Instruction/ maintenance manual of the product R-410A Bryant
Go to page of 28
Form No. PDS 591B.18.1 DELUXE 11 SEER AIR CONDITIONER WITH PURON ® (R-410A) 591B (60 Hz) Sizes 018 thru 060 Br yant’ s Quantum Plus 591B with Puron® provides features which cannot be matched by any other family of equipment. The 591B is a Quantum Plus air conditioning system utilizing Br y- ant’ s unique Puron refr igerant.
—2— DIMENSIONS AIR DISCHARGE AIR DISCHARGE AIR IN AIR IN AIR IN 3 / 8 " DIA. TIEDOWN KNOCKOUTS (2) PLACES L K J E D C L NOTES: 1. ALLOW 30" CLEARANCE TO SERVICE SIDE OF UNIT, 48" ABOVE UNIT, 6" ON ONE SIDE, 12" ON REMAINING SIDE, AND 24" BETWEEN UNITS FOR PROPER AIRFLOW.
— 3 — RECOMMENDED TUBE DIAMETERS * For tube sets g reater than 50 ft, consult Application Guideline and Ser vice Manual — Air Conditioners and Heat Pumps Using Puron ® Refrigerant. CHECK-FLO-RA TER ® PISTON * Piston listed is f or any approv ed non-capillar y tube coil combination.
— 4 — SPECIFICA TIONS See notes on page 5. UNIT SIZE-SERIES 018-A 024-A 030-A 036-A Operating W eight (Lb) 168 178 188 198 ELECTRICAL Unit V olts — Hertz — Phase 208/230-60-1 Operating V oltage Range* 187-253 Compressor — Rated Load Amps 10.
— 5 — SPECIFICA TIONS Continued * P er missible limits of the v oltage range at which the unit will oper ate satisf actorily . Oper ation outside these limits may result in unit f ailure. † If wire is applied at ambient g reater than 30 ° C (86 ° F), consult T able 310-16 of the NEC (ANSI/NFP A 70).
— 6 — A CCESSOR Y USA GE GUIDELINE * For tubing line sets g reater than 50 ft, refer to Application Guideline and Service Manual — Air Conditioning and Heat Pumps Using Puron ® Refrigerant. † Only when low-pressure s witch is used. ‡ Required for lo w-ambient controller (full modulation feature) and MotorMaster ® Control only .
— 7 — A CCESSOR Y DESCRIPTION AND USA GE (Listed Alphabetically) Continued 10. Low-Ambient Pressure Switc h A long life pressure s witch which is mounted to outdoor unit service valve . It is designed to cycle the outdoor f an motor in order to maintain head pressure within normal operating limits (approximately 200 psig to 365 psig).
— 8 — COMBINA TION RA TINGS See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F A CTOR Y- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR † Accessory Puron TXV 018-A CC5A/CD5AA024* 17,400 NONE 10.
— 9 — COMBINA TION RA TINGS Continued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F A CTOR Y- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR † Accessory Puron TXV 024-A CE3AA024 23,400 TDR 11.
— 10 — COMBINA TION RA TINGS Continued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F A CTOR Y- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR † Accessory Puron TXV 036-A CC5A/CD5AA042* 35,400 NONE 10.
— 11 — COMBINA TION RA TINGS Continued UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F A CTOR Y- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR † Accessory Puron TXV 036-A COILS + 355MA V060080 V ARIABLE SPEED FURNA CE CC5A/CD5AA042 35,400 TDR 11.
— 12 — UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F A CTOR Y- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR † Accessory Puron TXV 042-A CE3AA042 40,000 TDR 11.5 — 11.5 10.30 CE3AA048 40,500 TDR 11.5 — 11.
— 13 — See notes on page 14. . UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F A CTOR Y- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR † Accessory Puron TXV 048-A CE3AA060 47,000 TDR 11.5 — 11.5 10.65 CK3BA060 47,000 TDR 11.
— 14 — * T ested combination. † In most cases, only 1 method should be used to achie ve TDR function. Using more than 1 method in a system ma y cause degradation in perf or mance. Use either the accessory Time-Dela y Relay KAA TD0101TDR or a furnace equipped with TDR.
— 15 — DET AILED COOLING CAP A CITIES* See notes on page 22. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † .
— 16 — DET AILED COOLING CAP A CITIES* See notes on page 22. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † .
— 17 — DET AILED COOLING CAP A CITIES* Continued See notes on page 22. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys Kw** Capacity .
— 18 — DET AILED COOLING CAP A CITIES* Continued See notes on page 22. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys Kw** Capacity .
— 19 — DET AILED COOLING CAP A CITIES* Continued See notes on page 22. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys Kw** Capacity .
— 20 — DET AILED COOLING CAP A CITIES* Continued See notes on page 22. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys Kw** Capacity .
— 21 — DET AILED COOLING CAP A CITIES* Continued See notes on page 22. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys Kw** Capacity .
— 22 — DET AILED COOLING CAP A CITIES* Continued * Detailed cooling capacities are based on indoor and outdoor unit at the same ele vation per ARI standard 210/240-94. If additional tubing length and/or indoor unit is located abov e outdoor unit, a slight variation in capacity may occur .
— 23 — CONDENSER ONL Y RA TINGS* See notes on page 25. SST ° F CONDENSER ENTERING AIR TEMPERA TURES ° F 55 65 75 85 95 105 115 125 591BN018-A 30 TCG SDT KW 15.90 73.70 0.77 15.00 83.10 0.92 14.20 92.60 1.10 13.30 102.00 1.28 12.30 111.40 1.49 11.
— 24 — CONDENSER ONL Y RA TINGS* Continued See notes on page 25. SST ° F CONDENSER ENTERING AIR TEMPERA TURES ° F 55 65 75 85 95 105 115 125 591BN036-A 30 TCG SDT KW 32.70 77.00 1.99 30.90 86.20 2.23 29.10 95.40 2.49 27.30 104.60 2.77 25.40 113.
— 25 — SYSTEM DESIGN SUMMAR Y 1. Intended f or outdoor installation with free air inlet and outlet. Outdoor f an external static pressure av ailable is less than 0.01-in. wc. 2. Minimum outdoor oper ating air temper ature without lo w-ambient oper ation accessory is 55 ° F (12.
— 26 — MA TCHED SYSTEM A98599.
— 27 —.
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Cancels: New © 2001 Bryant Heating & Cooling Systems, 7310 W. Morris St. Indpls, IN 46231 — 28 — PRINTED IN U.S.A. Catalog No.
An important point after buying a device Bryant R-410A (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Bryant R-410A yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Bryant R-410A - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Bryant R-410A you will learn all the available features of the product, as well as information on its operation. The information that you get Bryant R-410A will certainly help you make a decision on the purchase.
If you already are a holder of Bryant R-410A, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Bryant R-410A.
However, one of the most important roles played by the user manual is to help in solving problems with Bryant R-410A. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Bryant R-410A along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center