Instruction/ maintenance manual of the product 355MAV Bryant
Go to page of 60
NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS SAFETY CONSIDERATIONS ........................................................................................................................................
LOCATION ..................................................................................................................................................................................................................15 General .....................
SAFETY CONSIDERATIONS Installing and servicing heating equipment can be hazardous due to gas and electrical components. Only trained and qualified personnel should install, repair, or service heating equipment. Untrained personnel can perform basic maintenance functions such as cleaning and replacing air filters.
Fig. 2—Dimensional Drawing Dimensions (in.) UNIT SIZE A D E 042040* 24-1/2 22-7/8 23* 042060 17-1/2 15-7/8 16 042080 21 19-3/8 19-1/2 060080 21 19-3/8 19-1/2 060100 21 19-3/8 19-1/2 060120 24-1/2 22-7/8 23 * These dimensions reflect the wider casing for the Trophy (96.
Before installing the furnace in Canada, refer to the current edition of the NSCNGPIC. Contact Standard Sales CSA International, 178 Rexdale Boulevard, Etobicoke, (Toronto) Ontario, Canada M9W 1R3.
ELECTROSTATIC DISCHARGE (ESD) PRECAUTION PROCEDURE CAUTION: Electrostatic discharge can affect electronic components. Follow the Electronic Discharge Precautions Procedure listed below during furnace and servicing to protect the furnace electronic control.
PROCEDURE 2—UPFLOW APPLICATIONS In an upflow application, the blower is located below the burner section, and conditioned air is discharged upwards. A. Condensate Trap Location (Factory-Shipped Orientation) The condensate trap is factory installed in the blower shelf and factory connected for UPFLOW applications.
NOTE: Failure to use CPVC elbows may allow drain to kink and prevent draining. f. Connect larger diameter drain tube and clamp (factory-supplied in loose parts bag) to condensate trap and clamp securely. g. Route tube to coupling and cut to appropriate length.
a. Connect relief port tube (green label) to condensate trap. b. Extend this tube (if required) by splicing to small diameter tube (factory-supplied in loose parts bag). c. Determine appropriate length, cut, and connect tube. E. Condensate Trap Field Drain Attachment Refer to Condensate Drain section for recommendations and procedures.
1. Remove 3 tubes connected to condensate trap. 2. Remove trap from blower shelf by gently pushing tabs inward and rotating trap. 3. Install casing hole filler cap (factory-supplied in loose parts bag) into blower shelf hole where trap was removed. 4.
c. Install cap and clamp on UPPER inducer housing drain connection where molded drain tube was removed. d. Use inducer housing drain tube (violet label and factory-supplied in loose parts bag) to connect LOWER inducer housing drain connection to the condensate trap.
a. Install drain tube coupling (factory-supplied in loose parts bag) into collector box drain tube (blue label) which was previously connected to condensate trap. b. Connect large diameter drain tube and clamp (factory-supplied in loose parts bag) to drain tube coupling, extending collector box drain tube.
CAUTION: The condensate trap MUST be installed below furnace. See Fig. 4 for dimensions. The drain connection to condensate trap must also be properly sloped to an open drain. NOTE: Combustion-air and vent pipes are restricted to a minimum length of 5 ft.
b. Install removed clamp and plug into UPPER collector box drain tube (blue label) which was previously connected to condensate trap. c. Connect LOWER collector box drain tube (blue and white striped label) to condensate trap. Tube does not need to be cut.
6. Determine appropriate length, cut, and connect tube. 7. Clamp tube to relief port connection. E. Condensate Trap Freeze Protection Refer to Condensate Drain Protection section for recommendations and procedures F. Construct a Working Platform Construct working platform where all required furnace clearances are met.
CAUTION: If these furnaces are used during construction when adhesives, sealers, and/or new carpets are being installed, make sure all combustion and circulating air requirements are followed. If operation of furnace is required during construction, use clean outside air for combustion and ventilation.
CAUTION: The furnace can operate in the high-fire mode when certain fault conditions occur. The following precautions should be taken: 1. Size gas piping based on the high-fire input. 2. Check the high-fire input and adjust it per the main literature instructions.
Table 1—Opening Dimensions (in.) FURNACE CASING WIDTH APPLICATION PLENUM OPENING FLOOR OPENING AB C D 17-1/2 Upflow Applications 16 24-1/8 16-5/8 24-3/4 Downflow Applications on Non-Combustible Floo.
NOTE: Remove furnace perforated, supply-air duct flanges when they interfere with mating flanges on coil or downflow subbase. To remove perforated, supply-air duct flanges, use wide duct pliers, duct flange tool, or hand seamers to bend flange back and forth until it breaks off.
CAUTION: The entire length of furnace MUST be supported when furnace is used in a horizontal position to ensure proper draining. When suspended, bottom brace supports sides and center blower shelf. When unit is supported from the ground, blocks or pad should support sides and center blower shelf area.
Maintain a 1-in. clearance from combustible materials to supply air ductwork for a distance of 36 in. horizontally from the furnace. See NFPA 90B or local code for further requirements.
PROCEDURE 5—FILTER ARRANGEMENT WARNING: Never operate unit without a filter or with filter access door removed. Failure to follow this warning can cause fire, personal injury, or death. The air filter arrangement will vary due to application, furnace orientation, and filter type.
Fig. 24—Bottom Filter Arrangement A00290 W ASHABLE FIL TER FIL TER SUPPORT FIL TER RET AINER 17 1 ⁄ 2 -IN. WIDE CASINGS ONL Y : INST ALL FIELD-SUPPLIED FIL TER FILLER STRIP UNDER FIL TER. 1 ″ 24 1 / 2 ″ 3 ″ 21-IN. WIDE CASINGS ONL Y : SUPPORT R ODS (3) EXTEND 1/4" ON EACH SIDE OF FIL TER AND REST ON CASING FLANGE Fig.
Risers must be used to connect to furnace and to meter. Support all gas piping with appropriate straps, hangers, etc. Use a minimum of 1 hanger every 6 ft. Joint compound (pipe dope) should be applied sparingly and only to male threads of joints. Pipe dope must be resistant to propane gas.
NOTE: The gas valve inlet press tap connection is suitable to use as test gage connection providing test pressure DOES NOT exceed maximum 0.5 psig (14-in. wc) stated on gas valve. (See Fig. 56.) Piping should be pressure tested in accordance with NFGC local and national plumbing and gas codes before furnace is attached.
CAUTION: Do not connect aluminum wire between disconnect switch and furnace. Use only copper wire. (See Fig. 28.) WARNING: The furnace casing MUST have an uninterrupted or unbroken ground according to NEC ANSI/NFPA 70-2002 and Canadian Electrical Code CSA C22.
NOTE: If desired, cut butt connectors off factory leads and strip insulation approximately 1/4 in and use field-supplied wire nuts to connect. b. An alternate method to attach EAC lead to control center is the following procedure: (1.) Remove 2 screws securing the control box to furnace blower shelf.
FRS LS ALS FSE GV C M P HI NOTE # 3 3 PL1 PL7 12 1 0 4 6 12 ORN BRN YEL GRN YEL 3 PL9 HSI 12 1.5 AMP EAC1 EAC2 2 1 PL4 1 2 3 7 8 4 5 6 YEL ORN BRN GRN BLU BRN RED 10 11 B2 RED 9 5 PL3 5BLU 4YEL 3VIO 2OR N 1RE D RED ORN VIO YEL WHT BLK RED ORN VIO YEL 9876 432 1 PL10 1 PL11 5 IND .
4. Follow the lighting instructions. Place the appliance being inspected in operation. Adjust thermostat so appliance shall operate continuously. 5. Test for draft hood equipped appliance spillage at the draft hood relief opening after 5 minutes of main burner operation.
NOTE: Furnace combustion-air and vent pipe connections are sized for 2-in. pipe. Any pipe size change should be made outside furnace casing in vertical pipe.
Other gas appliances with their own venting system may also use the abandoned chimney as a raceway providing it is permitted by local code, the current edition of the National Fuel Gas Code and the vent or liner manufacturer’s installation instructions.
Table 6—Approved Combustion-Air and Vent Pipe, Fitting and Cement Materials SPECIFICATION (MARKED ON MATERIAL) MATERIAL PIPE FITTINGS SOLVENT CEMENT AND PRIMERS DESCRIPTION D1527 ABS Pipe — — Sc.
CAUTION: Combustion air must not be taken from inside structure because inside air is frequently contaminated by halogens, which include fluorides, chlorides, bromides, and iodides. These elements are found in aerosols, detergents, bleaches, cleaning solvents, salts, air fresheners, adhesives, paint, and other household products.
NOTE: Do not count elbows or pipe sections in terminations or within furnace. See shaded areas in Fig. 40, 41, 42, 43, and 44. EXAMPLE: An 042080 size furnace located in Indianapolis, elevation 650 ft.
NOTE: A 2-in. diameter pipe must be used within the furnace casing. Make all pipe diameter transitions outside furnace casing. g. Drill a 1/8-in. hole in 2-in. combustion-air pipe using hole in intake housing as a guide. h. Install a field-supplied No.
If use of this drain connection is desired, drill out fitting’s tap plug with a 3/16-in. drill and connect a field-supplied 3/8-in. tube. This tube should be routed to open condensate drain for furnace and A/C (if used), and should be trapped. (See Fig.
d. Be certain that mating surfaces of inducer housing connection, elastomeric coupling, and 2-in. diameter vent pipe are clean and dry. Assemble the elastomeric (rubber) vent coupling (with 2 loose clamps) onto inducer housing connection. Insert the 2-in.
Fig. 40—Concentric Vent and Combustion-Air RoofTermination (Preferred) A93054 COMBUSTION AIR MAINTAIN 12 IN. (305 mm). (18 IN. (457 mm) FOR CANADA) MINIMUM CLEARANCE ABOVE HIGHEST ANTICIPATED SNOW LEVEL. MAXIMUM OF 24 IN. (610 mm) ABOVE ROOF. VENT Fig.
NOTE: Shaded parts in Fig. 39, 40, 41, 42, and 43 are considered to be termination. These components should NOT be counted when determining pipe diameter. Roof termination is preferred since it is less susceptible to damage, has reduced chances to take in contaminants, and has less visible vent vapors.
b. Termination kit should be positioned where vent vapors will not damage plants/shrubs or air conditioning equipment. c. Termination kit should be positioned so it will not be affected by wind eddy (such as inside building comers) or that may allow recirculation of flue gases, airborne leaves, or light snow.
An external trap is not required when connecting the field drain to this condensate trap. The field drain connection (condensate trap or drain tube coupling) is sized for l/2-in. CPVC, 1/2-in. PVC, or 5/8-in. ID tube connection. Drain pipe and fittings must conform to ANSI standards and ASTM D1785, D2466 or D2846.
Fig. 46—Concentric Vent and Combustion-Air Side Termination (Dimension “A” is Touching or 2-in. Maximum Separation) A93057 COMBUSTION AIR VENT A VENT 1 ″ (25 mm) MAXIMUM (TYP) Fig. 47—Sidewall Termination of 12 in. or Less (Dimension “A” is Touching or 2-in.
1. Fold heat tape in half and wrap on itself 3 times. 2. Locate heat tape between sides of condensate trap back. (See Fig. 50.) 3. Use wire ties to secure heat tape in place. Wire ties can be positioned in notches of condensate trap sides. (See Fig. 50.
PROCEDURE 1—SELF-TEST MODE The control center goes through a brief self-test whenever 115-v or 24-v power is interrupted. The self-test takes approximately 2 sec to complete. After power is restored, red (microprocessor) LED briefly comes on. Then green LED comes on for 1 sec, followed by 1 sec where both yellow and green LEDs are on.
2. Blower on —The blower motor is turned on IMMEDIATELY and slowly increases to maximum speed as soon as a call for heat is received. No blower calibration occurs. 3. Electronic Air Cleaner —The EAC-1 terminal does not operate in emergency heat mode.
8. Electronic Air Cleaner —The EAC-1 terminal is energized whenever blower operates. 9. Inducer speed operation —If cycle starts in low heat, inducer speed reduces slightly after the flame sense. If cycle starts in high heat, inducer speed increases 15 sec after flame sense.
1. Leave 115-v power to furnace turned on. 2. Remove main furnace door. 3. Remove blower access panel. 4. Move setup switch SW-6 to ON position. 5. Manually close blower access panel door switch. Use a piece of tape to hold switch closed. WARNING: Blower access panel door switch opens 115-v power to control center.
The DEHUM output on the thermidistat control or the humidistat output, is connected directly to the DEHUM terminal on the furnace control. In addition, the DE jumper located next to the DEHUM terminal must be removed to enable the DEHUM input (See Fig.
NOTE: The CF switches are factory set to provide continuous fan airflow equal to low-heat mode. 5. Replace main furnace door and blower access panel. C. Setup Switches (SW) The control center has 8 setup switches that may be set to meet the application requirements.
2. Locate setup switches on control center. (See Fig. 31.) 3. See Table 11 for setup switch description. (See Fig. 30.) 4. Replace main furnace door and blower access panel. NOTE: If a bypass humidifier is used, setup switch SW-3 (BPH) should be in ON position.
Furnace input rate must be within ±2 percent of input on furnace rating plate. 1. Determine natural gas orifice size and manifold pressure for correct input. a. Obtain yearly heat value average (at installed altitude) from local gas supplier. b. Obtain yearly specific gravity average from local gas supplier.
NOTE: DO NOT set low-heat manifold pressure less than 1.3-in. wc or more than 1.7-in. wc for natural gas. If manifold pressure is outside this range, change main burner orifices. CAUTION: DO NOT bottom out gas valve regulator adjusting screw. This can result in unregulated manifold pressure and result in excess overfire and heat exchanger failures.
j. Remove jumpers R to W/W1 and R to W2. 3. Verify natural gas input rate by clocking gas meter. NOTE: Be sure all pressure tubing, combustion-air and vent pipes, and burner enclosure front are in place when checking input by clocking gas meter. a. Calculate high-altitude adjustment (if required).
CANADA At installation altitudes from 2000 to 4500 ft, this furnace must be derated 5 percent by an authorized Gas Conversion Station or Dealer. To determine correct input rate for altitude, see example above and use 0.95 as derate multiplier factor. b.
m. Move setup switch SW-2 to OFF position and jumper R and W2 thermostat connections. (See Fig. 31.) This keeps furnace locked in high-heat operation. Repeat items h through k for high-heat operation. EXAMPLE: (High-heat operation at 0-2000 ft altitude) Furnace input from rating plate is 100,000 Btuh.
Furnace must operate within the temperature rise ranges specified on the furnace rating plate. Determine the air temperature as follows: 1. Place thermometers in return and supply ducts as close to furnace as possible. Be sure thermometers do not ’see’ heat exchangers so that radiant heat does not affect thermometer readings.
2. See thermostat manufacturer’s instructions for adjusting the heat anticipator and for varying heating cycle length. NOTE: When using an electronic thermostat, set cycle rate for 3 cycles per hr. 3. Return setup switch SW-2 to OFF position and replace thermostat on subbase.
3. Turn on 115-v power to furnace. 4. Set thermostat to call for heat. When pressure switches are functioning properly, fault code 42 will flash on control center approximately 10 sec after thermostat switch is closed. If either a fault code 31 or 32 is flashed when ICM inducer motor is disconnected, the furnace will shut itself down immediately.
CHECKLIST—INSTALLATION Load Calculation Condensate Drain _______ _______ _______ Heating Load (Btuh) Cooling Load (Btuh) Furnace Model Selection _______ _______ _______ _______ _______ Unit Level or.
© 2002 CAC/BDP 7310 W. Morris St., Indianapolis, IN 46231 355m4011 —60— Book/Tab: 1/6 Catalog No. 5335-518.
An important point after buying a device Bryant 355MAV (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Bryant 355MAV yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Bryant 355MAV - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Bryant 355MAV you will learn all the available features of the product, as well as information on its operation. The information that you get Bryant 355MAV will certainly help you make a decision on the purchase.
If you already are a holder of Bryant 355MAV, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Bryant 355MAV.
However, one of the most important roles played by the user manual is to help in solving problems with Bryant 355MAV. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Bryant 355MAV along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center