D1 00-67-00 1 I56-1 148-04 DH100 Air Duct Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS A Division of Pittwa y 3825 Ohio A venue, St. Charles, Illinois 60 174 1-800-SENSOR2, F AX: 630-377-6.
holes as indicated on the template . Insert the two jack nut receptacles . Drive a #1 0 machine screw into the jacknut to flare the r etainer and then back the screw out to use for de- tector mounting. [5.2.1] Sampling Tube Installation for Ducts Less Than 1 1 / 2 Feet Wide (see Figur e 2) 1.
[5.3] Secure The Detector Housing T o The Duct Slide the foam gaskets o ver the tube bushings as shown in Figure 3. Use the tw o machine screw s to screw the detector housing to the duct. CA UTION: Do not o vertighten the scr ews . Figure 3. Installation of foam gaskets over sampling tube bushings: A78-2045-00 [5.
W ARNING In no case should more than 2 air inlet holes be cut off the tube . There must be a minimum of 1 0 holes in the tube ex- posed to the air stream. [5.4.2] Installation For Ducts More Than 8 Feet W ide NO TE: T o install inlet tubes in ducts more than 8 feet wide , work must be performed inside the air duct.
F or signal wiring, (the wiring betw een interconnected de- tectors or fr om detectors to auxiliary devices), it is usually recommended that single conductor wir e be no smaller than 18 gauge . The duct smoke detector terminals accom- modate wire sizes up to 12 gauge .
D1 00-67-00 6 I56-1 148-04 SUPERVISORY SWITCH 76 4 (+) IN (+) OUT (+) (+) 5 8 (–) (–) IN (–) OUT 1ST DETECTOR IN LOOP DH100 (–) RA400Z (OPTIONAL) REMOTE ALARM LED 2.8 VDC NOM. IN ALARM SUPERVISORY SWITCH 76 4 (+) IN (+) OUT (+) (+) 5 8 (–) (–) IN (–) OUT LAST DETECTOR IN LOOP DH100 (–) RA400Z (OPTIONAL) REMOTE ALARM LED 2.
D1 00-67-00 7 I56-1 148-04 [6.2.2] Alarm T ests [6.2.2.1] M02-04-00 Magnet T est 1. Place the painted surface of the magnet onto the TEST locator on the bottom of the housing (Figur e 9). 2. The red alarm LEDs on the detector should latch on, as should any accessories (i.
[9] Model DH100 Air Duct Smoke Detector Specifications T emperature: 32 ° to 13 1 ° F0 ° to 55 ° C Humidity: 1 0% to 93% R.H. noncondensing Air V elocity: 500 to 4000 ft./min. 2.5 to 20.3 m/sec . Dimensions: 14.38 ″ L x 5.5 ″ W x 2.75 ″ D 36.
An important point after buying a device System Sensor I56-1148-04 (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought System Sensor I56-1148-04 yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data System Sensor I56-1148-04 - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, System Sensor I56-1148-04 you will learn all the available features of the product, as well as information on its operation. The information that you get System Sensor I56-1148-04 will certainly help you make a decision on the purchase.
If you already are a holder of System Sensor I56-1148-04, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime System Sensor I56-1148-04.
However, one of the most important roles played by the user manual is to help in solving problems with System Sensor I56-1148-04. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device System Sensor I56-1148-04 along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center