Single-Package Rooftop Products with Energy-Saving Features • Direct Spark Ignition • Low Sound Levels • Up to 81% AFUE • 12 SEER FEA TURE/BENEFITS One-piece heating and cooling units with low sound levels, easy installation, low maintenance, and dependable performance.
jobsite. A nesting feature ensures a positive basepan to roof curb seal when the unit is roof mounted. A convenient 3 ⁄ 4 -in. wide perimeter flange makes frame mounting on a rooftop easy . Downflow Operation is easily provided in the field to allow ver- tical ductwork connections.
MODEL NUMBER NOMENCLA TURE CU — Copper ARI* CAP ACITIES COOLING CAP ACITIES AND EFFICIENCIES UNIT 583A NOMINAL TONS ST ANDARD CFM NET COOLING CAP ACITIES (Btuh) SEER† SOUND RA TINGS** (Bels) 024040 2 800 24,000 12.0 7.2 024060 030040 2 1 ⁄ 2 1000 30,000 12.
ARI* CAP ACITIES (cont) HEA TING CAP ACITIES AND EFFICIENCIES UNIT 583A HEA TING INPUT (Btuh) OUTPUT CAP ACITY (Btuh) TEMPERA TURE RISE RANGE (°F) AFUE (%) 024040 40,000 32,040 20-50 80.1 030040 80.0 024060 60,000 47,040 35-65 78.4 030060 47,040 35-65 80.
PHYSICAL DA T A UNIT SIZE 583A 024040 024060 030040 030060 036060 036090 042060 042090 NOMINAL CAP ACITY (ton) 22 2 1 ⁄ 2 2 1 ⁄ 2 33 3 1 ⁄ 2 3 1 ⁄ 2 OPERA TING WEIGHT (lb) 290 290 313 313 321 321 382 382 COMPRESSORS Scroll Quantity 1 REFRIGERANT (R-22) Quantity (lb) 3.
OPTIONS AND ACCESSORIES F ACTORY -INST ALLED OPTIONS Louvered Grille provides hail and vandalism protection. See model number nomenclature for louvered grille options. Coil Options include copper/copper and vinyl-coated construc- tion for refrigerant coils.
OPTIONS AND ACCESSORIES (cont) Economizer Filter Rack Manual Outside Air Damper DAMPER BLADE MANUAL OUTSIDE AIR HOOD REPLACEMENT P ANEL 7.
BASE UNIT DIMENSIONS — UNIT SIZES 024-036 REQ’D CLEARANCES FOR OPERA TION AND SER VICING. in. (mm) Evaporator coil access side .................... 3 6 (914) Power entry side (except for NEC requirements) .......... 3 6 (914) Unit top ............
BASE UNIT DIMENSIONS — UNIT SIZES 042-060 REQ’D CLEARANCES FOR OPERA TION AND SER VICING. in. (mm) Evaporator coil access side .................. 3 6 (914) Power entry side (except for NEC requirements) ......... 3 6 (914) Unit top ...............
ACCESSOR Y DIMENSIONS UNIT 583A P ART NUMBER A in. [mm] B in. [mm] C in. [mm] D in. [mm] FLA T CURB 024-036 CPRFCURB006A00 8 [203] 1 1 27 ⁄ 32 [301] 30 5 ⁄ 8 [ 778] 28 3 ⁄ 4 [ 730] CPRFCURB007A0.
SELECTION PROCEDURE (WITH EXAMPLE) I DETERMINE COOLING AND HEA TING REQUIRE- MENTS A T DESIGN CONDITIONS: Given: Required Cooling Capacity (TC) .......... 35,000 Btuh Sensible Heat Capacity (SHC) ........... 25,000 Btuh Required Heating Capacity .....
PERFORMANCE DA T A NET COOLING CAP ACITIES 583A--024 T emp (F) Air Ent Condenser Evaporator Air — Cfm/BF 700/0.081 800/0.106 900/0.135 Evaporator Air — Ewb (F) 62 67 72 62 67 72 62 67 72 85 TC 22.3 24.9 27.6 22.9 25.3 28.1 23.3 25.6 28.3 SHC 20.2 16.
PERFORMANCE DA T A (cont) NET COOLING CAP ACITIES (cont) 583A--036 T emp (F) Air Ent Condenser Evaporator Air — Cfm/BF 1050/0.1 1 1 1200/0.142 1350/0.181 Evaporator Air — Ewb (F) 62 67 72 62 67 72 62 67 72 85 TC 31.4 36.2 40.6 32.4 37.1 41.2 33.1 37.
PERFORMANCE DA T A (cont) NET COOLING CAP ACITIES (cont) 583A--048 T emp (F) Air Ent Condenser Evaporator Air — Cfm/BF 1400/0.050 1600/0.085 1800/0.119 Evaporator Air — Ewb (F) 62 67 72 62 67 72 62 67 72 85 TC 45.2 49.7 54.7 46.4 50.9 56.0 47.5 51.
PERFORMANCE DA T A (cont) DR Y COIL AIR DELIVER Y* — HORIZONT AL AND DOWNFLOW DISCHARGE — UNIT SIZES 024-060 (Deduct 10% for 208 V olts) 230 AND 460 VOL T Unit 583A Motor Speed External Static Pressure (in. wg) 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.
PERFORMANCE DA T A (cont) 583A WET COIL PRESSURE DROP UNIT SIZE 583A AIRFLOW (cfm) PRESSURE DROP (in. wg) 024 700 0.0535 800 0.067 900 0.123 030 900 0.0687 1000 0.083 1 100 0.150 036 1 100 0.084 1200 0.100 1300 0.177 042 1300 0.099 1400 0.177 1500 0.204 048 1500 0.
PERFORMANCE DA T A (cont) HIGH AL TITUDE COMPENSA TION NA TURAL GAS ONL Y ORIFICE CONVERSION — 3.5 in. wg MANIFOLD PRESSURE* AL TITUDE (ft) INPUT (Btuh) OUTPUT (Btuh) ORIFICE NUMBER† 0-2000 40,000.
TYPICAL PIPING AND WIRING V ertical Discharge Horizontal Discharge NEC — National Electrical Code 18.
APPLICA TION DA T A 1. Condensate trap — A 2-in. condensate trap must be field supplied. 2. Ductwork — Secure downflow discharge ductwork to roof curb.
ELECTRICAL DA T A UNIT SIZE 583A V -PH-Hz VOL T AGE RANGE COMPRESSOR OUTDOOR F AN MOTOR INDOOR F AN MOTOR POWER SUPPL Y FUSE OR HACR BRKR Min Max RLA LRA FLA FLA MCA MOCP* 024 208/230-1-60 187 253 10.3 56.0 0.8 2.0 15.7 25 030 208/230-1-60 187 253 13.
TYPICAL WIRING SCHEMA TIC — 208/230-1-60 SHOWN LEGEND AHA — Adjustable Heat Anticipator BR — Blower Relay C— Contactor CAP — Capacitor COMP — Compressor Motor CR — Combustion Relay EQUIP.
TYPICAL WIRING SCHEMA TIC — 208/230-3-60 SHOWN LEGEND AHA — Adjustable Heat Anticipator BR — Blower Relay C— Contactor CAP — Capacitor COMP — Compressor Motor CR — Combustion Relay CS .
TYPICAL WIRING SCHEMA TIC — 460-3-60 SHOWN LEGEND AHA — Adjustable Heat Anticipator BR — Blower Relay C— Contactor CAP — Capacitor COMP — Compressor Motor CR — Combustion Relay CS — Ce.
CONTROLS OPERA TING SEQUENCE Heating — When the thermostat calls for heating, terminal ‘‘W’ ’ is energized, starting the induced-draft motor . When the hall- effect sensor on the induced-draft motor senses that it has reached the required speed, the burner ignition sequence be- gins.
GUIDE SPECIFICA TIONS P ACKAGED GAS HEA TING/ELECTRIC COOLING UNITS CONST ANT VOLUME APPLICA TION HV AC GUIDE SPECIFICA TIONS SIZE RANGE: 2 to 5 T ONS, NOMINAL COOLING 40,000 T O 130,000 BTUH NOMINAL HEA TING INPUT BRY ANT MODEL NUMBER: 583A P ART 1 — GENERAL 1.
GUIDE SPECIFICA TIONS (cont) L. Motors: 1. Compressor motors shall be of the refrigerant-cooled type with line-break thermal and current overload protection. 2. All fan motors shall have permanently lubricated bear- ings, and inherent, automatic reset, thermal overload protection.
.
Copyright 1999 Bryant Heating & Cooling Systems SPECIFICA TIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INST ALLED IN ACCORDANCE WITH INST ALLA TION INSTRUCTIONS Printed in U.
An important point after buying a device Bryant 583A (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Bryant 583A yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Bryant 583A - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Bryant 583A you will learn all the available features of the product, as well as information on its operation. The information that you get Bryant 583A will certainly help you make a decision on the purchase.
If you already are a holder of Bryant 583A, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Bryant 583A.
However, one of the most important roles played by the user manual is to help in solving problems with Bryant 583A. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Bryant 583A along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center