PDRP -1001 Series Deluge - Preaction Control Pa n e l Instructi on Manual 3825 Ohio A venue St. Charles, IL 6 0174 1-800 -SENSOR2 Fax: (6 30) 377-6 495 PN 50734 :D0 ECN 00-543 Docu men t 5073 4 I56-93.
Lim W arLg.p65 01/10/2000 An automatic fire alarm system –typically made up of smoke detectors, heat detectors, manual pull stations, audible warn- ing devices, and a fire alarm control with remote notification capability–can provide early warning of a developing fire.
Lim W arLg.p65 01/10/2000 WARNING - Several different sources of power can be con- nected to the fire alarm control panel. Disconnect all sources of power before servicing. Control unit and associated equip- ment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized.
NFPA Stan dards 4 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 NFP A Standards This control panel complies wi th the following NFP A standards: •N F P A 1 3 - Sprinkler S ystems •N F P A 1 5 .
Table of Contents PDRP-1001 Instruction M anual PN 50734:D0 04/06/01 5 T able of Contents NFPA Standards ........... ................. ............................ ............................ ...................... 4 NFPA Standards .......... .......
Table o f Contents 6 PDRP-1001 Instruction M anual PN 50734:D0 04/06/01 Setup and Configuration...... ................. ............ ................. ........... ................. ....... 25 Transmitter Modu le - 4XTM ........ ............ ..........
PDRP-1001 Instruction M anual PN 50734:D0 04/06/01 7 1. Product Descripti on Overview The PDRP-1001 Series Deluge - Preaction C ontrol System has been designed as a contro l center for use in single- and dual-hazard d eluge and p reaction applications.
1. Produ ct Descri ption Circu its 8 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 Circuits Input Circuits Initiating Device Circu it #1 (Style B/D) Initiating Device Circu it #2 (Style B/D) W ate.
Contro l Panel 1. Produc t Descrip tion PDRP-1001 Instruction M anual PN 50734:D0 04/06/01 9 Control Panel Figure 1 Control Panel SW 1 TB 1 TB 2 TB 3 TB 4 JP1 GE N ALM 2 SU PV 1 SU PV 2 GE N ALM 1 J4 .
1. Produ ct Descri ption DIP Swi tch Fu nctions 10 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 DIP Switch Functions The table below describes the DIP switch fun ctions. For a more detailed explaination see "Setting Mode of Operatio n" on page 28 .
Options 1. Produc t Descr iption PDRP-1001 Instruction M anual PN 50734:D0 04/06/01 11 Remote Annunciator - RZA-4X The Remot e Annunciato r mounts o n a standard single-g ang box, an d pro vides LED indica tion of the same fu ncti ons as the Zon e Rel ay Modu le.
1. Produ ct Descri ption Specifications 12 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 Specificati ons AC Power PDRP-1001 and PDRP-1 001A : 1 10/120 V AC, 50/ 60 Hz, 1 .2 amps PDRP-1001E: 220/24 0 V AC, 50/60 Hz, 0.6 amp s W ire size: m inimum #14 A WG with 600V insulation Battery (lead acid only) Maximum Char ging Circ uit: 27.
PDRP-1001 Instruction M anual PN 50734:D0 04/06/01 13 2. Installation Cabinet Mounting Carefully unp ack the system and check for shipping damage. Select a suitable location in a clean, dr y , vibration-free env ironment that is not subject to ex treme temperatures.
2. Inst allation Cabinet Moun ting 14 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 The figure below shows the exterio r dimensions and mounting ho le locations for the cabinet backbox and dimens .
Installing Optional Vol tmeter/Ammeter 2. Instal lation PDRP-1001 Instruction M anual PN 50734:D0 04/06/01 15 Installi ng Optional V oltmet er/Ammeter T o monitor battery voltage and battery char ging current, a 4XMM Meter Module is req uired.
2. Inst allation Power Connect ions 16 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 Power Connections W ARNING: Do not apply any type power to this control panel until all connections have been made and verified. AC Connections Disconnect (op en) the circuit breaker in the AC main breaker pan el and tag it “Out of Service”.
Power-limited Wiring R equirements 2. Instal lation PDRP-1001 Instruction M anual PN 50734:D0 04/06/01 17 Observe po larity wh en connecting t he batteri es. Connect t he battery cable (p/n 75203 o r 75202, depending on terminal size of battery) to terminal J9 on the main circuit board using the plug-in connector p rovided.
2. Inst allation Initiating D evice Circuits 18 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 Initiati ng Device Circuits The control panel provides four (4) Initiating Device Circui ts (#1, #2, #3 and #4) and they may be configured as either Style D (Class A) or Style B ( Class B).
Initiating Device Circu its 2. Installatio n PDRP-1001 Instruction M anual PN 50734:D0 04/06/01 19 Four-Wire Smoke Detector Connections A maximum of 200mA is available from th e 24VDC Resettable Power circuit on TB1 (+24VR terminals).
2. Inst allation Outp ut Ci rcuit s 20 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 Output Circui ts Notification Appliance Circuits The control panel provides two Style Z (Class A) or Style Y (Class B) Notification Appliance Circuits, which are supervised and power- limited.
Output Circuits 2. Instal lation PDRP-1001 Instruction M anual PN 50734:D0 04/06/01 21 Releasing Circuits CAUTION: To prevent accidential discharg e, connect releasing devices after initial panel tests are completed. The control panel pro vides two Style Y (Class B) Releasing Circu its, which are nonpower- limited.
2. Inst allation Powering External Devices 22 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 Alarm Relay Circuit One Form-C dry contact alarm relay is provided in the basic panel for controlling supplementary devi ces. Contacts are rated 2 amps at 30 VDC and 0.
Optional Modules 2. Instal lation PDRP-1001 Instruction M anual PN 50734:D0 04/06/01 23 Optional Mo dules Overview The control panel has two module connectors - J5 (upper position) and J8 (lower position). Three modules are available for the panel and they can be used in any com bination, including d uplicate modules.
2. Inst allation Opti on al Modu les 24 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 Installation - Lower Position T o install eith er the 4XTM, 4XZM or 4XLM module in the lower position follow these instruction s: Figure 14 Module Installation - Lower Position Step Action 1 Cut j umper ‘OP T 2’ on main ci rcuit bo ard.
Optional Modules 2. Instal lation PDRP-1001 Instruction M anual PN 50734:D0 04/06/01 25 Setup and Configuration Transmitter Module - 4XTM Connect a Remote A larm circuit, Rem ote T rouble circuit or a Municipal B ox to the T ransmitter Module as shown below .
2. Inst allation Opti on al Modu les 26 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 Zone Rel ay Module - 4XZM Note: The P AR-3 includes one (1) Zone Relay Module (4XZM). Relay #1 through #4 on this mod ule will a ctivate with outp uts #1 through #4.
Optional Modules 2. Instal lation PDRP-1001 Instruction M anual PN 50734:D0 04/06/01 27 LED Interface M odule - 4XLM Connect the terminals on TB1 of the LED Interface Mod ule to the corresponding termin als of the RZA- 4X Remote Annu nciator . Make wiri ng connectio ns with sy stem power off.
2. Inst allation Setting Mo de of Operation 28 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 Setting Mode of Opera tion Select op erating mode by setting the S W1 DIP swi tches as described below . After any chang es are made to the co nfiguration of the switches, the pan el must be reset.
Setting Mode of Operation 2. Installatio n PDRP-1001 Instruction M anual PN 50734:D0 04/06/01 29 Discharge Timer Select the desired discharge timer setting by setting DIP Switches 3, 4 and 5 accordingly . • For NFP A 13 and 15 appli cations timer mu st be s et to “Disabl ed”.
2. Inst allation Power -Up P rocedur e 30 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 Power-Up Procedure W ARNING: Prior to energizing this panel, notify all pers onnel and authorities, inclu ding any personnel w ho may be working on, a round, or near th is unit.
PDRP-1001 Instruction M anual PN 50734:D0 04/06/01 31 3. System Operation System Status LEDs Alarm, T r ouble and Supervisory LEDs will flash on and off until the event( s) has been acknowledged (TONE or ALARM SILENCE), at which point the LED will illuminate steadily .
3. Sys tem Oper ati on Control Sw itches 32 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 Control Switches Figure 22 Control Panel Switches T one Silence - Pressing this s witch ackn owledges alarm s, troub les and sup ervisories . The panel has alarm and trouble res ound with L ED flash of new condi tions.
Piezo 3. Sys tem Oper ati on PDRP-1001 Instruction M anual PN 50734:D0 04/06/01 33 Piezo The piezo (local buzzer) gener ates different tone patterns for d ifferent ev ent conditions: • Alarm - Generates a steady tone, no pu lse. • Tr o u b l e - Pulses one second on, one second of f.
3. Sys tem Oper ati on Last Event Recall 34 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 Last Event Recall Last Event Recall allows the user to display the previou s panel status. The Last Event Recall mak es use of the four panel switches as f ollows: 1.
System Events 3. Sys tem Oper ati on PDRP-1001 Instruction M anual PN 50734:D0 04/06/01 35 Single Zone in Alarm (Cross Zone) Condition Upon actuation of a single-zone initiating device, a red alarm LED will illuminate to indicate whether Zone 1 or Zone 2 is in alarm.
3. Sys tem Oper ati on System Events 36 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 Notes.
PDRP-1001 Instruction M anual PN 50734:D0 04/06/01 37 Appendix A: Secondary Power Calculation s Standby Battery Requirements The Standby Battery Curren t obtained in the table belo w represents the amou nt of current that mu st be supplie d by the secon dary power s ource (batte ries) to sustain co ntrol panel o peration fo r one hour .
Appendix A: Sec ondary Powe r Calculati ons Calculating the Batt ery Capacity 38 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 Calculating the Battery Capacity Use this table to determine the batter y capacity required by the system.
PDRP-1001 Instruction M anual PN 50734:D0 04/06/01 39 Appendix B: Compatible Devices T wo-wire Smoke Detectors, UL Listed Use the two-wire detecto rs listed below . T able 3 T w o-wire Smo ke Detectors Detector Model Identifier T ype Base Model Identifier Standb y Current (mA ) Detectors per Zone Syste m Sens or 14 00 A Ioniza tion n/a n/a 0.
Appen dix B: Com patible D evices Four-wire Smoke Detectors, UL Lis ted 40 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 Four-wire Smoke Detectors, UL Listed Use the f our-wire detect ors lis ted below .
Notification Appliances, UL Listed Appendi x B: C ompatible Devices PDRP-1001 Instruction M anual PN 50734:D0 04/06/01 41 Notification Appliances, UL Listed Control pane ls suppling Special Appl ication (FWR, Filtered) p ower must use the Notificatio n Appliances listed below .
Appen dix B: Com patible D evices Notification Appliances, UL Listed 42 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 T able 6 Notification Appliances System S ensor SP10 1R24M Sp eaker/St robe, 5.
Door Holders, UL Listed Appendi x B: C ompatible Devices PDRP-1001 Instruction M anual PN 50734:D0 04/06/01 43 Door Holders, UL Listed Use the Door Holders listed below .
Appen dix B: Com patible D evices 24 VDC Relays, UL Listed 44 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 Notes.
PDRP-1001 Instruction M anual PN 50734:D0 04/06/01 45 Appendix C: NFP A Stan dard-Specific Requiremen ts Minimum System Requirements The control panel has been design ed for use in commercial, industr.
Appendix C: NFPA Standard- Specifi c Requireme nts Digital Alarm Com municator/Transmitter - Noti -Fire 911AC 46 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 Digital Alarm Communicator /T ransmit.
Universal Digital Alarm Communicator - 411UDAC Appendi x C: NFPA Standar d-Specifi c Requirem ents PDRP-1001 Instruction M anual PN 50734:D0 04/06/01 47 Universal Digital Alarm Communicator - 41 1UDAC.
Appendix C: NFPA Standard- Specifi c Requireme nts Local Energy Mun icipal Box 48 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 Local Energy Municipal Box Using th e 4XTM T ransmitter Modu le for con nection to a Lo cal Ener gy Municipa l Box. • The M uni cipal Box cir cui t super vises for g round fault s and op ens ( i.
PDRP-1001 Instruction M anual PN 50734:D0 04/06/01 49 Remote Station Receiver - RS82-9 Using the 4XTM T ransmitter Module for con nection to a Fire•Lite RS82-9 R emote Station Receiver . • Intended fo r connection to a polarity r eversal circuit of a remote s tation receiving unit hav ing compatible ratings.
Appendix C: NFPA Standard- Specifi c Requireme nts Remote Station Rece iver - RS82-9 50 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 Notes.
PDRP-1001 Instruction M anual PN 50734:D0 04/06/01 51 Append ix D : T es ting & Maintena nce T esting Inspection Perform the following p rior to applying power to the system. • Check th e actual wiring hookup wi th the wir ing diagrams. • Insure that no pieces of wire h ave fallen into the circuitry .
Appen dix D: Test ing & Mai ntenance Troubleshoo ting 52 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 T able 9 T roubleshooting T able Symptom Problem Solution AC Power LED ON Syst em trou ble LED ON Circuit trouble LED ON Notificatio n appliance circuit trou ble 1.
Index PDRP-1001 Instruction M anual PN 50734:D0 04/06/01 53 Index Numerics 110/12 0 VAC 12 220/24 0 VAC 12 411UDAC 45, 4 7 4XLM LED Interface Mod ule 11, 23 4XMM Meter Module 11, 15 4XTM Transmitter M.
Index 54 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 inspection 51 interconnect wire, battery 30 Interface Module 11 interruption of circuits 34 J J1 connector 13 , 14 J2 Connector 15 J3 Connect.
Index PDRP-1001 Instruction M anual PN 50734:D0 04/06/01 55 rese ttabl e powe r 19, 22 resistance, allowable 19 resist or 47 reso und 32 reverse po larity 25 reverse po larity circu it 10 reverse po l.
Limited W arranty System S ensor ® warrants its produc ts to be free from defects in materials and workman- ship for eightee n (18) months fro m the date of man ufacture , under nor mal use and ser - vice. Products are date stamped at time of m anufacture.
An important point after buying a device System Sensor PDRP-1001 Series (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought System Sensor PDRP-1001 Series yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data System Sensor PDRP-1001 Series - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, System Sensor PDRP-1001 Series you will learn all the available features of the product, as well as information on its operation. The information that you get System Sensor PDRP-1001 Series will certainly help you make a decision on the purchase.
If you already are a holder of System Sensor PDRP-1001 Series, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime System Sensor PDRP-1001 Series.
However, one of the most important roles played by the user manual is to help in solving problems with System Sensor PDRP-1001 Series. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device System Sensor PDRP-1001 Series along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center