Installation and Operation Instructions Document 1243 H2343100- W ARNING If the information in this manual is not followed exactly , a fire or explosion may result causing property damage, personal injury or loss of life. Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
B RADFORD W HITE C ORP. Page 2 T ABLE OF CONTENTS SECTION 1. General Information 1.1 Introduction ...................................................... 4 1.2 Model Identification ......................................... 4 1.3 Appliance Overview ....
Brute Elite Page 3 SECTION 9. Modes of Operation 9.1 Hydronic Heating Demand ............................ 4 0 9.2 Hydronic Heating with Outdoor Reset ........... 40 9.3 Hydronic Heating with Domestic Hot Water (DHW) Priority ..........................
B RADFORD W HITE C ORP. Page 4 SECTION 1. General Information WARNING Brute Elite units must be installed in accordance with the procedures detailed in this manual, or the Bradford White warranty will be voided.
Brute Elite Page 5 Figure 1. Location of Components, Sizes 80–105. Figure 2. Location of Components, Sizes 150-210..
B RADFORD W HITE C ORP. Page 6 Figure 4. Location of Components, Size 399. Figure 3. Location of Components, Size 285..
Brute Elite Page 7 Figure 6. Location of Components, Size 600. Figure 5. Location of Components, Size 500..
B RADFORD W HITE C ORP. Page 8 Figure 7. Location of Components, Sizes 750 and 850..
Brute Elite Page 9 Figure 8. Contents of Shipping Package. 1.3 Appliance Overview See Figures 1 through 7 . 1.4 Warranty Bradford White’s Brute Elite appliances are covered by a limited warranty. All warranty claims must be made to an authorized Bradford White representative.
B RADFORD W HITE C ORP. Page 10 Figure 9. Dimensional Drawing, Sizes 80-500. Dimensions are nominal and are shown in inches , cm . * Brute Elite is shipped with adapters for the air and vent that accept standard pipe of the proper size and type.
Brute Elite Page 11 SECTION 2. Locating the Appliance 2.1 Locating the Appliance Brute Elite is for indoor installations only. The appliance should be located to provide clearances on all sides for maintenance and inspection.
B RADFORD W HITE C ORP. Page 12 HORIZONTAL INTAKE AND EXHAUST PVC VENT TERMINAL KITS 2" PVC 3" PVC 4" PVC 6" PVC SIZE Standard Concentric Standard Concentric Standard Standard CA00.
Brute Elite Page 13 INSTALLATION STANDARDS MATERIAL UNITED STATES CANADA Stainless Steel UL 1738 Venting must be ULC-S636 certified for use as PVC, sch 40 ANSI/ASTM D178 venting material. The venting material must be chosen CPVC, sch 40 ANSI/ASTM F441 based upon the intended application of the boiler.
B RADFORD W HITE C ORP. Page 14 units unless the vent system meets this requirement. Brute Elite units are never permitted to share a vent with Category I appliances. A condensate drain trap is built into Brute Elite. Connect a 3/4" PVC pipe between the drain connection and a floor drain (or condensate pump if a floor drain is not accessible).
Brute Elite Page 15 1. Figure 12 shows the requirements for mechanical vent terminal clearances for the U.S. and Canada. 2. Vent terminals for condensing appliances or appliances with condensing vents are not permitted to terminate above a public walkway, or over an area where condensate or vapor could create a nuisance or hazard.
B RADFORD W HITE C ORP. Page 16 *When vent terminal is less than 10 feet (3m) horizontally from a forced air inlet, the terminal must be at least 3 feet (0.
Brute Elite Page 17 provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm be installed. 2. Approved Carbon Monoxide Detectors Each carbon monoxide detector shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
B RADFORD W HITE C ORP. Page 18 SECTION 4. Gas Supply and Piping 4.1 Gas Supply and Piping Gas piping should be supported by suitable hangers or floor stands, not the appliance. Review the following instructions before proceeding with the installation.
Brute Elite Page 19 SCHED 40 METAL PIPE CAPACITY FOR 1.50 SPECIFIC GRAVITY UNDILUTED PROPANE NOMINAL PIPE SIZE @ 11" W.C. INLET AND 0.5" W.C.
B RADFORD W HITE C ORP. Page 20 Brute Elite's efficiency is higher with lower return water temperatures. Therefore, to get the most of low return temperature with multiple boilers, pipe as shown in Figures 17-19 . Brute Elite BNTH models can be ordered with or without a pump included.
Brute Elite Page 21 6A.3 Freeze Protection WARNING Glycol must not be used in domestic hot water applications. Refer to Section 6B.4 for instructions on BNTV, domestic hot water freeze protection. Brute Elite units are certified for indoor use only, and are not design-certified for placement outdoors.
B RADFORD W HITE C ORP. Page 22 Figure 15. Hydronic Piping — Single Boiler (zoning with circulators)..
Brute Elite Page 23 Figure 16. Hydronic Piping — Single Boiler, Low Temp Radiant Space Heating using Low Loss Header and Zone Valves..
B RADFORD W HITE C ORP. Page 24 Figure 17. Hydronic Piping — Multiple Boilers (zoning with circulators)..
Brute Elite Page 25 Figure 18. Hydronic Piping — Multiple Boilers with Indirect DWH Tank Piped from System Loop..
B RADFORD W HITE C ORP. Page 26 Figure 19. Hydronic Piping — Multiple Boilers, Reverse Return, Multi-Temp Zones (zoning with circulators)..
Brute Elite Page 27 Figure 20. Hydronic Piping — Heating zones with indirect DWH tank piped with zone pumps (indirect directly off boiler). Boiler pump must shut down during DHW.
B RADFORD W HITE C ORP. Page 28 Figure 21. Hydronic Piping, multiple boilers with indirect DWH off one boiler. Boiler pump must shut-down during DHW..
Brute Elite Page 29 6B.2 Piping Requirements Water piping should be supported by suitable hangers and floor stands. Do not support piping with the appliance. Due to expansion and contraction of copper pipe, consideration should be given to the type of hangers and supports used.
B RADFORD W HITE C ORP. Page 30 6B.3 Cold Water Make-Up The cold water make-up may be connected to the tank or to the inlet of the boiler as shown in Figures 23- 26.
Brute Elite Page 31 Figure 25. DHW Piping, Two Heaters, One Vertical Tank. Figure 26. DHW Piping, Two Heaters, Two Vertical Tanks. NOTES: 1. Optional CWMU & Recirc. line location. 2. Locate BNTV DHW sensor or remote aquastat well in lower 1/3 of tank.
B RADFORD W HITE C ORP. Page 32 SECTION 7. Electrical Connections WARNING The appliance must be electrically grounded in accordance with the requirements of the authority having jurisdiction or, in the absence of such requirements, with the latest edition of the National Electrical Code, ANSI/NFPA 70, in the U.
Brute Elite Page 33 7.2 Pump Connections Brute Elite energizes the pump contacts upon a call for heat. Once the call for heat is satisfied the pump will remain on for the defined pump overrun time. NOTE: System and DHW contacts are dry contacts. Appropriate voltage must be supplied to the System and DHW pumps for proper operation.
B RADFORD W HITE C ORP. Page 34 Figure 28. Lead-Lag / Cascading Wiring Connections..
Brute Elite Page 35 Figure 29. Ladder Diagram. 7.11 Wiring Diagrams (see Figures 29 and 30) Caution Label all wires prior to disconnection when servicing controls.
B RADFORD W HITE C ORP. Page 36 Figure 30. Wiring Diagram (all sizes)..
Brute Elite Page 37 SECTION 8. Brute Elite Control Setup and Operation The Brute Elite control is an integrated electronic control that replaces many of the individual components found on older appliances.
B RADFORD W HITE C ORP. Page 38 4. Prepurge timer is started once the prepurge RPM is achieved. 5. Pre ignition time of 2 seconds to check the flame sensor operation and status. During this period an intermittent spark can be seen. 6. Trial for ignition period, 4 seconds.
Brute Elite Page 39 NAME FUNCTION VALUE CH on Burner demand begins when the 5°F differential outlet water temperature reaches "Outlet water temperature setpoint" minus "CH on different.
B RADFORD W HITE C ORP. Page 40 SECTION 9. Modes of Operation The Brute Elite control allows the boiler to operate in many different modes of operation. The mode must be selected based upon the requirements of the installation. The following sections describe the basic operation of the Brute Elite in each of the different modes.
Brute Elite Page 41 setpoint is used to limit the maximum water temperature leaving the boiler only. The modulation rate is controlled by a 4-20mA (0-10Vdc using converter) signal supplied by an external control.
B RADFORD W HITE C ORP. Page 42 firing rate is controlled by the DHW setpoint temperature and the water temperature at the heat exchanger outlet. Once the DHW call is supplied the control starts the boiler and DHW pumps and begins the ignition process.
Brute Elite Page 43 13. Check gauge for correct water pressure and also check water level in the system. If the height indicated above the boiler insures that water is at the highest point in the circulating loop, then the system is ready for operation.
B RADFORD W HITE C ORP. Page 44 in Table 16 . If the CO 2 is not within the range shown, adjustments may be made. To adjust the low fire CO 2 , locate the low fire adjuster screw according to the appropriate figure. Slowly make adjustments in 1/16 of a revolution increments until the CO 2 is within the range identified.
Brute Elite Page 45 Figure 33B. Brute Elite Gas Valves (600, 750 and 850). 600 750, 850 Figure 33A. Brute Elite Gas Valves (285, 399 and 500). 80–285 500 399.
B RADFORD W HITE C ORP. Page 46 SECTION 1 1. Maintenance WARNING Disconnect all power to the appliance before attempting any service to the appliance. Contact with electricity can result in severe injury or death. 11.1 System Maintenance (yearly, unless otherwise noted) 1.
Brute Elite Page 47 appliance and shut off all manual gas valves to the appliance. Remove the front door to the appliance and the control panel plastic bezel.
B RADFORD W HITE C ORP. Page 48 11.2.6 Transformer with Integral Circuit Breaker The appliance has a 24Vac transformer with integral 4 amp circuit breaker installed for supplying the control voltage required for the appliance only.
Brute Elite Page 49 SECTION 12. T rouble Shooting 12.1 Sequence of Operation Brute Elite is a cold start appliance that should start only on a call for heat from a tank aquastat, room thermostat, zone valve end switch or other space temperature control device.
B RADFORD W HITE C ORP. Page 50 CODE# PROBLEM PROBABLE CAUSE SOLUTION COMMON LOCKOUT CODES 27 Internal error Flame rod to ground Check wiring / probe grounded, dirty probe 47 Flame rod to ground leaka.
Brute Elite Page 51 49 Maximum cycle count Control operates correctly, was reached however the cycle count will not increment any higher than 999,999 cycles Replace controller or adjust the count usin.
B RADFORD W HITE C ORP. Page 52 13.2 Parts List SIZE SIZE SIZE SIZE SIZE SIZE SIZE SIZE SIZE SIZE ITEM DESCRIPTION BNTH 80 BNTH 105 BNTH 150 BNTH 210 BNTH 285 BNTH 399 BNTH 500 BNTH 600 BNTH 750 BNTH .
Brute Elite Page 53 SIZE SIZE SIZE SIZE SIZE SIZE SIZE SIZE SIZE SIZE ITEM DESCRIPTION BNTH 80 BNTH 105 BNTH 150 BNTH 210 BNTH 285 BNTH 399 BNTH 500 BNTH 600 BNTH 750 BNTH 850 BNTV 150 BNTV 199 BNTV 2.
B RADFORD W HITE C ORP. Page 54 SIZE SIZE SIZE SIZE SIZE SIZE SIZE SIZE SIZE SIZE ITEM DESCRIPTION BNTH 80 BNTH 105 BNTH 150 BNTH 210 BNTH 285 BNTH 399 BNTH 500 BNTH 600 BNTH 750 BNTH 850 BNTV 150 BNT.
Brute Elite Page 55 SIZE SIZE SIZE SIZE SIZE SIZE SIZE SIZE SIZE SIZE ITEM DESCRIPTION BNTH 80 BNTH 105 BNTH 150 BNTH 210 BNTH 285 BNTH 399 BNTH 500 BNTH 600 BNTH 750 BNTH 850 BNTV 150 BNTV 199 BNTV 2.
B RADFORD W HITE C ORP. Page 56 Figure 35. Jacket Components..
Brute Elite Page 57 Figure 36A. Internal Components, Sizes 80–210. Figure 36B. Internal Components, Sizes 285–600..
B RADFORD W HITE C ORP. Page 58 Figure 36C. Internal Components, Sizes 750-850..
Brute Elite Page 59 Figure 37A. Gas Train Components, Sizes 80-500..
B RADFORD W HITE C ORP. Page 60 Figure 37B. Gas Train Components, Sizes 600-850..
Brute Elite Page 61 Figure 38. Heat Exchanger Components..
B RADFORD W HITE C ORP. Page 62 Figure 39. Electrical Components..
Brute Elite Page 63.
H2343100- Dimensions and specifications subject to change without notice in accordance with our policy of continuous product improvement. Ambler , P A 19002 T ech. Service (800) 334-3393 Service Parts (800) 538-2020 www.BradfordWhite.com W arranty Service (800) 531-21 1 1 Litho in U.
An important point after buying a device Bradford-White Corp BNTV (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Bradford-White Corp BNTV yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Bradford-White Corp BNTV - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Bradford-White Corp BNTV you will learn all the available features of the product, as well as information on its operation. The information that you get Bradford-White Corp BNTV will certainly help you make a decision on the purchase.
If you already are a holder of Bradford-White Corp BNTV, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Bradford-White Corp BNTV.
However, one of the most important roles played by the user manual is to help in solving problems with Bradford-White Corp BNTV. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Bradford-White Corp BNTV along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center