Instruction/ maintenance manual of the product PA13361-A Bard
Go to page of 25
Manual 2100-467D Page 1 of 25 SINGLE P ACKAGE AIR CONDITIONERS MODELS P A13241-A P A13301-A P A13361-A P A13361-B P A13422-A P A13422-B P A13422-C P A13482-A P A13482-B P A13482-C P A13602-A P A13602-.
Manual 2100-467D Page 2 of 25 CONTENTS Getting Other Informations and Publications ........ 3 General Instructions Important ................................................................ 4 Shipping Damage ...........................................
Manual 2100-467D Page 3 of 25 Getting Other Information and Publications These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.
Manual 2100-467D Page 4 of 25 GENERAL INSTRUCTIONS IMPORTANT The equipment covered in this manual is to be installed by trained, experienced service and installation technicians. All duct work, supply and return ducts, must be properly sized for the design airflow requirement of the equipment.
Manual 2100-467D Page 5 of 25 TABLE 2 ELECTRICAL SPECIFICATIONS l e d o MA - 1 4 2 3 1 A PA - 1 0 3 3 1 A PA - 1 6 3 3 1 A PB - 1 6 3 3 1 A PA - 2 2 4 3 1 A PB - 2 2 4 3 1 A PC - 2 2 4 3 1 A PA - 2 8 .
Manual 2100-467D Page 6 of 25 TABLE 3 OPTIONAL FIELD INSTALLED HEATER PACKAGES ONLY TO BE USED WITH THE MODELS INDICATED e g a k c a P r e t a e H l e d o M & s t l o V e s a h PA - 1 4 2 3 1 A PA.
Manual 2100-467D Page 7 of 25 TABLE 4 OPTIONAL FIELD INSTALLED ELECTRIC HEATER TABLE r e t a e H e g a k c a P . o N l e d o M s t l o V t i n U s e s a h P y t i c a p a C & W K . r t H s t l o V 0 4 2 @ y t i c a p a C & W K . r t H s t l o V 8 0 2 @ V 8 0 2 / 0 4 2 .
Manual 2100-467D Page 8 of 25 FIGURE 1 DIMENSIONS OF UNITS MIS-2142 Unit Dimension Chart Condenser air intake grille Condenser air intake grille Blower motor access door Condenser fan G 47 11/16".
Manual 2100-467D Page 9 of 25 INST ALLA TION LOCATION GENERAL The unit must be located outside, or in a well ventilated area. It must not be in the space being heated or cooled.
Manual 2100-467D Page 10 of 25 24" min. 36" min. 24" min. The distance between 1 inch clearance Air Inlet Air Inlet Supply and Return Ducts Building Heater Package Access Control Panel .
Manual 2100-467D Page 11 of 25 FIGURE 4 ELEVATED MOUNTING PLATFORM 48" min. 32°F or lower climate 12" min. if in on surface of platform Both legs must rest 48" min.
Manual 2100-467D Page 12 of 25 FIGURE 5 CONDENSATE DRAIN TRAP 5. OTHER INSTALLATIONS – Many other installations are possible with the packaged air conditioner. No matter what the installation, always consider the following facts: A. Insure that the discharge air is not obstructed in any way so as to cause operation difficulties.
Manual 2100-467D Page 13 of 25 TABLE 6 THERMOSTAT WIRE SIZE A V r e m r o f s n a r TA L Fe g u a G e r i W m u m i x a M e c n a t s i D t e e F n I 5 53 . 2 0 2 8 1 6 1 4 1 2 1 5 4 0 6 0 0 1 0 6 1 0 5 2 TRANSFORMER TAPS 230/208V, 1 phase and 3 phase equipment employ dual primary voltage transformers.
Manual 2100-467D Page 14 of 25 L Unit Contr ol Panel C E Y W2 O G MIS - 2149 B Y Term in al R G C HEA T ON UNITS WI T H 15 OR MORE K W C L o w V o l t a g e W i r i n g B R W RC R Y1 L G C G Block R E.
Manual 2100-467D Page 15 of 25 ST ART UP These units require R-410A refrigerant and Polyol Ester oil. GENERAL: 1. Use separate service equipment to avoid cross contamination of oil and refrigerants. 2. Use recovery equipment rated for R-410A refrigerant.
Manual 2100-467D Page 16 of 25 THREE PHASE SCROLL COMPRESSOR START UP INFORMATION (Model PA13361-B) Scroll compressors, like several other types of compressors, will only compress in one rotational direction. Direction of rotation is not an issue with single phase compressors since they will always start and run in the proper direction.
Manual 2100-467D Page 17 of 25 ADJUSTABLE DELAY-ON-MAKE AND BREAK TIMER On a call for compressor operation the delay-on-make period begins which will be 10% of the delay-on-break setting. When the delay-on-make is complete and the high pressure switch (and low pressure switch if employed) is closed, the compressor contactor is energized.
Manual 2100-467D Page 18 of 25 FAN BLADE SETTINGS Shown in Figure 8 are the correct fan blade setting dimensions for proper air delivery across the outdoor coil. Any service work requiring removal or adjustment in the fan and/or motor area will require that the dimensions below be checked and blade adjusted in or out on the motor shaft accordingly.
Manual 2100-467D Page 19 of 25 (Continued on Page 20 in Table 11) l e d o M r i A n r u t e R e r u t a r e p m e T e r u s s e r P° 5 6° 0 7° 5 7° 0 8° 5 8° 0 9° 5 9° 0 0 1° 5 0 1° 0 1 1° .
Manual 2100-467D Page 20 of 25 TABLE 11 PRESSURE TABLE COOLING Air T emperature Entering Outdoor Coil Degree F LOW SIDE PRESSURE +2 PSIG HIGH SIDE PRESSURE +5 PSIG l e d o M r i A n r u t e R e r u t .
Manual 2100-467D Page 21 of 25 SUCTION AND DISCHARGE TUBE BRAZING Compliant Scroll compressors have copper plated steel suction and discharge tubes. These tubes are far more rugged and less prone to leaks than copper tubes used on other compressors.
Manual 2100-467D Page 22 of 25 NOTE: Affects Models PA13241, PA13301, PA13361 TROUBLESHOOTING GE ECM 2.3 ™ MOT ORS CAUTION: Disconnect power from unit before removing or replacing connectors, or servicing motor. To avoid electric shock from the motor’s capacitors, disconnect power and wait at least 5 minutes before opening motor.
Manual 2100-467D Page 23 of 25 TROUBLESHOOTING GE ECM2.3 ™ MOT ORS CONT’D. Replacing ECM Control Module To replace the control module for the GE variable-speed indoor blower motor you need to take the following steps: 1. You MUST have the correct replacement module.
Manual 2100-467D Page 24 of 25 FIGURE 13 ↓ ↓ NOTE: Bard Models PA13422, PA13482 & PA13602 contain the X13-Series Motors. TROUBLESHOOTING GE X13-SERIES ECM2.3 ™ MOT ORS If the Motor is Running 1. It is normal for the motor to rock back and forth on start up.
Manual 2100-467D Page 25 of 25 FIGURE 14 TROUBLESHOOTING GE X13-SERIES ECM2. 3 ™ MOT ORS CONT’D. Model X13 Communication Diagnostics The X13 motor is communicated through 24 VAC low voltage (Thermostat Control Circuit Wiring). 1. Start with unit wiring diagram to confirm proper connections and voltage (see Figure 14).
An important point after buying a device Bard PA13361-A (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Bard PA13361-A yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Bard PA13361-A - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Bard PA13361-A you will learn all the available features of the product, as well as information on its operation. The information that you get Bard PA13361-A will certainly help you make a decision on the purchase.
If you already are a holder of Bard PA13361-A, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Bard PA13361-A.
However, one of the most important roles played by the user manual is to help in solving problems with Bard PA13361-A. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Bard PA13361-A along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center