Trademarks used in this text: Dell, the DELL logo, PowerEdge, and PowerApp are trademarks of Dell Computer Corporation. Other trademarks and trade names may be used in this document to refer to either the entities claiming the marks and names or their products. Dell Computer Corporation disclaims any proprietary interest in trademarks and trade names other than its own.
January 2001 P/N 2D786 Rev. A00


Use the following safety guidelines to ensure your own personal safety and to help protect your server, storage system, or appliance from potential damage. For com- plete safety, regulatory, and warranty information, refer to your system’s System Information document.
Throughout this guide, blocks of text may be accompanied by an icon and printed in bold type or in italic type. These blocks are notes, notices, cautions, and warnings, and they are used as follows:
Observe the following precautions for rack stability and safety. Also refer to the rack installation documentation accompanying the system and the rack for specific warn- ing and/or caution statements and procedures.
Servers, storage systems, and appliances are considered to be components in a rack. Thus, “component” refers to any server, storage system, or appliance, as well as to various peripherals or supporting hardware.

After installing system/components in a rack, never pull more than one component out of the rack on its slide assemblies at one time. The weight of more than one extended component could cause the rack to tip over and injure someone.
NOTE: Dell’s servers, storage systems, and appliances are certified as components for use in Dell’s rack cabinet using the Dell customer rack kit. The final installation of Dell systems and rack kits in any other brand of rack cabinet has not been approved by any safety agencies. It is the customer’s responsibility to have the final combination of Dell systems and rack kits for use in other brands of rack cabinets evaluated for suit- ability by a certified safety agency.


Dell™ PowerApp™ 100 and 110 Appliances and PowerEdge™ 350 Systems — Rack Installation Guide
This installation guide provides instructions for trained service technicians installing one or more Dell PowerApp 100 or 110 or PowerEdge 350 systems in a rack. This guide includes procedures for the following three rack kits:
One rack kit is required for each system to be installed in the rack.
This procedure provides instructions for installing a Dell system in a two-post open- frame relay rack, such as those found in telecommunications equipment facilities. Both 3-inch and 6-inch wide two-post racks are accommodated.
The two-post open-frame relay rack must be properly secured to the floor, to the ceiling or upper wall, and where applicable, to adjacent racks, using floor and wall fasteners and bracing specified or approved by the rack manufacturer or by industry standards. See the two-post open-frame relay rack manufacturer’s installation docu- mentation for precautionary warnings and information before attempting this installation.
See “Safety Instructions” at the front of this document for additional safety informa- tion regarding rack installation.

The rack kit includes the following items (see Figure 1-1):

12-24 x 0.5-inch pan-head Phillips screws (2)
10-24 x 0.375-inch pan- head Phillips screws (4)
Recommended Tools and Supplies
You need the following tools and supplies to install the system in a two-post open- frame relay rack:

Each 1-U (1.75-inch) vertical space has three holes, with center-to-center spacing between holes (beginning at the center of the top hole of a 1-U space) of 0.625, 0.625, and 0.5 inch (see Figure 1-2).


Repeat this step to install the remaining bracket on the other side of the system.

10-24 x 0.375-inch pan-head Phillips screws (2 per bracket)
12-24 x 0.5-inch pan-head Phillips screws
Installing the System in the Rack
This completes the two-post center-mount rack installation.

This procedure provides instructions for installing a Dell system in a two-post open- frame relay rack, such as those found in telecommunications equipment facilities. Both 3-inch and 6-inch wide 2-post racks are accommodated.
The two-post open-frame relay rack must be properly secured to the floor, to the ceiling or upper wall, and where applicable, to adjacent racks, using floor and wall fasteners and bracing specified or approved by the rack manufacturer or by industry standards. Refer to the two-post open-frame relay rack manufacturer’s installation documentation for precautionary warnings and information before attempting this installation.
See “Safety Instructions” found earlier in this guide for additional safety information regarding rack installation.
The two-post flush-mount rack kit includes the following items (see Figure 1-4):


10-24 x 0.25 inch flat- head Phillips screws (4)
12-24 x 0.5-inch pan- head Phillips screws (4)
Recommended Tools and Supplies
You need the following tools and supplies to install the system in a two-post open- frame relay rack:

Each 1-U (1.75-inch) vertical space has three holes, with center-to-center spacing between holes (beginning at the center of the top hole of a 1-U space) of 0.625, 0.625, and 0.5 inch (see Figure 1-5).

1.75 inches (1 U)

Repeat this step to install the remaining bracket on the other side of the rack.


Ensure that the flat end of the inside rail is toward the front of the chassis and that the end with two threaded holes is located at the back of the chassis. The flat central part of the inside rail must be facing the chassis, with the raised upper and lower rail surface facing outward (see Figure 1-7).


An internally threaded stud projecting from the front of the tray flanges accepts the captive fastener on the front of the system.

captive fasteners


This completes the two-post flush-mount rack installation.
This procedure provides instructions for installing a Dell system in a four-post rack cab- inet. Both 24-U and 42-U racks are accommodated.
The rack kit includes the following items (see Figure 1-10):
server tab · thumbscrew


slide assemblies with mounting brackets (1 pair)
10-32 x 0.5-inch pan-head Phillips screws (4)
10-24 x 0.375-inch pan-head Phillips screws (6)

Before you begin installing your system in the rack, carefully read “Safety Instruc- tions,” found earlier in this guide.
NOTICE: This rack kit is intended to be installed in a Dell rack by trained service technicians. If you install the kit in any other rack, be sure that the rack meets the specifications of American National Standards Institute (ANSI)/Electronic Industries Association (EIA) standard ANSI/EIA-310-D-92, International Electrotechnical Commission (IEC) 297, and Deutsche Indus- trie Norm (DIN) 41494. One rack kit is required for each Dell server, storage system, or appliance that is installed in a rack.
You need the following tools and supplies to install the system in a four-post rack cabinet:
For instructions on installing the system itself, see “Installing the System in the Four- Post Rack” found later in this guide.
To install the slide assemblies in the rack, perform the following steps:
The subsections that follow include instructions for performing these tasks.

Removing the Doors From the 42-U Rack
This procedure provides instructions for removing doors from earlier 42-U Dell racks. If you have a newer Dell PowerEdge 4210 rack, refer to the procedures contained in the Dell PowerEdge 4210 Rack Installation Guide.
Slide the button cover up as far as it will go, press the push button, rotate the handle clockwise until the latch releases, and then pull the door open.

push-button cover · push button · handle

a. One person should grasp the top of the door to stabilize it. The other person should grasp the bottom of the door.
b. The person holding the bottom of the door should press the hinge release lever on the bottom hinge and then pull the door away from the rack.
c. The person holding the top of the door should press the hinge release lever on the top hinge and then pull the door away from the rack.

hinge release lever

Removing the Doors From the 24-U Rack


a. With the door open, lift out and fully retract all hinge pins.
b. Once all the hinge pins have been lifted out and retracted, lift the door out.

If you want to reverse the door so that the handle is on the other side, perform the following steps:
Installing the Slide Assemblies in the Four-Post Rack

You must allow 1 U (1.75 inches) of vertical space for each system you install in the rack.

For more information about requirements for installing components in a rack, see the Dell Rack Advisor software available on the Dell World Wide Web site at http://support.dell.com

To install the slide assemblies in the rack, perform the following steps:

1 U (1.75 inches) between slide assemblies (drawing is not to scale)
1-U template

The hooks on the bottom of the mounting bracket should enter the holes beside the lower marks you made in the vertical rails.

10-32 x 0.5-inch pan-head Phillips screw (2 per slide assembly)
mounting-bracket flange · slide assemblies (2)

Installing the Inner Rails on the System Chassis
To install the inner rails to the sides of the system, perform the following steps.

10-24 x 0.375-inch pan- head Phillips screws (6)
Grasp the system with one hand on the right side of the system and the other hand on the left side of the system.
inner rail (2)


Installing the Cable-Management Arm
To install the cable-management arm on the back of the system, perform the follow- ing steps:
The bracket snaps into the square mounting holes on the vertical rail and is secured with a captive thumbscrew.


For details, see your system’s Installation and Troubleshooting Guide and User’s Guide.
a. After connecting the cables to the system, unscrew the thumbscrews that secure the front of the server to the front vertical rail.
b. Slide the system forward to the fully extended position.
c. Route the cables along the cable-management arm, allowing some additional cable slack at the hinge positions, and secure the cables to the cable- management arm with the Velcro straps attached to the cable-management arm.
pin

The following subsections describe procedures for replacing the rack doors on earlier Dell 42-U and 24-U racks. If you have a Dell PowerEdge 4210 rack, see the procedures contained in the Dell PowerEdge 4210 Rack Installation Guide.
Replacing the Rack Doors on a 42-U Rack
Replacing the Rack Doors on a 24-U Rack
This completes the four-post rack kit installation.

installing in four-post rack
cable-management arm, 1-23 slide assemblies, 1-20
rack-mount precautions, 1-4, 1-5, 1-13
routing cables, 1-23
four-post rack, 1-17
two-post rack kit, 1-8
four-post rack, 1-21 two-post center-mount rack, 1-4 two-post flush-mount rack, 1-9
installing in four-post rack, 1-22 installing in two-post center-mount
rack, 1-4 installing in two-post flush-mount rack,
1-9 weight, 1-21
four-post rack, 1-11 two-post center-mount rack, 1-2 two-post flush-mount rack, 1-5
M
four-post rack, 1-12 two-post flush-mount, 1-6
four-post rack, 1-19 two-post center-mount rack, 1-3 two-post flush-mount rack, 1-7
four-post kit, 1-13 two-post center-mount kit, 1-2 two-post flush-mount kit, 1-6
marking the vertical rails
four-post rack, 1-19
two-post center-mount kit installation,
two-post flush-mount installation, 1-5
W
PowerEdge 4210 rack, 1-14, 1-24