Instruction/ maintenance manual of the product 120/208V Tripp Lite
Go to page of 18
1. Important Safety W arnings 2 2. Control P anels 3 2.1 Front P anel 3 2.2 Battery Access Panel (Co ver Removed) 4 2.3 Rear Panel 5 3. Installation 6 3.1 UPS Location 6 3.2 Mounting Bracket Installation 6 3.3 Grounding Connection 6 3.4 UPS Input And Output Hard wire Connection 6 3.
2 SA VE THESE INSTR UCTIONS. This manual contains important instructions and warnings that should be follo wed during the installation and maintenance of all T ripp Lite SmartOnline 3-Phase 20kV A and 30kV A UPS Systems. UPS Location Warnings • Installyour UPS in acontrolled en vironment.
2. Control P anels 3 Note: F amiliarize yourself with the location and function of the features on your UPS system befor e installing and operating it. “ON” Button: 1. This buttonturns theUPS System's in verter ON. “OFF” Button: 2.
4 1 2 3 4 5 6 7 Individual models may vary slightly from diagram. 2.2 Battery Access P anel (Cover Removed) 2. Control P anels ( continued ) Internal Battery Packs: 1. Thesesupply backup runtime toconnected equipment. Eachpack consists oftwo strings (onepositiveand onenegativ e).
Individual models may vary slightly from diagram. 5 Manual Bypass Switch: 1. This dialis used toput the UPS in“BYP ASS” mode, whichmust be donebefore performing anymaintenance on theUPS withthe connected load supported.
6 Mov e your UPS over short distances using its wheels. Note: The wheels ar e not designed to pro vide long-term support for the UPS system after f inal installation.
7 WIRING CONNECTION Connectyour wiring to theinput and outputterminal blocks locatedon the rear panelof your UPS(see figurebelow). CA UTION! Qualified personnel should follo w all procedures prescribed by N.
8 Momentarilypress the “SELECT” buttononthe front panelto browsethrough differentpowerreadings onthe LCD Display . BYP ASS OUTPUT R: XXXV R: XXX.XV S: XXXV S: XXX.XV T: XXXV T: XXX.XV (Bypass&Output Vo ltage) OUTPUT LO AD R: XXX% XXX.
9 Condition LCD Display Message Overload Shutdown ONBYP ASS O VERLO AD 150% SHUTDO WN... VERSION: XXXXXXX UPS Output Short Circuit ONBYP ASS SHOR T CIRCUIT! SHUTDO WN... VERSION: XXXXXXX Overtemperature ONBYP ASS HIGHTEMP! SHUTDO WN... VERSION: XXXXXXX DCBUS Overv oltage ON BYP ASS DCBUS O.
3 V + - 10 Thisfemale DB9 port connectsyour UPS viaan RS-232 cableto a workstationor serverequipped withTrippLite software.Theport uses RS-232 communicationsto report UPS statusand powerconditions.
X 1 2 3 4 5 6 X 11 Thisoptional feature is onlyfor those applicationswhich require connectionto a facility'sEmergencyPowerOff(EPO) circuit.Whenthe UPS System isconnected to this circuit,it enables emergenc y shutdownof theoutput.
UPS System Batter y Back Co nnec to r White wir e Blue wire UPS System Batter y Back Co nnec to r Fu se Block Bracket Red wire (+ ) Black wire (–) 12 Qualifiedservice personnelshould familiarizethemselves withthe battery packwiring diagram prior toadding or replacingbatteries.
13 Placethe UPS System inBypass Mode orcompletely turn itoff, dependingon preference. (See section5.4, Operation of Manual Bypass Switch , or4.2, T urning the UPS Off .) 1 Remov e battery accesspanel, located on theFRONTof theUPS system.
14 Slide the battery string with the RED cable into an empty slot within the battery compartment as sho wn. Make sure that the string is oriented as shown in the diagram 7A . Note: If the auxiliary battery connector is in the way , remove its mounting screw and position the cable to allow adequate room to add the battery strings 7B .
240 15 D ANGER! B A TTER Y CARTRIDGE FUSES MUST BE INSERTED LAST DUE TO THE DANGER OF PO TENTIAL ARCING OF CONNECTORS. FUSE REPLA CEMENT The fuses protect against shor t circuit damage . If a heavy overload or shor t cir cuit is encountered, a fuse will blow .
16 Y our SmartOnline 3-Phase UPSSystem is cov ered by thelimited warranty describedbelow . Extended warranty(2-, 3- and4-year) and start-upservice programsare av ailable. Formore information, callTrippLiteCustomer Service at(773) 869-1234.
17 Model: SU20K3/3 Input Input Voltage 120/208V AC, 3ø, 4 Wire (plus ground), wye Input Frequency 60 Hz ± 3 Hz V oltage Correction Range 88-144/166-250V AC Input Cur rent (Per Phase, On-Line) 60A Inr ush Cur rent <300A Power Factor (Full Load) >0.
200901138 93-2624 18 Model: SU30K3/3 Input Input Voltage 120/208V AC, 3ø, 4 Wire (plus ground), wye Input Frequency 60 Hz ± 3 Hz V oltage Correction Range 88-144/166-250V AC Input Cur rent (Per Phase, On-Line) 90A Inr ush Cur rent <300A Power Factor (Full Load) >0.
An important point after buying a device Tripp Lite 120/208V (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Tripp Lite 120/208V yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Tripp Lite 120/208V - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Tripp Lite 120/208V you will learn all the available features of the product, as well as information on its operation. The information that you get Tripp Lite 120/208V will certainly help you make a decision on the purchase.
If you already are a holder of Tripp Lite 120/208V, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Tripp Lite 120/208V.
However, one of the most important roles played by the user manual is to help in solving problems with Tripp Lite 120/208V. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Tripp Lite 120/208V along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center