Instruction/ maintenance manual of the product SU20KX Tripp Lite
Go to page of 60
1 5 9 3 7 11 2 6 10 4 8 12 13 14 Owner’ s Man ual PR O TEC T Y O UR INVESTMENT! Comp lete d an d sig ned start-up f orms MUST be subm itted and app rov ed by T ripp Lite to activate y our warranty .
1 5 9 3 7 11 2 6 10 4 8 12 13 14 2 T able of Contents 1 Introduction 3 2 Important Safety Instructions 4 3 Control P anel Features 6 4 Front and Rear P anel Features 7 5 Cabinet Installation 9 5-1 Pre.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 3 1 – Intr oduction T ripp Lite’ s SmartOnline 3-Phase UPS Systems (Models SU20KX, SU40KX, SU60KX and SU80KX) are ideal for backing up and protecting data centers, telecommunications (V oIP), networks, industrial facilities, security/emer gency systems and more.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 4 2 – Impor tant Saf ety Instructions SA VE THESE INSTRUCTIONS All sections of this manual contains instructions and warnings that should be follo wed during the installation and operation of the UPS systems described in this manual.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 5 2 – Impor tant Saf ety Instructions Battery W arnings The UPS system does not require routine maintenance. There are no user -serviceable parts inside. Only qualified service personnel should open • the access panels for any reason.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 A E F G H I J K B C D 6 3 – Contr ol P anel Features “NORMAL” LED: • This green light illuminates to indicate that the UPS system is in online (normal) mode. The primary AC input supply is present and within standard operating parameters.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 A B C D H H I I G E F 7 4 – Fr ont and Rear P anel Features Note: Individual models may vary fr om diagr ams. Unit shown with fr ont bezels r emoved. Control P anel: • The control panel allo ws the operator to monitor and control the UPS system.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 H L H P O N M J K I I 8 Note: Individual models may vary fr om diagr ams. Unit shown with fr ont bezels r emoved. Levelers: • The le velers pro vide long-term support for the UPS system.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 1 4 3 2 5 9 5 – Cabinet Installation Read Section 2 – Impor tant Safety Instructions Bef ore Installation 5-1 Preparation The UPS system must be installed in a str.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 1 2 3 4 50 cm (19.7”) 50 cm (19.7”) 100 cm (39.4”) A B 10 5 – Cabinet Installation (continued) 5-3 Placement Use the casters to mov e the UPS system for a short distance over • a lev el, smooth, stable surface.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 VBoar d W1: RED, W2: BLUE, W3: WHITE, W4: BLACK 12V , 9AH, 10PCS 12V , 9AH, 10PCS 12V , 9AH, 10PCS 12V , 9AH, 10PCS RED RED RED RED BLACK BLA CK BLACK BLA CK RED RED R.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 UPS System Batter y Back Connec to r UPS System Batter y Back Connec to r Fuse Block Bracket 12 6 – Internal Battery Connection (continued) SU40KX shown 6-1 Internal.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 1 2 3 4 5 13 6 – Internal Battery Connection (continued) 6-2 Internal Battery Connection Procedure Place the UPS system in bypass (or turn it completely off) and turn • off the internal battery circuit break er switch, located on the rear of the UPS system.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 7 6 8 9 10 TERMINALS TERMINALS SIDE VIEW SIDE VIEW 14 6-2 Internal Battery Connection Procedure (continued) Slide a battery string with a red cable into an empty slot within • the battery compartment. Make sure the battery string is oriented as shown in the diagram.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 11 13 14 240 12 15 6 – Internal Battery Connection (continued) 6-2 Internal Battery Connection Procedure (continued) Use a voltmeter (user -supplied) to test the voltage of each internal • battery pack.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 16 7 – Wiring D ANGER! LETHAL HIGH V OL T A GE HAZARD! All wiring should be performed by a qualified electrician, in accordance with the w arnings in this manual and all applicable electrical and safety codes.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 Main Input Grounding T erminals R R R S S S T T T N N N + – N Output Bypass Input External Battery Connection + – + – External Battery Cabinet Breaker Switch 17 .
1 5 9 3 7 11 2 6 10 4 8 12 13 14 TO EXTERNAL BA TTERY CABINET 18 7 – Wiring (continued) 7-4 External Battery Cabinet Wiring Diagrams (continued) 7-5 Electrical and Cable Data Input, Bypass Input, Re.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 1 2 4 3 6 5 + – + – + – A A B B A 19 7 – Wiring (continued) 7-6 External Battery Cabinet Wiring W arning: External battery cabinets v ary . Read the external battery cabinet’ s documentation bef ore attempting to connect it to the UPS system.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 1 2 4 5 3 A B + – + – R S T N R S T N R S T N Q4 Q2 Q1 Q3 20 7 – Wiring (continued) 7-7 A C Input/Output Wiring (Single UPS) After de-energizing all input and output (A C and DC) of the UPS • system, remov e the terminal block cover from the UPS system.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 2 2 1 1 B B A B B A 21 7 – Wiring (continued) 7-8 A C Input/Output Wiring (P arallel UPS – Single Input Source) Parallel UPS W arnings: The total input cable length must be equal to the total • output cable length in order to pre vent unbalanced load sharing between two UPS systems under r eserve mode (i.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 22 8 – Operating Modes This section provides a basic description of the UPS system’ s operating modes. For more information about switching between operating modes, refer to Section 9 – Start-Up, Shutdown and Bypass .
1 5 9 3 7 11 2 6 10 4 8 12 13 14 23 8 – Operating Modes (continued) 8-5 Online Mode (P arallel UPS) Parallel redundanc y (1+1) provides UPS system redundancy or increased total capacity . Under parallel redundancy , the total load is shared by two UPS systems.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 24 8 – Operating Modes (continued) 8-8 Manual Bypass Mode (P arallel UPS) Similar to manual bypass mode for a single UPS system ( Section 8-4 ), except with parallel (1+1) UPS systems. Note: Both UPS systems must be switched into manual bypass mode .
1 5 9 3 7 11 2 6 10 4 8 12 13 14 Contr ol P anel Cir cuit Br eaker Switc hes (UPS System F ront P anel) 1 1 2 2 A E F G K A B C D H I J Q4 Q3 Q2 Q1 Output Output Manual Bypass Manual Bypass Bypass Inp.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 3 1 4 2 5 3 Output Manual Bypass Bypass Input Main Input Output Manual Bypass Bypass Input Main Input Q4 Q2 Q1 Output Manual Bypass Bypass Input Main Input Q3 A A A 26.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 1 1 3-7 2 A A 6 5 7 3 Output Manual Bypass Bypass Input Main Input Q3 Q1 Q4 Q2 Output Manual Bypass Bypass Input Main Input 3 5 4 Q3 Q1 Q4 Q2 27 9 – Star t-Up, Shutd.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 1 3 6 5 7 Output Manual Bypass Bypass Input Main Input Q4 Q3 Q2 Q1 Q2 Q3 Q4 Q1 28 9-6 Shutdown Pr ocedure (Single UPS) (continued) T o transfer the critical load to NORMAL mode from Manual Bypass: 1.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 1 2 A A B B 3 5 4 6 Output Manual Bypass Bypass Input Main Input Q2 Output Manual Bypass Bypass Input Main Input Q1 A Output Manual Bypass Bypass Input Main Input Q4 2.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 1 2 A Output Manual Bypass Bypass Input Main Input Q1 Q4 3 4 Output Manual Bypass Bypass Input Main Input Q2 A 30 9 – Star t-Up, Shutdown and Bypass (continued) 9-9 Shutdown Pr ocedure (P arallel UPS) W arning: The UPS system shutdown pr ocedure will eliminate the A C power output f or all loads.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 1 2 3 4 A Output Output Output Manual Bypass Manual Bypass Manual Bypass Bypass Input Bypass Input Bypass Input Main Input Main Input Main Input Q1 Q3 Q2 Q4 5 A 6 Q4 Q.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 1 2 3 5 4 A Output Manual Bypass Bypass Input Main Input Q2 Q4 Output Output Manual Bypass Manual Bypass Bypass Input Bypass Input Main Input Main Input Q3 Q1 A 32 9 .
1 5 9 3 7 11 2 6 10 4 8 12 13 14 Contr ol P anel E F G K A B C D H I J 33 10 – Displa y and Configuration 10-1 Control P anel Diagram “NORMAL” (Gr een) LED: Illuminated when the UPS input • power is normal. “B A TTERY” (Amber) LED: Illuminated when the UPS is in • Battery Backup mode.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 1 1 When any e vent occurs, you will see the sign “!” flashes. Y ou can press “ ” to see the details. For example: Press “ ” again to go to the next message. If there is no further message, the screen will return to the def ault screen.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 2 3 4 35 10 – Displa y and Configuration (continued) 10-3-1 Status Display (contin ued) The loads are supplied by bypass source due to initial startup of • the UPS. The UPS is starting up by battery power . • The UPS system is in auto bypass mode.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 5 6 7 36 10 – Displa y and Configuration (continued) 10-3-1 Status Display (contin ued) The UPS system is operating in online (normal) mode. Connected • equipment loads will receiv e battery backup po wer if the mains (utility or generator) power source f ails.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 8 9 37 10 – Displa y and Configuration (continued) 10-3-1 Status Display (contin ued) The UPS system is operating in economy mode, and connected • equipment loads are being powered by the bypass source.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 38 10 – Displa y and Configuration (continued) 10-4 Main Menu (continued) UPS System “Measure Menu 1. Press the enter button ( ) to select “MEASURE” from the main menu. 2. Use the scroll buttons ( or ) to scroll through the a v ailable data screens.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 1 2 39 10 – Displa y and Configuration (continued) 10-5 UPS Setup Befor e changing the setting of each SETUP , you ha ve to login f irst. Accessing the UPS system setup menu requires a password. From • the login screen, press the enter button ( ) to select whether to log in as an administrator or user .
1 5 9 3 7 11 2 6 10 4 8 12 13 14 3 1 2 40 10 – Displa y and Configuration (continued) 10-5 UPS Setup (continued) If the password is wrong, press ” • ” to reselect. 10-5-1 Bypass Setup Enter the UPS system setup menu. Use the scroll buttons ( • , ) to mov e the cursor to “BYP ASS SETUP”, then press the enter button ( ).
1 5 9 3 7 11 2 6 10 4 8 12 13 14 3 1 41 10 – Displa y and Configuration (continued) 10-5-1 Bypass Setup (continued) From the “FREQUENCY RANGE” screen, use the scroll b uttons • ( , ) to select a bypass frequency range and press the enter button ( ) to conf irm the setting.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 2 3 4 42 10 – Displa y and Configuration (continued) 10-5-2 Output Setup (continued) Output V oltage Do not change the default v oltage setting as it will negati vely affect UPS performance.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 5 6 43 10 – Displa y and Configuration (continued) 10-5-2 Output Setup (continued) From the “FREQ CONVER TER MODE” screen, use the scroll buttons ( , ) to select the desired setting and press the enter button ( ) to conf irm the setting.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 1 2 3 44 10 – Displa y and Configuration (continued) 10-5-3 Battery Setup (continued) Enter the UPS system setup menu. Use the scroll buttons ( , ) to mov e the cursor to “B A TTER Y SETUP”, then press the enter button ( ).
1 5 9 3 7 11 2 6 10 4 8 12 13 14 4 5 6 45 10 – Displa y and Configuration (continued) 10-5-3 Battery Setup (continued) From the “INST ALL D A TE” screen, use the scroll buttons ( , ) to select the desired settings and press the enter button ( ) to confirm the settings.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 1 2 46 10-5-4 Charger Setup Use “ ” or ” ” to select “CHARGER”, then press ” ” to confirm. From the “CHARGER CURRENT” screen, use the scroll buttons ( , ) to select the desired setting and press the enter button ( ) to confirm the setting.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 1 2 3 47 10-5-5 P arallel Setup Use “ ” or ” ” to select “P ARALLEL”, then press ” ” to confirm. Use “ ” or ” ” to select the desired item, then press ” ” to confirm. Parallel Gr oup The parallel group setting tells the UPS that it is operating in parallel.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 1 2 3 48 10 – Displa y and Configuration (continued) 10-5-6 Control & T est Setup Use “ ” or ” ” to select “CONTR OL & TEST”, then press ” ” to confirm. Use “ ” or ” ” to select the desired item, then press ” ” to confirm.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 4 5 6 49 10 – Displa y and Configuration (continued) 10-5-6 Control & T est Setup (continued) Manual Battery T est Press ” ” to execute “MANU AL BA T TEST”. Allows you to run a battery test at a non-scheduled time at the user’ s discretion.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 7 1 2 50 10 – Displa y and Configuration (continued) 10-5-6 Control & T est Setup (continued) Select “BUZZER AND LED TEST” to initiate test of the control panel LEDs and audible alarm. Y ou must enter the administrator password to conf irm the operation.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 3 4 5 51 10 – Displa y and Configuration (continued) LCD Contrast Use “ ” or ” ” to set the contrast of LCD screen, then press ” ” to confirm. Changes the contrast ratio of the LCD. (This item is user accessible!) 1 is the lowest and 5 is the highest le vel.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 6 7 8 52 10 – Displa y and Configuration (continued) 10-5-7 Local Setup (continued) Administrator Password From the “P ASSWORD CHANGE” screen, use the scroll buttons ( , ) and the enter button ( ) to select the desired menu choice.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 1 2 3 53 10 – Displa y and Configuration (continued) 10-6 Maintenance Use “ ” or ” ” to select ”MAINTEN ANCE” in the main menu, then press ” ” to confirm. The first item is the series number of the UPS unit.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 4 5 54 10 – Displa y and Configuration (continued) 10-6 Maintenance (continued) Event Log Use “ ” or ” ” to read the ev ent log, then press” ” to confirm. Advance Use “ ” or ” ” to select the “ ADV ANCED” item, then press ” ” to confirm.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 SNMPWEBCARD Slot Input Dry Contact Interface P arallel Configuration P or t RS-232 Serial P or t Output Dry Contact Interface 55 11 – Comm unications Note: The communications connections described in this section ar e optional.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 P1 P2 56 11 – Comm unications (continued) 11-4 Remote Emergency P ower Off (EPO) Cir cuit Diagram The Remote Emergenc y Power Of f (EPO) input connection (P1) allows you to connect the UPS system to your facility’ s EPO circuit.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 57 11 – Comm unications (continued) 11-8 Output Dry Contact Interface Detail The UPS system has six dry contact output connections. These contacts can be normally open or normally closed. Default Messages Contact Message Description Pin 1-2 Load on inverter The UPS system is working normally .
1 5 9 3 7 11 2 6 10 4 8 12 13 14 OUTPUT DR Y CONT A CT 58 11 – Comm unications (continued) 11-9 Output Dry Contact Circuit Diagram The UPS system has six dry contact output connections. These contacts can be normally open or normally closed. Contacts are rated for 250V AC/28V DC; 8A.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 59 12 – Specifications 12-1 UPS System T echnical Specifications 12-2 UPS System Floor Loading T able 12-3 Battery P ack Floor Loading T able Optional Messages Mod.
1 5 9 3 7 11 2 6 10 4 8 12 13 14 60 13 – Storage and Service 14 – W arranty Storage The UPS system must be stored in a clean, secure en vironment with a temperature less than 40° C (104° F) and a relati ve humidity less than 90% (non-condensing).
An important point after buying a device Tripp Lite SU20KX (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Tripp Lite SU20KX yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Tripp Lite SU20KX - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Tripp Lite SU20KX you will learn all the available features of the product, as well as information on its operation. The information that you get Tripp Lite SU20KX will certainly help you make a decision on the purchase.
If you already are a holder of Tripp Lite SU20KX, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Tripp Lite SU20KX.
However, one of the most important roles played by the user manual is to help in solving problems with Tripp Lite SU20KX. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Tripp Lite SU20KX along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center