Coleman Air Handler (F*FP)

16 pages·225 KB·Air Conditioner·PDF·ENDEFRITNLJA
Coleman Air Handler (F*FP)
Table of Contents 80 sections INSTALLATION MANUAL · SINGLE PIECE AIR HANDLERS · MODELS: F*FP · TABLE OF CONTENTS · … ShowHide
INSTALLATION MANUALp.1SINGLE PIECE AIR HANDLERSp.1MODELS: F*FPp.1TABLE OF CONTENTSp.1LIST OF FIGURESp.1LIST OF TABLESp.1SAFETYp.1SPECIFIC SAFETY RULES AND PRECAUTIONSp.2INSPECTIONp.2LIMITATIONSp.2SAFETY REQUIREMENTSp.2CLEARANCESp.2LOCATIONp.2GENERAL INFORMATIONp.2MINIMUM CLEARANCEp.3OF 1” ALL SIDESp.3FLEXIBLE DUCT COLLARp.3POWER WIRING TO MAIN POWER SOURCEp.3SUPPLY AIR POWER WIRINGp.3CONTROL WIRINGp.3REFRIGERANT LINESp.3THERMOSTATp.3TO CONDENSATE DRAINp.3FILTER ACCESSp.3LOUVEREDp.3HORIZONTAL DRAIN PAN CONVERSIONp.3DUCT CONNECTIONSp.5COIL METERING DEVICESp.5TXV Metering Devicep.5AIR FILTERSp.5SUSPENSION KITSp.5TAIL END UPp.6FAN RELAY FAN CONNECTIONSp.6TRANSFORMER CONNECTIONS (HIGH VOLTAGE)p.6F A Np.6K2 T9Ap.6L 2 L 1p.64-PIN POWER CONNECTORp.6ROTATE BULB TO KEEP TAIL AT BOTTOMp.6K1 T9Ap.61 STAGE HEAT RELAYp.6FANp.6& HEAT COMp.6LIMp.6& LIM PWRp.6VERTICAL RISERp.6BREAK TAB FOR VARIABLE SPEED MOTORp.6TESTp.624 VOLT Rp.6HEAT 2p.6DRVp.6DRV HEAT 3p.6HEAT 4p.62 4 V A Cp.62 SPEED LTRIP ECMp.65 AMP CONTROL VOLTAGE FUSEp.65 A M Pp.624 VOLT COMMONp.6M A Xp.6R Y G W2 W1 O Cp.6REFRIGERANT LINE CONNECTIONp.6JUMPER BARp.6JUMPER BAR COVERp.6AIR FLOWp.6ELECTRIC HEATERS & OPERATING CONTROLSp.6LOW VOLTAGE CONTROL CONNECTIONp.8LINE POWER CONNECTIONSp.8TYPICAL WIRING WITHOUT ELECTRIC HEATp.8GND. LUGp.8ELECTRIC HEAT WITHOUT CIRCUIT BREAKERp.83 PHASE (10 - 15 KW)p.8POWER SUPPLYp.8POWER SUPPLY 1p.8POWER SUPPLY 2p.8POWER SUPPLY 3p.8POWER WIRING (208/230-1-60)p.8NOTE: USE ONLY COPPER CONDUCTORSp.8BLOWER SPEED CONNECTIONSp.84-5 TON HIGH EFFICIENCY MOTOR (X-13)p.81-1/2 TON TO 4 TON STANDARD MOTORp.8
Page 1 of the Coleman Air Handler (F*FP) user manual — Table of Contents
Page 1 · Contents
Contents

Contents

INSTALLATION MANUALp.1SINGLE PIECE AIR HANDLERSp.1MODELS: F*FPp.1TABLE OF CONTENTSp.1LIST OF FIGURESp.1LIST OF TABLESp.1SAFETYp.1SPECIFIC SAFETY RULES AND PRECAUTIONSp.2INSPECTIONp.2LIMITATIONSp.2SAFETY REQUIREMENTSp.2CLEARANCESp.2LOCATIONp.2GENERAL INFORMATIONp.2MINIMUM CLEARANCEp.3OF 1” ALL SIDESp.3FLEXIBLE DUCT COLLARp.3POWER WIRING TO MAIN POWER SOURCEp.3SUPPLY AIR POWER WIRINGp.3CONTROL WIRINGp.3REFRIGERANT LINESp.3THERMOSTATp.3TO CONDENSATE DRAINp.3FILTER ACCESSp.3LOUVEREDp.3HORIZONTAL DRAIN PAN CONVERSIONp.3DUCT CONNECTIONSp.5COIL METERING DEVICESp.5TXV Metering Devicep.5AIR FILTERSp.5SUSPENSION KITSp.5TAIL END UPp.6FAN RELAY FAN CONNECTIONSp.6TRANSFORMER CONNECTIONS (HIGH VOLTAGE)p.6F A Np.6K2 T9Ap.6L 2 L 1p.64-PIN POWER CONNECTORp.6ROTATE BULB TO KEEP TAIL AT BOTTOMp.6K1 T9Ap.61 STAGE HEAT RELAYp.6FANp.6& HEAT COMp.6LIMp.6& LIM PWRp.6VERTICAL RISERp.6BREAK TAB FOR VARIABLE SPEED MOTORp.6TESTp.624 VOLT Rp.6HEAT 2p.6DRVp.6DRV HEAT 3p.6HEAT 4p.62 4 V A Cp.62 SPEED LTRIP ECMp.65 AMP CONTROL VOLTAGE FUSEp.65 A M Pp.624 VOLT COMMONp.6M A Xp.6R Y G W2 W1 O Cp.6REFRIGERANT LINE CONNECTIONp.6JUMPER BARp.6JUMPER BAR COVERp.6AIR FLOWp.6ELECTRIC HEATERS & OPERATING CONTROLSp.6LOW VOLTAGE CONTROL CONNECTIONp.8LINE POWER CONNECTIONSp.8TYPICAL WIRING WITHOUT ELECTRIC HEATp.8GND. LUGp.8ELECTRIC HEAT WITHOUT CIRCUIT BREAKERp.83 PHASE (10 - 15 KW)p.8POWER SUPPLYp.8POWER SUPPLY 1p.8POWER SUPPLY 2p.8POWER SUPPLY 3p.8POWER WIRING (208/230-1-60)p.8NOTE: USE ONLY COPPER CONDUCTORSp.8BLOWER SPEED CONNECTIONSp.84-5 TON HIGH EFFICIENCY MOTOR (X-13)p.81-1/2 TON TO 4 TON STANDARD MOTORp.8
Page 2 of the Coleman Air Handler (F*FP) user manual — GENERAL INFORMATION
Page 2 · click to enlarge
Page 2

SPECIFIC SAFETY RULES AND PRECAUTIONS

Top and side power wiring and control wiring, accessible screw termi- nals for control wiring, easy to install drain connections and electric heaters all combine to make the installation easy, and minimize installa- tion cost.

FIRE OR ELECTRICAL HAZARD Failure to follow the safety warnings exactly could result in serious injury, death or property damage. A fire or electrical hazard may result causing property damage, per- sonal injury or loss of life.

INSPECTION

As soon as a unit is received, it should be inspected for possible dam- age during transit. If damage is evident, the extent of the damage should be noted on the carrier’s freight bill. A separate request for inspection by the carrier’s agent should be made in writing. Also, before installation the unit should be checked for screws or bolts, which may have loosened in transit. There are no shipping or spacer brackets which need to be removed.

1. Install this air handler only in a location and position as specified in SECTION I of these instructions.
2. Always install the air handler to operate within the air handler’s intended maximum outlet air temperature. Only connect the air handler to a duct system which has an external static pressure within the allowable range, as specified on the air handler rating plate.

Also check to be sure all accessories such as heater kits, suspension kits, and coils are available. Installation of these accessories or field conversion of the unit should be accomplished before setting the unit in place or connecting any wiring, electric heat, ducts or piping.

3. When an air handler is installed so that supply ducts carry air circulated by the air handler to areas outside the space containing the air handler, the return air shall also be handled by duct(s) sealed to the air handler casing and terminating outside the space containing the air handler.

LIMITATIONS

These units must be wired and installed in accordance with all national and local safety codes.

Voltage limits are as follows:

4. The air handler is not to be used for temporary heating of buildings or structures under construction.
Air Handler VoltageVoltage code1Normal Operating Voltage Range 208/230-1-6006187-253
5. The size of the unit should be based on an acceptable heat loss calculation for the structure. ACCA, Manual J or other approved methods may be used.
1. Rated in accordance with ARI Standard 110, utilization range “A”.

SAFETY REQUIREMENTS

Airflow must be within the minimum and maximum limits approved for electric heat, evaporator coils and outdoor units.

  • This air handler should be installed in accordance with all national and local building/safety codes and requirements, local plumbing or wastewater codes, and other applicable codes.
  • Refer to the unit rating plate for the air handler model number, and then see the dimensions page of this instruction for supply air plenum dimensions in Figure 1. The plenum must be installed according to the instructions.
  • Provide clearances from combustible materials as listed under Clearances to Combustibles.
  • Provide clearances for servicing ensuring that service access is allowed for both the burners and blower.
  • Failure to carefully read and follow all instructions in this manual can result in air handler malfunction, death, personal injury and/or property damage.
  • Check the rating plate and power supply to be sure that the electrical characteristics match.
  • Air handler shall be installed so the electrical components are protected from water.
  • Installing and servicing heating equipment can be hazardous due to the electrical components. Only trained and qualified personnel should install, repair, or service heating equipment. Untrained service personnel can perform basic maintenance functions such as cleaning and replacing the air filters. When working on heating equipment, observe precautions in the manuals and on the labels attached to the unit and other safety precautions that may apply.
  • These instructions cover minimum requirements and conform to existing national standards and safety codes. In some instances these instructions exceed certain local codes and ordinances, especially those who have not kept up with changing residential and non-HUD modular home construction practices. These instructions are required as a minimum for a safe installation.
Entering Air Temperature Limits Wet Bulb Temp.°FDry Bulb Temp. °F Min.Max.Min.Max. 57726595

CLEARANCES

Clearance must be provided for:

1. Refrigerant piping and connections - minimum 12” recommended.
2. Maintenance and servicing access - minimum 36” from front of unit recommended for blower motor / coil replacement.
3. Condensate drain line.
4. Filter removal - minimum 36” recommended.

LOCATION

Location is usually predetermined. Check with owner’s or dealer’s installation plans. If location has not been decided, consider the follow- ing in choosing a suitable location:

1. Select a location with adequate structural support, space for service access, clearance for air return and supply duct connections.
2. Use hanging brackets to wall mount unit as shown under suspension kits section.
3. Normal operating sound levels may be objectionable if the air handler is placed directly over some rooms such as bedrooms, study, etc.
4. Precautions should be taken to locate the unit and ductwork so that supply air does not short circuit to the return air.
5. Select a location that will permit installation of condensate line to an open drain.

GENERAL INFORMATION

This Single Piece Air Handler provides the flexibility for installation in any upflow or horizontal application. These versatile models may be used for cooling or heat pump operation with or without electric heat. BRAND LABEL (available from Distribution) apply to center of the blower access panel.

NOTE: When the coil is installed in a draw-thru application, it is recom- mended to trap the primary and secondary drain line. If the secondary drain line is not used, it must be capped. The coil is provided with a secondary drain. It should be piped to a loca- tion that will give the occupant a visual warning that the primary drain is clogged. If the secondary drain is not used it must be capped.

The unit can be positioned for bottom return air in the upflow position, and right or left return in the horizontal position.

Page 3 of the Coleman Air Handler (F*FP) user manual — HORIZONTAL DRAIN PAN CONVERSION
Page 3 · click to enlarge
Page 3
6. When an evaporator coil is installed in an attic or above a finished ceiling, an auxiliary drain pan should be provided under the coil as is specified by most local building codes.

If electric heat is used, a minimum clearance of 1” must be main- tained on all sides of the supply air duct and/or plenum continuously for up to 3’ (See Figure 1).

7. Proper electrical supply must be available.
8. Clearances must also be taken into consideration, and provided for as follows:

A. Refrigerant piping and connections are located in the front.

MINIMUM CLEARANCE

B. Maintenance and servicing through the front or access side of unit with both sides and rear of unit having zero inch clear- ance.

OF 1” ALL SIDES

C. Condensate drain lines are connected in the front (clear of fil- ter).

D. Filter removal.

E. When no electric heat is used, the unit as well as all duct work and plenum are designed for zero clearance to combus- tible materials.

FLEXIBLE DUCT COLLAR

FIGURE 1Plenum Clearances

POWER WIRING TO MAIN POWER SOURCE

SUPPLY AIR POWER WIRING

CONTROL WIRING

REFRIGERANT LINES

THERMOSTAT

TO CONDENSATE DRAIN

FILTER ACCESS

LOUVERED

ELECTRIC HOT WATER HEATER (Must comply with water heater installation instructions)

FIGURE 2Typical Installation

HORIZONTAL DRAIN PAN CONVERSION

These air handler units are supplied ready to be installed in a right hand horizontal position. If unit requires left hand positioning, the unit must have the pan installed in the correct position.

DO NOT TRY TO KNOCK OUT PANEL OPENING FOR SECOND- ARY DRAIN PAN. SEE ITEM 7.

1. Remove blower access, coil access, and center access panels.

Models F*FP045,048,060 have a coil baffle and support bracket factory installed for right hand horizontal application (refer to Figure 3C). For left hand applications the coil support bracket must be moved to the right side of the coil, and the coil baffle must be rotated to avoid water blow-off. To rotate baffle, remove the coil assembly from the unit (remove front two screws holding the coil support bracket and the two screws holding the drain pan). Remove four screws in coil baffle and remove the coil baffle and rotate ends. Resecure the baffle and reinstall the coil assembly ensuring that the rear of the drain pan is secured under the back flange of the unit. Reinstall the coil support bracket on the right side of the coil.

3. Position horizontal pan, as required in either “A” or “B” position, locking it into the vertical drain pan as shown.
4. Horizontal drain pans have 4 plugged drains. Remove plugs from connections being used.
6. Attach horizontal pan with 2 screws removed in step no. 2 or supplied with the unit. Ensure that the drain pan is lying flat against the insulation of the cabinet.
7. Horizontal drain cutout in the center access panel should be removed by using a utility knife (if not previously cut out).
8. Re-position and replace access panels.

3’

Page 4 of the Coleman Air Handler (F*FP) user manual — MINIMUM CLEARANCE
Page 4 · click to enlarge
Page 4
Coleman Air Handler (F*FP) — MINIMUM CLEARANCE diagram (page 4)
Fig. 1

DUCT WORK MAY BE FASTENED CAUTIOUSLY WITH SCREWS TO THE SIDES AND REAR OF UNIT

"S" BRACKET MUST BE USED TO FASTEN DUCT WORK TO FRONT OF UNIT

FIGURE 3Filter Access & Drain Pan Conversion / Coil Baffle
Coleman Air Handler (F*FP) — MINIMUM CLEARANCE diagram (page 4)
Fig. 2

ALL DIMENSIONS ARE IN INCHES. THEY ARE SUBJECT TO CHANGE WITHOUT NOTICE. CERTIFIED DIMENSIONS WILL BE PROVIDED UPON REQUEST.

(21 INCHES) MAX. FILTER WIDTH (B MINUS 1-1/2 INCHES)

FILTER ACCESS DRAIN CONNECTIONS FOR UPFLOW APPLICATIONS BOTTOM VIEW

FIGURE 4Dimensions & Duct Sizes
TABLE 1Dimensions
MODELS F*FPDimensionsWiring K.O.’s*Refrigerant Connections Line Size ABCDEFJ PowerK HeightWidthDepthControlLiquidVapor 02440-3/418 18 21-1/2 21-1/2 21-1/2 24 24 242212-1/8 17-3/814-7/816-1/27/8 (1/2) 1-3/8 (1)7/8 (1/2)3/85/8 03040-3/414-7/816-1/23/4 03640-3/418-3/8203/4 04040-3/418-3/8207/8 04240-3/418-3/8207/8 04550-3/420-7/822-1/27/8 (1/2) 1-3/8 (1), 1-23/32 (1-1/4)7/8 04850-3/420-7/822-1/27/8 06050-3/420-7/822-1/27/8
Coleman Air Handler (F*FP) — MINIMUM CLEARANCE diagram (page 4)
Fig. 3
Page 5 of the Coleman Air Handler (F*FP) user manual — SUSPENSION KITS
Page 5 · click to enlarge
Page 5

DUCT CONNECTIONS

A suspension kit is available. Models 1BH0601 (unit sizes 018-060) is designed specifically for the units contained in this instruction (upflow application only). For installation of these accessory kits, see the instructions packed with the kit.

Coleman Air Handler (F*FP) — DUCT CONNECTIONS diagram (page 5)
Fig. 4

Use 1/2" screws to connect ductwork to bottom of unit. Longer screws will pierce the drain pan and cause leakage. If pilot holes are drilled, drill only though field duct and unit bottom flange.

For suspension of these units in horizontal applications, it is recom- mended to use angle steel support brackets with threaded rods, sup- porting the units from the bottom, at the locations shown in Figure 5.

COIL METERING DEVICES

The coil in this Air Handler unit will have a TXV metering device installed at the factory.

The model number will have the following format: F*FPxxxH06T2y - The coil will have a Thermal Expansion Valve (TXV) installed. The y character specifies which TXV is installed at the factory. Please refer to the TXV Metering Device section for installation notes.

The vast majority of problems encountered with combination heating and cooling systems can be linked to improperly designed or installed duct systems. It is therefore highly important to the success of an instal- lation that the duct system be properly designed and installed.

TABLE 2Installed TXV Sizes
Indoor Coil ModelMetering Device F4FP024H06T2ATXV 2A F4FP024H06T2BTXV 2B F4FP030H06T2ATXV 2A F4FP036H06T2ATXV 2A F4FP040H06T2ATXV 2A F4FP040H06T2CTXV 2C F4FP042H06T2ATXV 2A F4FP042H06T2CTXV 2C F4FP045H06T2CTXV 2C F5FP048H06T2CTXV 2C F5FP060H06T2CTXV 2C
Coleman Air Handler (F*FP) — COIL METERING DEVICES diagram (page 5)
Fig. 5

Use flexible duct collars to minimize the transmission of vibration/noise into the conditioned space. If electric heat is used, non-flammable material must be used.

Where return air duct is short, or where sound may be a problem, sound absorbing glass fiber should be used inside the duct. Insulation of duct work is a must where it runs through an unheated space during the heating season or through an uncooled space during the cooling season. The use of a vapor barrier is recommended to prevent absorp- tion of moisture from the surrounding air into the insulation.

The supply air duct should be properly sized by use of a transition to match unit opening. All ducts should be suspended using flexible hang- ers and never fastened directly to the structure. This unit is not designed for non-ducted (freeblow) applications. Size outlet plenum or transition to discharge opening sizes shown in Figure 4.

TXV Metering Device

Duct work should be fabricated and installed in accordance with local and/or national codes. This includes the standards of the National Fire Protection Association for Installation of Air-Conditioning and Ventilat- ing Systems, NFPA No. 90B.

Coleman Air Handler (F*FP) — TXV Metering Device diagram (page 5)
Fig. 6 · TXV Metering Device

AIR FILTERS

Air filters must be field supplied. A 1" filter access rack has been built into the unit. See Figure 4. Remove filter access cover shown. Install proper size filter. Standard 1" size permanent or throw away filter may be used, or, permanent washable filters are available using model num- bers: 1PF0601, 602, 603BK. See Table 3 for filter size.

FIGURE 6TXV Bulb Installation

Equipment should never be operated without filters.

Please refer to Table 2 to verify which TXV is installed in this Air Han- dler unit and that this AHU is a valid system match for the AC or HP unit installed.

SUSPENSION KITS

Coleman Air Handler (F*FP) — SUSPENSION KITS diagram (page 5)
Fig. 7

The TXV is bolted into the coil assembly of this Air Handler unit at the factory. The temperature sensing bulb will need to be attached to the coil suction header line after the line set is brazed to the coil.

  • Make sure the TXV bulb is outside of the Air Handler cabinet. Excess tubing should remain inside the cabinet.
  • Take caution not to apply high temperatures to the TXV assembly or equalizer line while brazing.
  • Attach field line sets and braze to coil connections. Replace access panels & secure.
  • Secure the TXV bulb to the suction line with the clamp provided. Choose a horizontal location as close to the cabinet as possible, but not directly on the brazed connection joint. Refer to Figure 7.
  • The bulb should be in direct contact with the coil suction line along the length of the bulb.
Units (Nominal Tons)Dimension WWXX 018, 024, 030, 036, 040, 04214”40-3/4” 045, 048, 06019-1/2”50-3/4”
FIGURE 5Typical Horizontal Installation
Page 6 of the Coleman Air Handler (F*FP) user manual — ELECTRIC HEATERS & OPERATING CONTROLS
Page 6 · click to enlarge
Page 6
  • If the suction line is 3/4" diameter - position the bulb near the top of the copper tube as shown. If the tube is 7/8" diameter - position the bulb near the bottom of the tube. Refer to Figure 7.
  • Wrap the clamp, bulb & line securely with insulation provided.

only, install the 6-pin jumper plug to the control board to bypass the heater limit controls. This jumper plug is secured to the duct cover near the 4-pin power plug harness. Failure to install the plug will cause the blower to run continuously. (See Figure 8).

TAIL END UP

Coleman Air Handler (F*FP) — TAIL END UP diagram (page 6)
Fig. 8

FAN RELAY FAN CONNECTIONS

TRANSFORMER CONNECTIONS (HIGH VOLTAGE)

Coleman Air Handler (F*FP) — FAN RELAY FAN CONNECTIONS diagram (page 6)
Fig. 9

F A N

*

K2 T9A

L 2 L 1

4-PIN POWER CONNECTOR

ROTATE BULB TO KEEP TAIL AT BOTTOM

1 2 3 4

H

K1 T9A

6-PIN CONNECTOR (LIMIT, 2ND, 3RD & 4TH HEAT RELAY DRIVER)

1 STAGE HEAT RELAY

FAN

& HEAT COM

LIM

& LIM PWR

VERTICAL RISER

BREAK TAB FOR VARIABLE SPEED MOTOR

TEST

24 VOLT R

HEAT 2

DRV

DRV HEAT 3

HEAT 4

2 4 V A C

DRV

2 SPEED LTRIP ECM

FIGURE 7Bulb Location

5 AMP CONTROL VOLTAGE FUSE

5 A M P

24 VOLT COMMON

M A X

R Y G W2 W1 O C

COIL UNDER PRESSURE. Relieve pressure by removing plug from piping connection. Coil will have factory installed TXV. See outdoor unit documentation for cor- rect TXV to be used. Refer to unit nameplate for TXV identification for this unit.

FIGURE 8Control Board

Mark the unit nameplate with the appropriate heater selection on the space provided or NONE to indicate cooling only. To operate these units with electric heat, it is necessary to field install an electric heater kit (2HK). See Electric Heater Kit Accessory Installation instructions for proper installation procedure. Prior to installing electric heat, it is neces- sary to perform the following procedure:

NOTE: The coil should be open to the air for no more than 2 minutes to keep moisture and contaminates from entering the system. If the coil cannot be brazed into the refrigeration system in that time, the ends should be temporarily closed or plugged. For a short term delay, use masking tape over the ends of the copper tubing to close the tube to the air. For a longer term delay, use plugs or caps. There is no need to purge the coil if this procedure is followed.

1. Remove the 4-pin power plug from the control board (See Figure 8).

REFRIGERANT LINE CONNECTION

See the outdoor unit installation instructions for the procedure to install field supplied tubing for systems with sweat fittings.

Right-hand Airflow Application Only - Models with Circuit Breakers - See Figure 9

Stub adapters are available to adapt sweat connections to quick con- nections.

If unit is to be installed for right hand air flow, the circuit breakers in the heat kit will need to be removed and rotated 180°, so the OFF position will be down when the cabinet is positioned on the right side. This is an NEC requirement. Do One Breaker At A Time - to make sure wires are reconnected properly. Loosen terminal screws on the wires and gently pull the wires back from the breaker. Remove screws securing the breaker plate and rotate 180°, then secure the breaker plate and reconnect the wires to the breaker. Proper torque for terminal screws is 35 in/lbs.

Connect lines as follows:

2. Plan for TXV bulb placement.

HEAT KIT ASSEMBLY REMOVE 3 SCREWS TO REMOVE THE CIRCUIT BREAKER BRACKET FROM HEAT KIT ASSEMBLY

3. Remove rubber plugs from refrigerant lines.
4. Braze the suction line. Re-attach the center access panel, if it had been removed.
5. Braze the liquid line.

JUMPER BAR

6. Install supplied grommets on both the suction and liquid lines to complete the air seal.

JUMPER BAR COVER

7. See previous section for TXV bulb.

FIELD SUPPLY WIRING WILL BE ATTACHED TO THIS SIDE OF THE CIRCUIT BREAKER(S)

AIR FLOW

Lines should be sound isolated by using the appropriate hangers or strapping.

When field supplied lines are used be sure to insulate the suction line only.

CIRCUIT BREAKER(S) - THERE MAY BE ONE, TWO OR THREE

CIRCUIT BREAKER BRACKET HEAT KIT WIRING WILL BE ATTACHED TO THIS SIDE OF THE CIRCUIT BREAKER(S)

ELECTRIC HEATERS & OPERATING CONTROLS

FIGURE 9Electric Heaters in Horizontal Configuration - Right Hand

The low voltage transformer and fan / heater control, are standard on all models. See Figure 8. The air handlers are shipped pre-wired to oper- ate as cooling only applications. To complete the installation for cooling

Air Flow

Page 7 of the Coleman Air Handler (F*FP) user manual — TAIL END UP
Page 7 · click to enlarge
Page 7
Page 7 of the Coleman Air Handler (F*FP) user manual — TAIL END UP
Page 8 of the Coleman Air Handler (F*FP) user manual — C G
Page 8 · click to enlarge
Page 8

LOW VOLTAGE CONTROL CONNECTION

The 24 volt power supply is provided by an internally wired low voltage transformer which is standard on all models. However, if the unit is con- nected to a 208 volt power supply the low voltage transformer must be rewired to the 208 volt tap. See the unit wiring label.

LINE POWER CONNECTIONS

Field supplied low voltage wiring can exit the unit on the top right hand corner or the right hand side panel (see Fig. 5, item K).

Power may be brought into the unit through the supply air end of the unit (top when unit is vertical) or the left side panel. Use the hole appro- priate to the unit's orientation in each installation to bring conduit from the disconnect. The power lead conduit should be terminated at the electrical control box. Refer to Tables 4, 8 & 10 for wire requirements. Also see Figure 10.

Install a 7/8" plastic bushing in the selected hole and keep low voltage wiring as short as possible inside the control box.

The field wiring is to be connected at the screw terminals of the control board. Refer to Figure’s 12 and 13.

TYPICAL WIRING WITHOUT ELECTRIC HEAT

GND. LUG

ELECTRIC HEAT WITHOUT CIRCUIT BREAKER

1 PHASE ELECTRIC HEAT WITH CIRCUIT BREAKER AS SHIPPED FROM FACTORY

GND. LUG

3 PHASE (10 - 15 KW)

GND. LUG

GND. LUG

SINGLE SOURCE (2.5 - 25 KW) - 25 KW SHOWN

POWER SUPPLY

GND. LUG

GND. LUG

POWER SUPPLY

1 PHASE ELECTRIC HEAT WITH CIRCUIT BREAKER & BREAKER BAR REMOVED MULTI-SOURCE (15 - 25 KW) - 25 KW SHOWN

GND. LUG

ELECTRIC HEAT WITHOUT CIRCUIT BREAKER SINGLE SOURCE (2.5 - 10 KW)

POWER SUPPLY

GND. LUG

GND. LUG

GND. LUG

POWER SUPPLY 1

POWER SUPPLY 2

POWER SUPPLY

POWER SUPPLY 3

POWER WIRING (208/230-1-60)

NOTE: USE ONLY COPPER CONDUCTORS

FIGURE 10Line Power Connections

BLOWER SPEED CONNECTIONS

Higher efficiencies will be obtained if the indoor air volume is as high as possible provided the CFM does not exceed limitations and the sound level is not objectionable.

Except for F4FP045, which has a 4-speed motor, and F5FP* which has a 5-speed high efficiency X-13 motor, all air handlers contain three speed blower motors which are pre-wired to the control board.

Connect motor wires to motor speed tap receptacle for speed desired. See wiring label for motor wiring details. See Figure 11.

Adjust blower motor speed to provide airflow within the minimum and maximum limits approved for evaporator coil, electric heat and outdoor unit. Speed tap adjustments are made at the motor terminal block, See Figure 11. Airflow data is shown in Tables 6 and 11.

The unit control is designed for the addition of a two speed fan kit. See accessory kit for details.

4-5 TON HIGH EFFICIENCY MOTOR (X-13)

1-1/2 TON TO 4 TON STANDARD MOTOR

TO RELAY

TO CONTROL BOARD C (Common)

FACTORY WIRED TO TRANSFORMER

PUR PUR

BLK

YEL

CAP

FACTORY WIRED TO FAN MOTOR RELAY TERMINAL ON CONTROL BOARD

BRN

1 2 3 4 5

C G

GRN

BLU

HIGH

L N

YEL

YEL

PUR TO TRANSFORMER

GRN BLOWER

230V 208 / 230V FAN MOTOR

GND. 230 VOLT BLOWER MOTOR

FIGURE 11Blower Speed Connections
Page 9 of the Coleman Air Handler (F*FP) user manual — LOW VOLTAGE CONTROL CONNECTION
Page 9 · click to enlarge
Page 9
TABLE 3Physical and Electrical Data
Models F*FP024030036040 Blower - Diameter x Width10 x 610 x 810 x 810 x 8 MotorHP1/41/31/21/3 Nominal RPM1075107510751075 Voltage208/230 AmpsFull Load (208/230)1.6/1.4 (50 Hz:2.1)2.5 / 2.23.3/2.9 (50 Hz:2.3)2.5 / 2.2 Locked Rotor (208/230)3.3 / 2.96.2 / 5.57.4 / 6.56.2 / 5.5 Filter1TypeDISPOSABLE OR PERMANENT Size16 x 20 x 116 x 20 x 120 x 20 x 120 x 20 x 1 Permanent Type Kit1PF0601BK1PF0601BK1PF0602BK1PF0602BK Shipping / Operating Weight (lbs.)98 / 93105 / 100115 / 109121 / 115
Models F*FP042045048060 Blower - Diameter x Width10x810x1011x1011x10 MotorHP3/41/31.01.0 Nominal RPM113092510501050 Voltage208/230230 AmpsFull Load (208/230)4.4/3.83.0/2.77.67.6 Locked Rotor (208/230)11.9/10.34.8/4.1–– Filter1TypeDISPOSABLE OR PERMANENT Size20 x 20 x 122 x 20 x 122 x 20 x 122 x 20 x 1 Permanent Type Kit1PF0602BK1PF0603BK1PF0603BK1PF0603BK Shipping / Operating Weight (lbs.)121/115150/144153/147160/154
1. Field Supplied
TABLE 4Electrical Data - Cooling Only (50 & 60 Hz)
Models F*FPTotal Motor AmpsMinimum Circuit AmpacityMax. O.C.P.1 Amps/TypeMinimum Wire Size A.W.G. 60 Hertz60 Hertz 208V240V208V240V 0241.61.52.01.81514 0302.52.33.22.81514 0363.33.04.23.71514 0402.52.33.22.81514 0424.44.05.54.81514 0453.12.63.93.41514 0487.67.69.59.51514 0607.67.69.59.51514
1. OCP = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.
TABLE 5Conversion Table
KW & MBH Conversions - for Total Power Input Requirement FOR208VOPERATION MULTIPLY240VTABULATED KW & MBH BY.751 230V240V.918 220V240V.840
Page 10 of the Coleman Air Handler (F*FP) user manual — LOW VOLTAGE CONTROL CONNECTION
Page 10 · click to enlarge
Page 10
TABLE 6Electrical Data - 1 Ø - 208/230-1-60 1
Models F*FPHeater* ModelMax. Static & Min. CFMTotal Heat2KW Staging3 KWMBHW1 OnlyW2 OnlyW1 + W2 StaticTap208V240V208V240V208V240V208V240V208V240V 0242HK*6500506B0.5Low3.85.013.017.13.85.03.85.03.85.0 2HK*6500806BLow5.67.519.125.63.85.05.67.55.67.5 2HK*6501006BLow7.510.025.634.13.85.07.510.07.510.0 0302HK*6500506B0.5Low3.85.013.017.13.85.03.85.03.85.0 2HK*6500806BLow5.67.519.125.63.85.05.67.55.67.5 2HK*6501006BLow7.510.025.634.13.85.07.510.07.510.0 2HK16501506BHI11.315.038.651.23.85.07.510.011.315.0 0362HK*6500506B0.5Low3.85.013.017.13.85.03.85.03.85.0 2HK*6500806BLow5.67.519.125.63.85.05.67.55.67.5 2HK*6501006BLow7.510.025.634.13.85.07.510.07.510.0 2HK16501506BMed11.315.038.651.23.85.07.510.011.315.0 2HK16501906B40.5High13.217.645.160.12.83.810.413.813.217.6 0402HK*6500506B0.5Low3.85.013.017.13.85.03.85.03.85.0 2HK*6500806BLow5.67.519.125.63.85.05.67.55.67.5 2HK*6501006BLow7.510.025.634.13.85.07.510.07.510.0 2HK16501506BHigh11.315.038.651.23.85.07.510.011.315.0 0422HK*6500506B0.5Low3.85.013.017.13.85.03.85.03.85.0 2HK*6500806BLow5.67.519.125.63.85.05.67.55.67.5 2HK*6501006BLow7.510.025.634.13.85.07.510.07.510.0 2HK16501506BLow11.315.038.651.23.85.07.510.011.315.0 0452HK*6500506B0.5Low3.85.013.017.13.85.03.85.03.85.0 2HK*6500806BLow5.67.519.125.63.85.05.67.55.67.5 2HK*6501006BMed7.510.025.634.13.85.07.510.07.510.0 2HK16501506BHigh11.315.038.651.23.85.07.510.011.315.0 0482HK*6500506B0.5Med Low3.85.013.017.13.85.03.85.03.85.0 2HK*6500806BMed Low5.67.519.125.63.85.05.67.55.67.5 2HK*6501006BMed Low7.510.025.634.13.85.07.510.07.510.0 2HK16501506BMed Low11.315.038.651.23.85.07.510.011.315.0 2HK16502006BMed Low15.020.051.268.33.85.011.310.015.020.0 2HK16502506BMed Low18.825.064.285.33.85.011.315.018.825.0 0602HK*6500506B0.5Med3.85.013.017.13.85.03.85.03.85.0 2HK*6500806BMed5.67.519.125.63.85.05.67.55.67.5 2HK*6501006BMed7.510.025.634.13.85.07.510.07.510.0 2HK16501506BMed11.315.038.651.23.85.07.510.011.315.0 2HK16502006BMed15.020.051.268.33.85.07.510.015.020.0 2HK16502506BMed18.825.064.285.33.85.011.315.018.825.0
1. Heat amps shown at 240V represents maximum heater rating. 2. See conversion Table 5. 3. If first stage heat or 66 is connected to W1, otherwise refer to this table. 4. 2HK16501906B only applies to F4FP036 model.

* May be 0 (no breaker) or 1 (with breaker).

Page 11 of the Coleman Air Handler (F*FP) user manual — LOW VOLTAGE CONTROL CONNECTION
Page 11 · click to enlarge
Page 11

TABLE 7: Electrical Data - (For Single Source Power Supply) - Copper Wire 1 Ø - 208/230-1-601

Models F*FPHeater* ModelHeater Amps 240VField Wiring Min. Circuit AmpacityMax. O.C.P.2 Amps/Type75°C Wire Size - AWG 208V240V208V240V208V240V 0242HK*6500506B20.824.727.725301010 2HK*6500806B31.335.540.7404588 2HK*6501006B41.746.953.7506086 0302HK*6500506B20.825.828.730301010 2HK*6500806B31.336.741.7404588 2HK*6501006B41.748.154.7506086 2HK16501506B62.570.980.8809043 0362HK*6500506B20.826.829.530301010 2HK*6500806B31.337.742.6404588 2HK*6501006B41.749.155.6506086 2HK16501506B62.571.981.6809043 2HK16501906B373.383.395.29010033 0402HK*6500506B20.825.828.730301010 2HK*6500806B31.336.741.7404588 2HK*6501006B41.748.154.7506086 2HK16501506B62.570.980.8809043 0422HK*6500506B20.828.130.53035108 2HK*6500806B31.338.943.6404588 2HK*6501006B41.750.356.6606066 2HK16501506B62.573.282.6809043 0452HK*6500506B20.826.629.330301010 2HK*6500806B31.337.442.3404588 2HK*6501006B41.748.855.3506086 2HK16501506B62.571.781.4809043 0482HK*6500506B20.832.835.6354088 2HK16500806B31.343.048.4455088 2HK16501006B41.755.361.5607064 2HK16501506B62.577.387.8809043 2HK16502006B83.3101.0113.811012521 2HK16502506B104.2124.3139.912515011/0 0602HK*6500506B20.832.835.6354088 2HK16500806B31.342.948.3455088 2HK16501006B41.755.361.6607064 2HK16501506B62.578.587.8809043 2HK16502006B83.3101.0113.811012521 2HK16502506B104.2122.2139.512515011/0
1. Heat amps shown at 240V represents maximum heater rating. 2. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse. 3. 2HK16501906B only applies to F4FP036 model.

* May be 0 (no breaker) or 1 (with breaker).

TABLE 8: Electrical Data - (For Multi-Source Power Supply) - Copper Wire 1 Ø - 208/230-1-601

Models F*FPHeater ModelMin. Circuit AmpacityMax. O.C.P.1 Amps/Type75°C Wire Size - AWG CircuitCircuitCircuit 1st2nd3rd1st2nd3rd1st2nd3rd 208/240208/240208/240208/240208/240208/240208/240208/240208/240 0302HK16501506B25.8/28.745.1/52.1—30/3050/60—10/108/6— 0362HK16501506B26.8/29.545.1/52.1—30/3050/60—10/108/6— 2HK16501906B238.3/42.645.7/52.6—40/4550/60—8/88/6— 0402HK16501506B25.8/28.745.1/52.1—30/3050/60—10/108/6— 0422HK16501506B28.1/30.545.1/52.1—30/3550/60—10/88/6— 0452HK16501506B26.6/29.345.1/52.1—30/3050/60—10/108/6— 0482HK16501506B32.8/35.645.1/52.1—35/4050/60—8/88/6— 2HK16502006B55.3/61.645.1/52.1—60/7050/60—6/48/6— 2HK16502506B32.8/35.645.1/52.145.1/52.135/4050/6050/608/88/68/6 0602HK16501506B32.8/35.645.1/52.1—35/4050/60—8/88/6— 2HK16502006B55.3/61.645.1/52.1—60/7050/60—6/48/6— 2HK16502506B33.8/35.645.1/52.145.1/52.135/4050/6050/608/88/68/6
1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse. 2. 2HK16501906B only applies to F4FP036 model.
Page 12 of the Coleman Air Handler (F*FP) user manual — LOW VOLTAGE CONTROL CONNECTION
Page 12 · click to enlarge
Page 12
TABLE 9Electrical Data - 3 Ø - 208/230-3-60 1
Models F*FPHeater2 ModelMax. Static & Min. CFMTotal HeatKW Staging3 KWMBHW1 OnlyW2 OnlyW1 + W2 StaticTap208240208240208240208240208240 0242HK06501025B0.5Low7.510.025.634.13.85.07.55.07.510.0 0302HK06501025B0.5Low7.510.025.634.13.85.07.55.07.510.0 2HK06501525B0.5High11.315.038.651.23.85.07.510.011.315.0 0362HK06501025B0.5Low7.510.025.634.13.85.07.55.07.510.0 2HK06501525B0.5High11.315.038.651.23.85.07.510.011.315.0 0402HK06501025B0.5Low7.510.025.634.13.85.07.55.07.510.0 2HK06501525B0.5High11.315.038.651.23.85.07.510.011.315.0 0422HK06501025B0.5Low7.510.025.634.13.85.07.55.07.510.0 2HK06501525B0.5Low11.315.038.651.23.85.07.510.011.315.0 0452HK06501025B0.5Med7.510.025.634.13.85.07.55.07.510.0 2HK06501525B0.5High11.315.038.651.23.85.07.510.011.315.0 0482HK06501025B0.5Med Low7.510.025.634.13.85.07.55.07.510.0 2HK06501525B0.5Med Low11.315.038.651.23.85.07.510.011.315.0 0602HK06501025B0.5Med7.510.025.634.13.85.07.55.07.510.0 2HK06501525B0.5Med11.315.038.651.23.85.07.510.011.315.0
1. Heat amps shown at 240V represents maximum heater rating. 2. Heaters are 3 Phase. 3. If first stage heat or 66 is connected to W1, otherwise refer to this table.

TABLE 10: Electrical Data - (For Single Source Power Supply) - Copper Wire 3 Ø - 208/230-3-601

Models F*FPHeater2 ModelField Wiring Min. Circuit AmpacityMax. O.C.P.3 Amps/Type75°C Wire Size - AWG 208V240V208V240V208V240V 0242HK06501025B41.246.5455088 0302HK06501025B42.247.4455088 2HK06501525B42.247.4455088 0362HK06501025B43.148.2455088 2HK06501525B43.148.2455088 0402HK06501025B42.247.4455088 2HK06501525B42.247.4455088 0422HK06501025B44.249.1455088 2HK06501525B44.249.1455088 0452HK06501025B42.847.9455088 2HK06501525B42.847.9455088 0482HK06501025B48.353.9506086 2HK06501525B48.353.9506086 0602HK06501025B48.353.9506086 2HK06501525B48.353.9506086
1. Heat amps shown at 240V represents maximum heater rating. 2. Heaters are 3 Phase. 3. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.
Page 13 of the Coleman Air Handler (F*FP) user manual — F4FV060H06T2*
Page 13 · click to enlarge
Page 13
TABLE 11Airflow Data for 230 Volt - Heat Pump Models 1

CFM @ External Static Pressure - IWC

0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00

High 950 910 865 835 775 730 662 590 502 400

F4FP024H06T2*

High 1,270 1,210 1,150 1,085 1,015 946 862 769 645 502

F4FP030H06T2*

High - 1,310 1,250 1,175 1,120 1,053 983 894 779 645

F4FP036H06T2*

High 1,270 1,210 1,150 1,085 1,015 946 802 769 645 502

F4FP040H06T2*

High - 1,575 1,500 1,420 1,350 1,273 1,192 1,102 996 871

F4FP042H06T2*

High 1,575 1,535 1,475 1,390 1,310 1,245 1,147 1,030 897 735

Med High 1,375 1,315 1,255 1,185 1,110 1,040 944 848 732 606

F4FP045H06T2*

Med Low 1,210 1,160 1,110 1,050 980 921 844 737 640 533

High 2223 2158 2090 2029 1929 1861 1788 1679 1594 1501

Med High 1948 1904 1801 1815 1777 1741 1681 1618 1539 1453

F5FP048H06T2*

Med Low 1499 1454 1415 1370 1328 1269 1228 1191 1132 1093

High 2195 2145 2070 2008 1920 1852 1754 1663 1570 1462

Med High 1938 1899 1873 1824 1791 1724 1679 1603 1521 1420

F5FP060H06T2*

Med Low 1525 1483 1441 1383 1356 1291 1253 1208 1169 1123

High 2,285 2,195 2,105 2,015 1,950 1,845 1,770 1,685 1,590 1,485

F4FV060H06T2*

1. Includes Return Air Filter and Largest Electric Heater.

All F*FP series air handler units are UL Listed up to 0.50" w.c. external static pressure, including air filter, wet coil, and largest KW size heater.

230 Volt · Models Blower Motor · Speed

Page 14 of the Coleman Air Handler (F*FP) user manual — F4FV060H06T2*
Page 14 · click to enlarge
Page 14
TABLE 12Airflow Data 1 for 208 Volt - Heat Pump Models

CFM @ External Static Pressure - IWC

0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00

High 855 819 779 752 698 657 596 531 452 360

F4FP024H06T2*

High 1143 1089 1035 977 914 851 776 692 581 451

F4FP030H06T2*

High 1235 1179 1125 1058 1008 947 885 804 701 580

F4FP036H06T2*

High 1143 1089 1035 977 914 851 776 692 581 451

F4FP040H06T2*

High 1400 1418 1350 1278 1215 1145 1073 991 897 784

F4FP042H06T2*

High 1418 1382 1328 1251 1179 1120 1032 927 807 661

Med-high 1238 1184 1130 1067 999 936 850 763 659 545

F4FP045H06T2*

Med-low 1089 1044 999 945 882 829 760 663 576 480

High 2209 2140 2093 2000 1939 1864 1746 1724 1655 1587

Med High 1945 1906 1871 1819 1784 1741 1667 1640 1595 1550

F5FP048H06T2*

Med Low 1506 1464 1415 1369 1325 1283 1238 1193 1139 1100

High 2134 2124 2052 1979 1861 1756 1639 1597 1512 1427

Med High 1916 1875 1838 1777 1744 1671 1594 1584 1537 1490

F5FP060H06T2*

Med Low 1494 1435 1390 1341 1284 1241 1194 1139 1087 1036

High 2057 1976 1895 1814 1728 1661 1593 1517 1431 1337

F4FV060H06T2*

1. Includes Return Air Filter and Largest Electric Heater. All F*FP series air handler units are UL Listed up to 0.50" w.c. external static pressure, including air filter, wet coil, and largest KW size heater.

208 Volt · Models Blower Motor · Speed

Page 15 of the Coleman Air Handler (F*FP) user manual — NOTES:
Page 15 · click to enlarge
Page 15

F* SERIES F* SERIES

Air Handler Control Wiring Typical A/C - Cooling only Applications

Air Handler Control Wiring Typical A/C with Electric Heat Applications

THERMOSTAT AIR HANDLER

THERMOSTAT AIR HANDLER

BOARD 1 - STAGE AIR CONDITIONING R R

BOARD 1 - STAGE AIR CONDITIONING R R

Y Y

Y

Y Y

Y

G G

G G

1 Field Installed Jumper - If Required

W1

W1

HUMIDISTAT

W1

W1

HUMIDISTAT

W2

W2

W2

W2

O

O

HUM

HUM

CFM selection board only on F4FV model

1 NOTEDehumidification control connection (”Humidistat” jumper on CFM selection board must be removed)

CFM selection board only on F4FV model

Y1

Y1

Y2

Y2

FIGURE 12Cooling Models with Electric Heat Wiring

AIR HANDLER

THERMOSTAT

BOARD HEAT PUMP

R R R

Y Y Y

G G

E W1 W1 Out

W2 W2

O O O

L X/L

W1 W

HUM

HUMIDISTAT 1

CFM selection board only on F4FV model

Y1

Y2

FIGURE 13Single Stage Heat Pump Control Wiring

NOTES:

1. “Y” Terminal on Air Handler Control Board must be connected for full CFM and applications requiring 60 second Blower Off Delay for SEER enhancement.
2. 1 Optional Dehumidification Humidistat contacts open on rise. 3. For F4FV model - Remove Humidistat Jumper on CFM Selection Board - if used. 4. For F4FV model - For Heat Pump Applications - Remove Heat Pump Jumper on CFM Selection Board. 5. To change quantity of heat during HP defrost cycle - Reverse connections at W1 and W2 on Air Handler Control Board.
Page 16 of the Coleman Air Handler (F*FP) user manual — Unitary 5005 Norman Product York OK Group Drive 73069
Page 16 · click to enlarge
Page 16

DRAIN CONNECTIONS

The drain pan connections are designed to ASTM Standard D 2466 Schedule 40. 3/4" PVC is preferred. Since the drains are not subject to any pressure it is not necessary to use Schedule 40 pipe for drain lines.

All drain lines should be trapped a minimum of three inches, should be pitched away from unit drain pan and should be no smaller than the coil drain connection.

It is recommended that all drain connections be sealed with teflon tape or equivalent.

MAINTENANCE

Filters must be cleaned or replaced when they become dirty. Inspect at least once per month. The frequency of cleaning depends upon the hours of operation and the local atmospheric conditions. Clean filters keep unit efficiency high.

Threaded drain connection should be hand-tightened, plus no more than one turn.

COIL CLEANING

If the coil needs to be cleaned or replaced, it should be washed with Calgon CalClean (mix one part CalClean to ten parts water). Allow solu- tion to remain on coil for 30 minutes before rinsing with clean water. Solution should not be permitted to come in contact with painted sur- faces.

Horizontal drain cutout in the center access panel should be removed by using a utility knife. DO NOT TRY TO KNOCK OUT.

Route the drain line so that it does not interfere with accessibility to the coil, air handling system or filter and will not be exposed to freezing temperatures. See Figures 2, 3 and 4.

LUBRICATION

The bearings of the blower motor are permanently lubricated.

CONDENSATE DRAINS

During the cooling season check the condensate drain lines to be sure that condensate is flowing from the primary drain but not from the sec- ondary drain. If condensate ever flows from the secondary drain the unit should be promptly shut off and the condensate pan and drains cleaned to insure a free flowing primary drain.

The coil is provided with a secondary drain that should be trapped and piped to a location that will give the occupant a visual warning that the primary drain is clogged. If the secondary drain is not used it must be capped.

TROUBLESHOOTING GUIDE

PROBLEM POSSIBLE CAUSE

1. No heat units do not have 6-pin connector installed. 2. Limit open or not connected. 3. Variable speed break-out tab broken out. 4. Blower OFF delay (approx. 1 min). 5. Thermostat fan switch in “ON” position.

Blower Runs all of the time

Blown Fuse 1. Low voltage short to C or ground from R, Y, G, W, or O.

1. 4-pin connector loose. 2. Loose wire from control to transformer (24V and 230V). 3. Blown fuse on control board.

No 2nd stage heat 1. Check 6-pin connector and connections to panel mount relays. 2. Verify that both W1 & W2 are connected at the terminal strip.

1. Check filter. 2. Closed registers. 3. Restricted airflow (supply registers or return registers) 4. Check blower motor operation. 5. If the safety limit opens 4 times, the control will not permit the heating element to operate for 1 hour.

No Heat or Limited Heating

Subject to change without notice. Printed in U.S.A. 292043-UIM-B-0707 Copyright © by York International Corp. 2007. All rights reserved. Supersedes: 292043-UIM-A-0507

Unitary 5005 Norman Product York OK Group Drive 73069

No 24V

Ask about the Coleman Air Handler (F*FP)

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Coleman Air Handler (F*FP)

Be the first to ask — other owners or our team will answer.

Original document

Coleman Air Handler (F*FP) manual PDF

16 pages·225 KB·Air Conditioner·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…