Instruction/ maintenance manual of the product 20_PV_I Burnham
Go to page of 32
1 8141775R12-3/01 Price - $3.00 INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS FOR SERIES 2PV POWER VENT GAS - FIRED BOILER For service or repairs to boiler, call your heating contractor. When seeking information on boiler, provide Boiler Model Number and Serial Number as shown on Rating Label.
2 The following terms are used throughout this manual to bring attention to the presence of hazards of various risk levels, or to important information concerning product life. Table of Contents I. Pre-Installation ....................................
3 Figure 1: Elevation Views.
4 I. Pre-Installation C. Appliance is design certified for installation on combustible flooring. The boiler must not be installed on carpeting. D. Provide clearance between boiler jacket and combustible material in accordance with local fire ordinance.
5 2 . Determine Total Input of all appliances in space. Round result to nearest 1,000 Btu per hour (Btuh). 3 . Determine type of space. Divide Volume by Total Input. a . If result is greater than or equal to 50 ft³ per 1,000 Btuh, space is considered an unconfined space .
6 III. Water Piping and Trim CAUTION Failure to properly pipe boiler may result in improper operation and damage to boiler or building. A. Design and install boiler and system piping to prevent oxygen contamination of boiler water.
7 Figure 3: Recommended Boiler Piping For Series - Loop Hot Water Heating Systems Figure 4: Recommended Piping for Combination Heating & Cooling (Refrigeration) Systems.
8 IV. Gas Piping A. Size gas piping. Design system to provide adequate gas supply to boiler. Consider these factors: 1. Allowable pressure drop from point of delivery to boiler. Maximum allowable system pressure is ½ psig. Actual point of delivery pressure may be less; contact gas supplier for additional information.
9 Table 2: Maximum Capacity of Schedule 40 Pipe in CFH For Gas Pressures of 0.5 psig or Less Table 3: Fitting Equivalent Lengths Table 4: Specific Gravity Correction Factors Length [Feet] 0.
10 Table 5: Burnham Vent System Components Figure 7: Vent Connector Installation B. Removal of Existing Boiler. For installations not involving the replacement of an existing boiler, proceed to Step C.
11 D. Install Vent Pipe, General. 1. Start at vent connector. Work toward vent terminal. 2. Use ¾ inch pipe strap to support horizontal runs, maintain vent location and slope, and prevent sags. Do not restrict thermal expansion movement. Maximum support spacing is 5 feet.
12 Figure 9: Recommendations for Thimble and Wall Penetration VI. Electrical A. General. Install wiring and ground boiler in accordance with requirements of authority having jurisdiction, or in absence of such requirements the National Electrical Code , ANSI/NFPA 70, and/or the CSA C22.
13 Figure 10: Wiring Diagram Figure 11: Main Burner Installation VII. System Start-up A. Safe operation and other performance criteria were met with gas manifold and control assembly provided on boiler when boiler underwent tests specified in American National Standard for Gas-Fired Low- Pressure Steam and Hot Water Boilers, ANSI Z21.
14 Figure 12: Gas Valve Pressure Tap D. Prepare to check operation. 1. Obtain gas heating value (in Btu per cubic foot) from gas supplier. 2. Connect manometer to pressure tap on gas valve. See Figure 12. 3. For natural gas fired boiler, temporarily turn off all other gas-fired appliances.
15 Figure 16: Main Burner Flame J. Check thermostat operation. Raise and lower temperature setting to start and stop boiler operation. K. Check ignition control module shut-off. Disconnect igniter/sensor cable from Terminal 9 (SPARK). Gas valve should close and pilot and main burners should extinguish.
16 Figure 17: Operating Instructions Adjust gas valve pressure regulator as necessary (turn adjustment screw counterclockwise to decrease manifold pressure, or clockwise to increase manifold pressure). If pressure can not be attained, check gas valve inlet pressure.
17 TROUBLE SHOOTING GUIDE SPLIT (SEPARATE) CONTROLS, 24 VOLT OPERATION WITH ELECTRONIC IGNITION AND INTERMITTENT CIRCULATION NOTE: 1. Read Sequence of Operation prior to using Trouble Shooting Guide. See Page 14. 2. Prior to replacing a control, always check for broken wires or loose connectors that provide power to that control.
18.
19 Note : Minimum pilot signal should be 1.0 microamps. Disconnect Pilot Ground wire from Module and connect DC microammeter between Ground Terminal and Pilot Ground wire.
20 Important Product Safety Information Refractory Ceramic Fiber Product Warning : This product contains refractory ceramic fibers (RCF). RCF has been classified as a possible human carcinogen. After this product is fired, RCF may, when exposed to extremely high temperature (>1800F), change into a known human carcinogen.
21 VIII. Service A. General. Inspection and service should be conducted annually. Turn off electrical power and gas supply while conducting service or maintenance. Follow instructions TO TURN OFF GAS TO APPLIANCE. See Figure 17. CAUTION Label all wires prior to disconnection when servicing controls.
22 Table 7: Pilot Burner Location Figure 18: Spark Gap Setting Figure 19: Flueway Cleaning at rear of burner. See Figure 11. Slide burner over orifice. 7. Reconnect pilot gas supply, igniter/sensor cable, and ground wire. Reinstall Burner Access Panel.
23 Table 8: Minimum Suction Pressure Figure 20: Procedure for Measuring Fan Suction Pressure I. Lubrication. There are no parts requiring lubrication by service technician or owner. Circulator bearings are water lubricated. Blower motor bearings are factory sealed.
24 IX. Repair Parts All Series 2PV Repair Parts may be obtained through your local Burnham Wholesale distributor. Should you require assistance in locating a Burnham distributor in your area, or have questions regarding the availability of Burnham products or repair parts, please contact your Burnham Regional Sales Office as listed below.
25 Key No. Description [Quantity] Part Number 203PV 204PV 205PV 206PV 1. Section Assembly 617170321 617170421 617170521 617170621 2. Canopy/Blower Assembly 2A Canopy [1] 61117034 [1] 61117044 [1] 6111.
26 Key No. Description [Quantity] Part Number 203PV 204PV 205PV 206PV 3. Base Assembly Group 3 Base Assembly, Complete [1] 618600391 [1] 618600491 [1] 618600591 [1] 618600691 3A Base Tray Assembly [1].
27 Key No. Description [Quantity] Part Number 203PV 204PV 205PV 206PV 4. Manifold and Main Burners 4A Main Burner [2] 8236099 [4] 8236099 [6] 8236099 [8] 8236099 4B Main Burner with 60° Pilot Bracket.
28 Key No. Description [Quantity] Part Number 203PV 204PV 205PV 206PV 5. Pilot Burner and Gas Valve 5A Pilot Assembly, Natural Gas, Honeywell Q348A1333 [1] 8236104 Pilot Assembly, LP Gas, Honeywell Q348A1341 [1] 8236107 5B Pilot Orifice, Natural Gas Honeywell 388146NE Included with Key No.
29 Key No. Description [Quantity] Part Number 203PV 204PV 205PV 206PV 6. Jacket 6A Jacket Wrap-A-Round Panel (1) [1] 604170312 [1] 604170412 [1] 604170512 [1] 604170612 6B Jacket Upper Vestibule Panel.
30.
31 Key No. Description [Quantity] Part Number 203PV 204PV 205PV 206PV 7. Miscellaneous Trim and Controls 7A Safety Relief Valve, 30 psi, ¾ NPT, Conbraco 10-408-05 [1] 81660319 7B Limit, Honeywell L40.
32.
An important point after buying a device Burnham 20_PV_I (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Burnham 20_PV_I yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Burnham 20_PV_I - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Burnham 20_PV_I you will learn all the available features of the product, as well as information on its operation. The information that you get Burnham 20_PV_I will certainly help you make a decision on the purchase.
If you already are a holder of Burnham 20_PV_I, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Burnham 20_PV_I.
However, one of the most important roles played by the user manual is to help in solving problems with Burnham 20_PV_I. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Burnham 20_PV_I along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center