Instruction/ maintenance manual of the product GL-E223-ADOC 0311 Weil-McLain
Go to page of 44
Part number GL-E223-ADOC 0311 This manual must only be used b y a qualified heating installer/serv ice tec hnician. BEFORE installing , read all instruc- tions in this manual and all other information shipped with the water heat er . P erform st eps in the order giv en.
AQUA PLUS indirect - fired w a ter hea ters — Pr oduct Manual Contents Please read before pr oceeding 3 W hen serv icing water heater . . . . . . . . . . . . . . . . . . . . 3 Operating restric tions . . . . . . . . . . . . . . . . . . . . . . . . 3 Boiler water r estric tions .
AQUA PLUS indirect - fired w a ter hea ters — Pr oduct Manual Please r ead befor e pr oceeding Failur e to adher e to the guidelines on this page can res ult in sever e personal injur y , death or substantia l property damage. R ead all inst ructio ns befor e insta lling.
AQUA PLUS indirect - fired w a ter hea ters — Pr oduct Manual Pr e-installation Figure 1 Clearance recommendations Codes 1. Installation must co nform w ith instructions in this manual and, where applicable: • local, stat e, pro vincial, and national codes, la ws, regulations and ordinanc es.
AQUA PLUS indirect - fired w a ter hea ters — Pr oduct Manual Pr e-installation (conti nued ) Hot W ater Can Scald! • W ater heated to te mperature for clothes washing, dish washing and other sanitizing needs can scald and cause permanent injur y .
AQUA PLUS indirect - fired w a ter hea ters — Pr oduct Manual Domestic water piping Figure 2 DHW piping Piping overview THERMAL EXP ANSION T ANK — If a backflow prev enter , check valv e, or pres.
AQUA PLUS indirect - fired w a ter hea ters — Pr oduct Manual Domestic water piping (conti nued ) LEGEND for Figure 2, page 6 Domestic water supplied to fixtures that could pose an injur y hazard d.
AQUA PLUS indirect - fired w a ter hea ters — Pr oduct Manual Recir culation Mas sac hus ett s cod e app lica tio ns re qui re reci rc u- lation piping or heat-traced piping if the distance fr om the wat er heat er to the furth est fixtur e ex cee ds 100 feet.
AQUA PLUS indirect - fired w a ter hea ters — Pr oduct Manual Recir culation (conti nued ) Figure 4 Time lag to obtain hot water at fixture for branch lengths of 10 and 25 feet (ASPE Domestic W ater Heating Design Manual) Time in seconds required to get hot water at fixture (from ASPE) Fixture flow rate (GPM) - 0.
AQUA PLUS indirect - fired w a ter hea ters — Pr oduct Manual Recir culation (conti nued ) Components Circulator (Figure 6, item 1) 1. Little flow is required to maintain a temperature in the piping. 2. Size of circulator depends on minimum flow re- quirements of the tempering valve.
AQUA PLUS indirect - fired w a ter hea ters — Pr oduct Manual Figure 7 Zoning with circulators — dir ect-connected system piping Notes • Place circulat ors at beg in- n i ng s o f z o n es . P l a c i n g them at the ends of zones coul d result in heating idle zones.
AQUA PLUS indirect - fired w a ter hea ters — Pr oduct Manual Boiler-side piping (conti nued ) Figure 8 Zoning with circulators — primary/secondary system piping Notes • Place circulato rs at beg in- n i ng s o f z o n es . P l a c i n g them at the ends of zones coul d result in heating idle zones.
AQUA PLUS indirect - fired w a ter hea ters — Pr oduct Manual Boiler-side piping (conti nued ) Figure 9 Zoning with zone valves — direct-connected system piping Notes • Place circulat ors at beg in- n i ng s o f z o n es . P l a c i n g them at the ends of zones coul d result in heating idle zones.
AQUA PLUS indirect - fired w a ter hea ters — Pr oduct Manual Boiler-side piping (conti nued ) Figure 10 Zoning with zone valves — primary/secondar y system piping Notes • Place circulato rs at beg in- n i ng s o f z o n es . P l a c i n g them at the ends of zones coul d result in heating idle zones.
AQUA PLUS indirect - fired w a ter hea ters — Pr oduct Manual Boiler-side piping (conti nued ) Figure 11 Dedicated single-boiler piping Notes • Place circulat ors at beg in- n i ng s o f z o n es . P l a c i n g them at the ends of zones coul d result in heating idle zones.
AQUA PLUS indirect - fired w a ter hea ters — Pr oduct Manual Boiler-side piping (conti nued ) Figure 12 Multiple water heaters — domestic water piping Figure 13 Alternate methods of revers-return.
AQUA PLUS indirect - fired w a ter hea ters — Pr oduct Manual Boiler-side piping (conti nued ) Figure 14 Multiple water heaters and dedicated multiple boilers — boiler water piping Notes • See lege nd a nd detail s i n Figure 12, page 16. 1. This drawin g is co nce ptua l only .
AQUA PLUS indirect - fired w a ter hea ters — Pr oduct Manual Connecting to a low-pr essur e steam boiler Special considerations W hen designi ng steam and dome stic hot wate r systems , there are some key issues that m ust be take n int o c onsideration d uring the initial de- sign phase.
AQUA PLUS indirect - fired w a ter hea ters — Pr oduct Manual Connecting to a low-pr essur e steam boiler (cont inued ) Figure 16 Low pressur e steam boiler application — Domestic water heating us.
AQUA PLUS indirect - fired w a ter hea ters — Pr oduct Manual Boiler-side wiring and contr ols Electrical shock hazard — Can cause severe personal inj ury , death or sub sta ntia l pr ope rty damag e. Dis co nnec t power befo re installing and / or serv icing.
AQUA PLUS indirect - fired w a ter hea ters — Pr oduct Manual Wiring — zoning with cir culators Notes • Also refer to th e WMC R manual and W e il-McLain Boiler Zone W iring Guide for further details. • Refe r to Wir in g re qu ir e- ments on page 20.
AQUA PLUS indirect - fired w a ter hea ters — Pr oduct Manual Wiring — zoning with zone valves Notes • Also ref er to the W MZV manual and W e il-McLain Boiler Zone W iring Guide for further details. • Refe r to Wir in g re qu ir e- ments on page 20.
AQUA PLUS indirect - fired w a ter hea ters — Pr oduct Manual W ater heater filling and star t-up The i nst al lat ion a nd wa ter che mist r y m ust m eet the requir ements below . Failure t o comply could result in damage to the water heater , causing possible severe personal injury , death or substantial pr opert y damage.
AQUA PLUS indirect - fired w a ter hea ters — Pr oduct Manual Hot W ater Can Scald! • W ater heated to te mperature for clothes washing, dish washing and other sanitizing needs can scald and cause permanent injur y .
AQUA PLUS indirect - fired w a ter hea ters — Pr oduct Manual W ater heater maintenance Boiler water — r ead and comply with all r equire ments under “Boiler water r estric tions, ” page 3. W ater from opened drain valves, unions and other connec- tions ma y be extr emely hot.
AQUA PLUS indirect - fired w a ter hea ters — Pr oduct Manual W ater heater maintenance (conti nued ) and their frequencies, including any not listed in the following paragr aphs.
AQUA PLUS indirect - fired w a ter hea ters — Pr oduct Manual T r oubleshooting Preparation for tr oubleshooting T ools needed Electr ical meter to measur e voltage and c ontinuity . Press ure gauge (such as W atts #276H300 test gauge). T emper ature gauge.
AQUA PLUS indirect - fired w a ter hea ters — Pr oduct Manual T r oubleshooting (conti nued ) Insufficient hot water 1 Und ersized water heate r? 2 Boiler system improperly siz ed? 3 Check component parts. 4 Check boiler operating tempera- tures. 5 Check location of flow contr ol devices.
AQUA PLUS indirect - fired w a ter hea ters — Pr oduct Manual T r oubleshooting (conti nued ) 1 Undersized water heater? • There are many methods of sizing various applicatio ns, i.e. ASHRAE sizing tables or ASPE domestic water heating design manual.
AQUA PLUS indirect - fired w a ter hea ters — Pr oduct Manual T r oubleshooting (conti nued ) • Is the cir culator between the boiler and the water heater properly sized to p rovide enough flow f.
AQUA PLUS indirect - fired w a ter hea ters — Pr oduct Manual T r oubleshooting (conti nued ) 4 Check boiler operating temperatures. • If possible, increase the boiler o perating temperature to 180°F or 200°F . • Maintain a minimal t emperature in the boiler during non-heating seasons.
AQUA PLUS indirect - fired w a ter hea ters — Pr oduct Manual T r oubleshooting (conti nued ) Excessive domestic water temperatur e 1 Reduce stacking.
AQUA PLUS indirect - fired w a ter hea ters — Pr oduct Manual T r oubleshooting (conti nued ) Boiler r elief valve lifting or weeping 1 Undersized expansion tank? • Insufficient allo wance for expansion on the boiler sid e can cause the boiler pressur e relief valv e to lift.
AQUA PLUS indirect - fired w a ter hea ters — Pr oduct Manual T r oubleshooting (conti nued ) T emperature/pr essur e relief valve lifting or weeping 1 Undersized or missing domestic water side expa.
AQUA PLUS indirect - fired w a ter hea ters — Pr oduct Manual T r oubleshooting (conti nued ) W ater on the floor near the tank 1 Check for leaks from sour ces other than the water heater . • Check for possible water seepag e through foundation cracks.
AQUA PLUS indirect - fired w a ter hea ters — Pr oduct Manual T r oubleshooting (conti nued ) Rapid decay of magnesium anode 1 Anodes last less than two years The purpose of the magnesium anode is to reduc e the damaging effects of agg ressiv e water on the water heater .
AQUA PLUS indirect - fired w a ter hea ters — Pr oduct Manual W ater quality problems 1 W ater smells like “r otten eggs.” • The most common cause of water to smell like “rotten eggs ” is a non-toxic sulfat e reducing bacteria.
AQUA PLUS indirect - fired w a ter hea ters — Pr oduct Manual • This is similar to the reaction that occurs as air bubbles form on the walls of a pan shortly befor e the water begins to boil. • The release of dissolved gas can also create air pockets and air locks in the water system piping.
AQUA PLUS indirect - fired w a ter hea ters — Pr oduct Manual Item Description Size/Model A QU A PLUS W eil-McLain Part Number 1 Magnesium anode replacement kit (includes anode, o-ring, insulating w.
AQUA PLUS indirect - fired w a ter hea ters — Pr oduct Manual AHRI ratings Model A QU A PLUS AHRI certified ratings 180°F boiler water entering | 58°F to 135°F domestic water First Hour Rating C.
AQUA PLUS indirect - fired w a ter hea ters — Pr oduct Manual Ratings with 200°F boiler supply water For water heater to achieve the rated performance below : Boiler water must be supplied t o the water heater at 200°F , and the boiler water flow rate must be no less than giv en in the tables below .
AQUA PLUS indirect - fired w a ter hea ters — Pr oduct Manual Ratings with 190°F boiler supply water For water heater to achieve the rated performance below: Boiler water must be supplied to the water heater at at least 190°F , and the boile r water flow rate m ust be no less than given in the tables below .
AQUA PLUS indirect - fired w a ter hea ters — Pr oduct Manual Ratings with 180°F boiler supply water For water heater to achieve the rated performance below: Boiler water must be supplied to the water heater at at least 180°F , and the boile r water flow rate m ust be no less than given in the tables below .
AQUA PLUS indirect - fired w a ter hea ters — Pr oduct Manual Dimensions Figure 25 Dimensions and ratings — AQUA PLUS indirect-fir ed water heaters Model A QU A PLUS Storage Connections Dimensions (inches) Ship. weight (approx.) DHW side Boiler side DHW In/Out & Recirc.
An important point after buying a device Weil-McLain GL-E223-ADOC 0311 (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Weil-McLain GL-E223-ADOC 0311 yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Weil-McLain GL-E223-ADOC 0311 - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Weil-McLain GL-E223-ADOC 0311 you will learn all the available features of the product, as well as information on its operation. The information that you get Weil-McLain GL-E223-ADOC 0311 will certainly help you make a decision on the purchase.
If you already are a holder of Weil-McLain GL-E223-ADOC 0311, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Weil-McLain GL-E223-ADOC 0311.
However, one of the most important roles played by the user manual is to help in solving problems with Weil-McLain GL-E223-ADOC 0311. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Weil-McLain GL-E223-ADOC 0311 along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center