Dell™ Systems Cabling Instructions for the –48 VDC

Dell Power Supply (48 VDC) — Dell™ Systems Cabling Instructions for the –48 VDC diagram (page 1)
Fig. 1 · Dell™ Systems Cabling Instructions for the –48 VDC

w w w. d e l l . c o m | s u p p o r t . d e l l . c o m

Page 2 of the Dell Power Supply (48 VDC) user manual — Notes, Notices, and Cautions
Page 2 · click to enlarge
Page 2

Notes, Notices, and Cautions

how to avoid the problem.

or death.

Information in this document is subject to change without notice. © 2002 Dell Computer Corporation. All rights reserved.

Reproduction in any manner whatsoever without the written permission of Dell Computer Corporation is strictly forbidden.

Trademarks used in this text: Dell and the DELL logo are trademarks of Dell Computer Corporation.

Other trademarks and trade names may be used in this document to refer to either the entities claiming the marks and names or their products. Dell Computer Corporation disclaims any proprietary interest in trademarks and trade names other than its own.

April 2002 P/N 9R972 Rev. A00

Page 3 of the Dell Power Supply (48 VDC) user manual — Precaution Statements
Page 3 · click to enlarge
Page 3

This document describes the requirements and instructions for connecting the safety ground wire for systems equipped with a –48 VDC power supply.

safety grounds. The system must be safety grounded at the cabinet frame. All electrical wiring must comply with applicable local or national codes and practices.

regulatory information. Read and follow all safety instructions prior to setup, operation, and service of your system.

frame. Do not attempt to connect power to the system until grounding cables are connected.

disconnected.

ensure that the power is removed from the DC circuit. To ensure that the power is off, locate the circuit breaker on the DC source circuit. Switch the circuit breaker to the off position and, if available, install an approved safety locking device to the circuit breaker or switch to prevent against another person from energizing the circuit.

Precaution Statements

This system is intended for restricted access locations (dedicated equipment rooms, equipment closet, or the like) in accordance with Articles 110-5, 110-6, 110-11, 110-14, and 110-17 of the National Electrical Code, American National Standards Institute (ANSI)/National Fire Protection Association (NFPA) 70.

Protect the system with a 7.2-ampere (A) minimum to 20-A maximum protective device or a 25-A maximum protective device when used with 90ºC wire.

Connect the system to a –48 VDC supply source that is electrically isolated from the AC source. Ensure that the –48 VDC source is efficiently secured to earth (ground).

first and disconnected last to prevent an energy hazard.

absence of a suitably installed ground conductor. Contact the appropriate electrical inspection authority or an electrician if you are uncertain whether suitable grounding is available.

Page 4 of the Dell Power Supply (48 VDC) user manual — Connecting the –48 VDC Power Cable and Safety Ground
Page 4 · click to enlarge
Page 4

w w w. d e l l . c o m | s u p p o r t . d e l l . c o m

  • Supply voltage: –(38–60) VDC
  • Current consumption: 7.5 A

Connecting the –48 VDC Power Cable and Safety Ground

1 Remove the #6-32 nut equipped with a lock washer from the grounding post on the back of the system.

2 Connect the safety ground (green/yellow wire) to the grounding post on the back of the system using the #6-32 nut equipped with a lock washer that you removed in step 1 (see Figure 1-1).

must connect both safety ground wires to the grounding post on the back of the system.

F igu r e 1- 1. Sa fe t y Gr o un d

safety ground wire grounding post

Dell Power Supply (48 VDC) — Connecting the –48 VDC Power Cable and Safety Ground diagram (page 4)
Fig. 2 · Connecting the –48 VDC Power Cable and Safety Ground

#6-32 nut with lock washer

Input Requirements

Page 5 of the Dell Power Supply (48 VDC) user manual — Input Requirements
Page 5 · click to enlarge
Page 5

3 Plug the DC power cable into the system.

Figure 1-2 and Table 1-1 indicate the DC input power cable connector’s pin orientation and descriptions.

See your Rack Installation Guide for information on routing cables.

Fi gu r e 1- 2. D C I n pu t Po w e r C a ble C o n ne c t o r ’s P i n O r i e n ta t i o n

Ta ble 1 - 1 . C o nn e c t o r Housing Pin Assignments

Pin Description Wire Color and Size

1 –48 VDC Black 14 AWG

2 –48 VDC return Red 14 AWG

Page 6 of the Dell Power Supply (48 VDC) user manual — Input Requirements
Page 6 · click to enlarge
Page 6

w w w. d e l l . c o m | s u p p o r t . d e l l . c o m

Ask about the Dell Power Supply (48 VDC)

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Dell Power Supply (48 VDC)

Be the first to ask — other owners or our team will answer.

Original document

Dell Power Supply (48 VDC) manual PDF

6 pages·808 KB·Computer Monitor·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…