Instruction/ maintenance manual of the product 576b Bryant
Go to page of 16
Cancels : II 569C-7 2-4 II 569C-72 -5 8/15/00 IMPORT ANT — READ BEFORE INST ALLING 1. Read an d become fam iliar w ith these install ation instruc tions b efore insta lling t his unit (Fig . 1). 2. Be sure the i nst alla tion conf orms t o all a ppl icab le local a nd na tion al code s.
— 2 — INST ALLA TION NO TE: When inst alli ng any a cces sory i tem, see the m anuf ac- turer’s installation instructions packaged with the accessory . A quali f ie d age nc y must us e f ac t ory - au th orize d ki ts or acc e s- sories when mo dify ing this unit.
— 3 — T a ble 1 — Ph ysical Data LEGEND *Unit is factory supplied w ith holding charge only . †T y pical operating charge with 25 f t of interconnec ting piping. **Storage capacity of condenser coil with coil 80% fu ll of liquid R-22 at 124 F .
— 4 — DIMENSIONS (f t- i n. ) UNIT A B C D E F With Alum inum Coils (Standar d) 569C072 1-6 1 / 2 1-2 3 / 4 —1 - 2 1 / 4 1-4 5 / 16 2-9 5 / 16 569C090 1-8 1-6 1 / 2 2-9 13 / 16 1- 3 2- 5 / 16 3-.
— 5 — B. Filter Drier and Moistu re Indica tor The fil ter d rier i s factor y ins talled. Mois ture in dicat or i s a field-ins talled acc essory and s hould be instal led just aft er liqui d line s hutof f valv e at th e evapo rat or coil . Do no t use a receiver .
— 6 — the current within 10%. Use the formula shown in T able 4, Note 2, to de termine the percent vo ltage imbal ance. Ope rat ion o n impr oper line volta ge or exces sive ph ase im bala nce cons tit utes abu se a nd may cau se dama ge t o elec trica l co mponen ts.
— 7 — T ab le 4 — Ele ctrical Data LEGEND NO TES: 1. In compliance with NEC requirements f or multimotor and combina- tion load equipment (refer to NEC Ar ticles 430 and 440), the over- current protective de vice f or t he unit shall be fuse or HA CR breaker .
— 8 — VI. A CCESSOR Y INST ALLA TION At t his ti me a ny requi red access ories shoul d be in stalled on the un it. Refer to T a ble 5 for a vailabl e ac cessorie s .
— 9 — ST ART -UP I. ST ART -UP AND ADJUSTMENTS A. Chec king Co oling Contr ol Operation Start an d check the uni t for proper co olin g contro l opera tion as fol lo w s: 1.
— 10 — SER VICE I. CLEANING Inspe ct unit interi or at t he beginn ing of each co oling se ason and as ope ratin g condition s require . A. Condenser Coil Inspect co il monthly . Clean conden ser coil an nually , or as requir ed by loca tion and ou tdoor-air conditions.
— 11 — IV . CAP A CITY CONTROL (576B12 0 Only) A suction pressu re-actuated u nloader con trols 2 cy linders and provides capacity control. Unloa ders are fa ctory set (see T able 1) , but may b e field adjus ted: A. Contr ol Set Po int The c ontro l se t po int ( cylin der l oad p oint ) is adju stab le from 0 to 85 psig .
— 12 — VIII. REFRIGERANT SER VICE POR TS Eac h unit has 3 s ervic e port s: on e on th e suc tion li ne , on e on the liq uid line, and on e on the comp resso r discha rge line. Be sure caps on the po rts are tight. IX. H IGH FL O W V AL V ES Located on the compres sor hot gas and suction tubes are High Flow V alves .
— 13 — TROUBLESHOO TING GUIDE NO TE: See Fig. 15 and 16 for component arrangements. SYMPT OM CA USE REMED Y Compressor does not run — Contactor open P ower off . Restore power . Fuses blown. Replace with correct fuses after finding cause and correcting.
Copyright 20 00 Br yant H eating & Coo ling Sy stems 801 CA T ALOG NO. 5356-90 3 LEGEND FOR FIG. 15 AND 16 C— Contactor , Compressor CAP — Capacitor CB — Circuit Breaker CH — Crankcase Hea.
CL-1 ST ART -UP CHECKLIST I. PRELIMINAR Y INFORMA TION OUTDO OR: MODE L NO . ____________ ______ _____ _________ __ SERIAL NO . ___ _____ _________ _____ ______ ________ INDOOR: AI R HANDL ER MAN UF ACTUR ER _____ _________ ______________ _____ ______ ________ ______ _____ ___ MODE L NO .
Copyright 20 00 Br yant H eating & Cool ing Sy stems 801 CL-2 CA T ALOG NO . 5356-903 CUT ALONG DOT TED LINE CUT ALONG DO TTED LINE III. ST ART -UP CHECK EV APORA T OR-F AN SPEED AND RECORD .
An important point after buying a device Bryant 576b (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Bryant 576b yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Bryant 576b - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Bryant 576b you will learn all the available features of the product, as well as information on its operation. The information that you get Bryant 576b will certainly help you make a decision on the purchase.
If you already are a holder of Bryant 576b, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Bryant 576b.
However, one of the most important roles played by the user manual is to help in solving problems with Bryant 576b. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Bryant 576b along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center