Instruction/ maintenance manual of the product PREFERRED 265A Bryant
Go to page of 32
Pr oduct Dat a MODEL 265A PREF ERR ED SERIES HEA T PUM P WITH PURON REFRIG ERANT SIZE S 018 TO 060 1 - - 1/2 TO 5 NO MINAL TONS TM Brya nt’ s hea t pumps wit h Puron r r efr iger ant provi de a coll ect ion of features un match ed by any o ther family of eq ui pmen t.
2 MODEL NUMBER NOMENCLA TURE 12 3 4 5 6 7 8 9 1 0 1 1 1 2 1 4 N N N A A/N N N N N A/N A/N N A 26 5 A N A 0 3 6 0 0 0 A Pro duct Fa mi ly Tie r SEER Major Series Voltag e Vari ations Cooling Capacit y .
3 PHYS ICAL DA T A UNIT SIZE SER IES 018 - - - B 024 - - - B 030 - - - B 036 - - - B 042 - - - B 048 - - - B 060 - - - B Operat ing Weig ht (lb ) 198 244 280 299 318 325 307 Shippin g Weight (lb) 232 280 310 335 354 361 344 Compressor T ype Scroll REFRIGERAN T Puron (R - - - 410A) Cont rol TXV (Puro n Hard Shutoff) Charge ( lb) 6.
4 ACCESSO RIES KIT NUMBE R KIT NA ME 018 - - - B 024 - - - B 030 - - - B 036 - - - B 042 - - - B 048 - - - B 060 - - - B KAACH1201AAA CRANKCASE HEA TER X X S S KAACH1401AAA CRANKCASE HEA TER X X X KSA.
5 ACCESSO R Y USAGE GUIDELINE ACCESSORY RE QUIRED F OR LOW - - - A MBIENT COOLING APPLIC ATIONS (Below 55 F) REQUI RED FOR LONG LINE APPLICATIONS* (Over 80 F t.
6 Accesso ry Descripti on an d Usage (Li sted Alp ha betica lly ) - - C ONTI NUED 10. Outdoor A ir T empe ratur e Se nsor De si gne d for us e w it h Brya nt Ther most at s li s te d in thi s publi cat ion. This de vice e nable s the ther mosta t to dis play the outdoor t empe ra ture .
7 ELECTRICAL DA T A UNI T SIZ E V/PH OPER VOL T S* CO MPR FAN MCA MIN WIRE SIZE { MIN WIRE SIZE { MAX LENGTH (F T) } MAX LENGTH (F T) } MAX FUSE** or CKT BRK AMPS MAX MIN LRA RLA FLA 60 C 75 C 60 C 75 C 018 - - - B 208/230/1 253 197 48 9 0.
8 DIMENSIONS 265A.
9 265A BALANCE POINT WORKSHEET 0 10 20 30 40 50 60 70 80 - - 1 0 0 1 02 03 04 05 06 07 0 8 0 OUT DOOR TE MPE RA TU RE , ºF BUILDI NG HEA T LOSS, UNI T INTEGRA TED HEA TING CAP ACI TY , MBTUH 0.
10 COMBINA TION RA TINGS Unit Size --- S e r i e s Indoor Model Cooling Capacity ARI Standard Ratings Cooling Heating Furn ace M odel Factory Enhance Standard Rating SEER TDR EER High T emp Low T emp HSPF E Capacity E COP H Capacity H COP 018 - - - B *FX4CNF018 17,800 TDR&TXV 15.
11 COMBINA TION RA TINGS CONTINUED Unit Size --- S e r i e s Indoor Model Cooling Capacity ARI Standard Ratings Cooling Heating Furn ace M odel Factory Enhance Standard Rating SEER TDR EER High T emp Low T emp HSPF E Capacity E COP H Capacity H COP 024 - - - B CNPH*2417A** 23,000 TDR&TXV 15.
12 COMBINA TION RA TINGS CONTINUED Unit Size --- S e r i e s Indoor Model Cooling Capacity ARI Standard Ratings Cooling Heating Furn ace M odel Factory Enhance Standard Rating SEER TDR EER High T emp Low T emp HSPF E Capacity E COP H Capacity H COP 030 - - B CAP**3017A** 28,800 TDR&TXV 15.
13 COMBINA TION RA TINGS CONTINUED Unit Size --- S e r i e s Indoor Model Cooling Capacity ARI Standard Ratings Cooling Heating Furn ace M odel Factory Enhance Standard Rating SEER TDR EER High T emp Low T emp HSPF E Capacity E COP H Capacity H COP 030 - - B CSPH*3612A** 29,000 TDR&TXV 15.
14 COMBINA TION RA TINGS CONTINUED Unit Size --- S e r i e s Indoor Model Cooling Capacity ARI Standard Ratings Cooling Heating Furn ace M odel Factory Enhance Standard Rating SEER TDR EER High T emp Low T emp HSPF E Capacity E COP H Capacity H COP 036 - - B CNPH*4221A** 34,600 TDR&TXV 15.
15 COMBINA TION RA TINGS CONTINUED Unit Size --- S e r i e s Indoor Model Cooling Capacity ARI Standard Ratings Cooling Heating Furn ace M odel Factory Enhance Standard Rating SEER TDR EER High T emp Low T emp HSPF E Capacity E COP H Capacity H COP 042 - - B CAP**4821A** 41,500 TDR&TXV 14.
16 COMBINA TION RA TINGS CONTINUED Unit Size --- S e r i e s Indoor Model Cooling Capacity ARI Standard Ratings Cooling Heating Furn ace M odel Factory Enhance Standard Rating SEER TDR EER High T emp Low T emp HSPF E Capacity E COP H Capacity H COP 042 - - B CSPH*4812A** 41,500 TDR&TXV 14.
17 COMBINA TION RA TINGS CONTINUED Unit Size --- S e r i e s Indoor Model Cooling Capacity ARI Standard Ratings Cooling Heating Furn ace M odel Factory Enhance Standard Rating SEER TDR EER High T emp Low T emp HSPF E Capacity E COP H Capacity H COP 048 - - B CSPH*4812A** 47,000 TDR&TXV 14.
18 DET AILED COOLING CAP ACITIES EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES deg F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† To t a l Sys- tem KW* * Capacity MBtuh† To t a l Sys- tem KW*.
19 DET AILED COOLING CAP ACITIES CONTINUED EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES deg F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† To t a l Sys- tem KW* * Capacity MBtuh† To t a l Sy.
20 DET AILED COOLING CAP ACITIES CONTINUED EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES deg F 75 85 95 105 115 125 CFM EWB Capacity MBtu h To t a l Sys- tem KW Capacity MBtu h To t a l Sys- tem .
21 DET AILED COOLING CAP ACITIES CONTINUED EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES deg F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† To t a l Sys- tem KW* * Capacity MBtuh† To t a l Sy.
22 DET AILED COOLING CAP ACITIES CONTINUED EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES deg F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† To t a l Sys- tem KW* * Capacity MBtuh† To t a l Sy.
23 DET AILED COOLING CAP ACITIES CONTINUED EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES deg F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† To t a l Sys- tem KW* * Capacity MBtuh† To t a l Sy.
24 DET AILED COOLING CAP ACITIES CONTINUED EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES deg F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† To t a l Sys- tem KW* * Capacity MBtuh† To t a l Sy.
25 HEA T PUMP HEA TING PERF ORMANCE INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES deg F --- 3 7 17 27 37 47 57 67 EDB CF M Cap acit y MBtuh To t a l Sys- tem KW† Cap acit y MBtuh To t a l Sys- .
26 HEA T PUMP HEA TING PERFO RMANCE CONTINUED IND OOR AIR OU TDOO R CO IL EN TER ING AIR TE MPER A TUR ES de g F -- 3 7 17 27 37 47 57 67 EDB CFM Capa city MBtuh To t a l System KW† Capacity M Btuh .
27 HEA T PUMP HEA TING PERFO RMANCE CONTINUED IND OOR AIR OUTDO OR C OIL E NTE RIN G AIR TEMPE RATURE S deg F -- 3 7 17 27 37 47 57 67 EDB CFM Capa city MBtuh To t a l System KW† Capacity M Btuh To .
28 HEA T PUMP HEA TING PERFO RMANCE CONTINUED IND OOR AIR OUTDO OR C OIL E NTE RIN G AIR TEMPE RATURE S deg F -- 3 7 17 27 37 47 57 67 EDB CFM Capa city MBtuh To t a l System KW† Capacity M Btuh To .
29 HEA T PUMP HEA TING PERFO RMANCE CONTINUED IND OOR AIR OUTDO OR C OIL E NTE RIN G AIR TEMPE RATURE S deg F -- 3 7 17 27 37 47 57 67 EDB CFM Capa city MBtuh To t a l System KW† Capacity M Btuh To .
30 HEA T PUMP HEA TING PERFO RMANCE CONTINUED IND OOR AIR OUTDO OR C OIL E NTE RIN G AIR TEMPE RATURE S deg F -- 3 7 17 27 37 47 57 67 EDB CFM Capa city MBtuh To t a l System KW† Capacity M Btuh To .
31 HEA T PUMP HEA TING PERFO RMANCE CONTINUED IND OOR AIR OUTDO OR C OIL E NTE RIN G AIR TEMPE RATURE S deg F -- 3 7 17 27 37 47 57 67 EDB CFM Capa city MBtuh To t a l System KW† Capacity M Btuh To .
32 GUI DE SPE CI FIC A T ION S GENERAL Sy stem Descrip tion Outdoor- - mount ed, a ir- -coole d, s pli t - - sys te m he at pump uni t sui tabl e for ground or roof top inst all ati on. Unit c onsi st s of a her met ic c ompr es sor , an ai r- - c oole d coi l, prope ll er- - type conde nse r fa n, and a cont rol box.
An important point after buying a device Bryant PREFERRED 265A (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Bryant PREFERRED 265A yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Bryant PREFERRED 265A - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Bryant PREFERRED 265A you will learn all the available features of the product, as well as information on its operation. The information that you get Bryant PREFERRED 265A will certainly help you make a decision on the purchase.
If you already are a holder of Bryant PREFERRED 265A, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Bryant PREFERRED 265A.
However, one of the most important roles played by the user manual is to help in solving problems with Bryant PREFERRED 265A. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Bryant PREFERRED 265A along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center