32 x 3/8 PPH Zinc 2 8 108866-01 Pilot (Natural Gas) 1 108866-02 Pilot (Propane/LP Gas) 1 9 111316-01 Pilot Bracket 1 10 111913-02 Burner Base Gasket 1 11 111310-02 Firebox Bottom 1 12 11165 Screw, #10 x 5/8 HWH Zinc 12 13 26827 Switch Bracket 1 14 14500 Brass Fitting 1 15 111912-01 Tubing Assembly 1 16 14569 Electronic Elec. Valve (Natural Gas) 1 14570 Electronic Elec. Valve (Propane/LP Gas) 1 17 14253 Flex Gas Line 1 18 11186 Screw, #8-32 x 1 Zinc 2 19 110286-01 Ignition Module, Synetek 1 20 11147 Screw, #10-24 x 1/2 PPH MS Blk 2 21 14129 Transformer, 24V Class 2 1 22 17223 Magnet 2 23 11201 Nut, 8-32 Hex Zinc 4 24 23416 Elect. Components Board 1 25 14120 Spade 1/4 Female Connector 4 26 14134 Wire, 18 GA Black 5 27 14126 Wire, 16 GA TFFN/MTW Green 1 28 14115 Spade Tongue Connector 1 29 14149 Spade 1/4 F R/Angle Connector 4 30 108863-01 24" Supply Connect Plug 1

111922-01A For more information, visit www.desatech.com For more information, visit www.desatech.com

Page 34 of the Desa (V)K42EN user manual — DEFLECTION HOODS (Not Shown) HD42 - Hood - Black (2" Brow)
Page 34 · click to enlarge
Page 34
Desa (V)K42EN — OPTIONAL REMOTE CONTROL INSTALLATION (Model WRC) diagram (page 34)
Fig. 88 · OPTIONAL REMOTE CONTROL INSTALLATION (Model WRC)

ACCESSORIES

Purchase these fireplace accessories from your local retailer. If they can not supply these accessories, call DESA’s Sales Department at 1-866-672-6040. for information. You can also write to the address listed on the back page of this manual.

BRICK LINER (Not Shown) BL42DA - Textured Refractory Brick Liner Kit BL42DSA - Standard Refractory Brick Liner Kit BL42DHA - Textured Refractory Herringbone Brick Liner Kit BL42DHSA - Standard Refractory Herringbone Brick Liner Kit

MANUAL BLOWER KIT - BK

Manual variable control blower accessory provides better heat distri- bution. Complete installation and operation instructions included in this manual.

This brick liner adds a touch of style to your direct-vent fireplace. Complete installation and operation instructions included in this manual.

FLEXIBLE GAS LINE CONNECTOR - GA5081 (Not Shown) For all models.

THERMOSTATICALLYCONTROLLED BLOWER KIT - BKT

PROPANE/NATURAL GAS CONVERSION KIT (Not Shown) PCDE-42C - Propane/LP Gas Conversion Kit NCDE-42C - Natural Gas Conversion Kit

Provides better heat distribution. Blower turns off and on automati- cally, as needed. Complete installation and operation instructions included in this manual.

FACE/LOUVER PANEL KIT (Not Shown) RLD42 - Rolled Louver Panels - Black FPD42 - Filligree Panel Kit - Black FPD42B - Filligree Panel Kit - Brushed Brass FPD42P - Filligree Panel Kit - Platinum FPD42PB - Filligree Panel Kit - Polished Brass

REMOTE CONTROL KIT - WRC SERIES (Not Shown)

Standard ON/OFF electronic remote control kit.

WALL MOUNTED THERMOSTAT CONTROL KIT - GWMT1 (Not Shown)

LOUVER TRIM KIT (Rolled Louvers Only) (Not Shown) LT42B - Rolled Louver Trim Kit - Brushed Brass LT42P - Rolled Louver Trim Kit - Platinum LT42PB - Rolled Louver Trim Kit - Polished Brass

Allows easy wall access for thermostatic operation of your fireplace.

WALL MOUNTED ON/OFF SWITCH - GWMS2 (Not Shown)

Allows burner system to be turned on and off with a wall switch.

DEFLECTION HOODS (Not Shown) HD42 - Hood - Black (2" Brow)

PERIMETER TRIM KIT (Not Shown) PT42 - Perimeter Trim Kit - Black PT42B - Perimeter Trim Kit - Brushed Brass PT42P - Perimeter Trim Kit - Platinum PT42PB - Perimeter Trim Kit - Polished Brass

111922-01A For more information, visit www.desatech.com For more information, visit www.desatech.com

Page 35 of the Desa (V)K42EN user manual — OWNER'S REGISTRATION FORM
Page 35 · click to enlarge
Page 35

OWNER'S REGISTRATION FORM

In order to provide better customer service for this and future purchases, we recommend that you register your product with us. You can register online at www.desatech.com. If access to our website is not available to you, please complete this Owner’s Registration Form and mail to the address on the back of this owner’s manual. Please provide the following product information:

Brand(Comfort Glow, Vanguard, etc.)
Model(EFP33PR, VTGH33NR, etc.)

Date Purchased: Note: Keep receipt for warranty verification.

Serial Number: 7 or 9 digit number located on product or identification tag.

First NameLast Name:

Address:

CityState: Zip: Country:
Home Phone( ) -

E-Mail:

Please answer the following questions to register your product with DESA:

1. Where will the product be used?

❍ Living/Family Room ❍ Office/Warehouse ❍ Utility Shed/Outbuilding ❍ Garage ❍ Bedroom ❍ Bathroom ❍ Other

2. If you bought this product yourself, did you plan to purchase this type of product before going into the store? ❍ Yes ❍ No
3. Who selected the product? ❍ Male ❍ Female ❍ Both
4. What is the population of your area? ❍ Under 10,000 ❍ 10,000 to 25,000 ❍ 25,000 to 50,000 ❍ 50,000 to 100,000

❍ 100,000 to 250,000 ❍ Over 250,000

5. What is your primary source of heat? ❍ Propane (LP Gas) ❍ Fuel Oil ❍ Wood ❍ Natural Gas ❍ Electric ❍ Other
6. How was the product installed? ❍ Professional Installer ❍ Self ❍ Other
7. Cost of product excluding sales tax? $
8. Cost to install product? $
9. Type of store where product was purchased? ❍ Hardware ❍ Propane Dealer ❍ Natural Gas/Utility Co. ❍ Home Center/Builder’s Supply

❍ Fireplace or Hearth Shop ❍ Farm Store ❍ Other

10. What motivated you to buy this product? ❍ Sudden Cold Weather ❍ Replace Older Model ❍ D.I.Y. Home Project

❍ Emergency Back-Up Heat ❍ Heater was on Sale ❍ Energy Savings/High Efficiency ❍ Construction Project ❍ Other

11. How did you learn about this product brand? ❍ Advertising ❍ Relative or Friend ❍ Store Display ❍ Other
12. Level of Education of Purchaser: ❍ Some High School ❍ Completed High School ❍ Completed College ❍ Completed Graduate School
13. Age of Purchaser: ❍ Under 20 ❍ 20 - 29 ❍ 30 - 39 ❍ 40 - 49 ❍ 50 - 59 ❍ 60 or Over
14. Buyer’s total annual household income: ❍ Under $15,000 ❍ $15,000 to $19,999 ❍ $20,000 to $34,999 ❍ $35,000 to $49,999

❍ $50,000 to $74,999 ❍ $75,000 to $99,999 ❍ $100,000 and Over

15. Store where product was purchased:
Name______________________________________
City_______________________ State: __________
16. In choosing this product, how important were the following:

Availability Price Brand Name Overall Quality Heat Output Made in USA Warranty Local Service Value for Price Prior Brand Experience Controls Location Thermostat, Remote, or Manual Operation Ease of Operation Special Features Salesperson’s Recommendation Friend/Relative’s Recommendation Portability Quiet Operation

Not Important Somewhat Important Very Important

❍

❍

❍

111922-01A For more information, visit www.desatech.com For more information, visit www.desatech.com

Page 36 of the Desa (V)K42EN user manual — OPTIONAL REMOTE CONTROL INSTALLATION (Model WRC)
Page 36 · click to enlarge
Page 36
Desa (V)K42EN — OPTIONAL REMOTE CONTROL INSTALLATION (Model WRC) diagram (page 36)
Fig. 89 · OPTIONAL REMOTE CONTROL INSTALLATION (Model WRC)

2701 Industrial Drive P.O. Box 90004 Bowling Green, KY 42102-9004

Desa (V)K42EN — OPTIONAL REMOTE CONTROL INSTALLATION (Model WRC) diagram (page 36)
Fig. 90 · OPTIONAL REMOTE CONTROL INSTALLATION (Model WRC)

111922-01A For more information, visit www.desatech.com For more information, visit www.desatech.com

Postage Required

Page 37 of the Desa (V)K42EN user manual — NOTES
Page 37 · click to enlarge
Page 37
Desa (V)K42EN — OPTIONAL REMOTE CONTROL INSTALLATION (Model WRC) diagram (page 37)
Fig. 91 · OPTIONAL REMOTE CONTROL INSTALLATION (Model WRC)

NOTES

111922-01A For more information, visit www.desatech.com For more information, visit www.desatech.com

Show 34 more labels / short text on this page
_______________________________________________________________________________________________ · _______________________________________________________________________________________________ · _______________________________________________________________________________________________ · _______________________________________________________________________________________________ · _______________________________________________________________________________________________ · _______________________________________________________________________________________________ · _______________________________________________________________________________________________ · _______________________________________________________________________________________________ · _______________________________________________________________________________________________ · _______________________________________________________________________________________________ · _______________________________________________________________________________________________ · _______________________________________________________________________________________________ · _______________________________________________________________________________________________ · _______________________________________________________________________________________________ · _______________________________________________________________________________________________ · _______________________________________________________________________________________________ · _______________________________________________________________________________________________ · _______________________________________________________________________________________________ · _______________________________________________________________________________________________ · _______________________________________________________________________________________________ · _______________________________________________________________________________________________ · _______________________________________________________________________________________________ · _______________________________________________________________________________________________ · _______________________________________________________________________________________________ · _______________________________________________________________________________________________ · _______________________________________________________________________________________________ · _______________________________________________________________________________________________ · _______________________________________________________________________________________________ · _______________________________________________________________________________________________ · _______________________________________________________________________________________________ · _______________________________________________________________________________________________ · _______________________________________________________________________________________________ · _______________________________________________________________________________________________ · _______________________________________________________________________________________________
Page 38 of the Desa (V)K42EN user manual — NOT A UPC
Page 38 · click to enlarge
Page 38
Desa (V)K42EN — OPTIONAL REMOTE CONTROL INSTALLATION (Model WRC) diagram (page 38)
Fig. 92 · OPTIONAL REMOTE CONTROL INSTALLATION (Model WRC)

KEEP THIS WARRANTY

Desa (V)K42EN — KEEP THIS WARRANTY diagram (page 38)
Fig. 93

Always specify model and serial numbers when communicating with the factory.

We reserve the right to amend these specifications at any time without notice. The only warranty applicable is our standard written warranty. We make no other warranty, expressed or implied.

LIMITED WARRANTY DIRECT-VENT FIREPLACE

DESA warrants this product to be free from defects in materials and components for two (2) years from the date of first purchase, provided that the product has been properly installed, operated and maintained in accordance with all applicable instructions. To make a claim under this warranty the Bill of Sale or cancelled check must be presented.

This warranty is extended only to the original retail purchaser. This warranty covers the cost of part(s) required to restore this heater to proper operating condition and an allowance for labor when provided by a DESA Authorized Service Center. Warranty part(s) MUST be obtained through authorized retailers of this product and/or DESA who will provide original factory replacement parts. Failure to use original factory replacement parts voids this warranty. The heater MUST be installed by a qualified installer in accordance with all local codes and instructions furnished with the unit.

This warranty does not apply to parts that are not in original condition because of normal wear and tear, or parts that fail or become damaged as a result of misuse, accidents, lack of proper maintenance or defects caused by improper installation. Travel, diagnostic cost, labor, transportation and any and all such other costs related to repairing a defective heater will be the responsibility of the owner.

TO THE FULL EXTENT ALLOWED BY THE LAW OF THE JURISDICTION THAT GOVERNS THE SALE OF THE PRODUCT; THIS EXPRESS WARRANTY EXCLUDES ANY AND ALL OTHER EXPRESSED WARRANTIES AND LIMITS THE DURATION OF ANY AND ALL IMPLIED WARRANTIES, INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE TO TWO (2) YEARS ON ALL COMPONENTS FROM THE DATE OF FIRST PURCHASE; AND DESA’S LIABILITY IS HEREBY LIMITED TO THE PURCHASE PRICE OF THE PRODUCT AND DESA SHALL NOT BE LIABLE FOR ANY OTHER DAMAGES WHATSOEVER INCLUDING INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES.

Some states do not allow a limitation on how long an implied warranty lasts or an exclusion or limitation of incidental or consequential damages, so the above limitation on implied warranties, or exclusion or limitation on damages may not apply to you.

This warranty gives you specific legal rights, and you may also have other rights that vary from state to state.

For information about this warranty write:

2701 Industrial Drive P.O. Box 90004 Bowling Green, KY 42102-9004 www.desatech.com

111922-01 Rev. A 07/03

NOT A UPC

111922-01A For more information, visit www.desatech.com For more information, visit www.desatech.com

111922 01

Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the Desa (V)K42EN

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.