Manual 2100-563C Page 1 of 40 MC4000 SERIES SOLID ST A TE DUAL UNIT LEAD/LAG CONTROLLER INST ALLA TION INSTRUCTIONS & REPLACEMENT P ARTS LIST Manual No.: 2100-563C Supersedes: 2100-563B File: V ol. III T ab 19 Date: 06-25-12 Bard Manufacturing Company , Inc.
Manual 2100-563C Page 2 of 40 CONTENTS Figures Figure 1 Controller Connections 1-S tage (W A/WL, W**A/ W**L Series) A/C w/No Economizers ..... 17 Figure 2 Controller Connections 2-S tage (W A*S/WL*S Series) A/C - No Economizers .
Manual 2100-563C Page 3 of 40 Getting Other Information and Publications These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.
Manual 2100-563C Page 4 of 40 SHIPPING DAMAGE Upon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.
Manual 2100-563C Page 5 of 40 SPECIFICATIONS/FEATURES FOR BASIC CONTROLLER MC4000 Basic Controller •Input power: 18-32 VAC, 60/50Hz, power is supplied from A/C #1 and/or A/C #2 •Isolation circuitr.
Manual 2100-563C Page 6 of 40 SPECIFICATIONS/FEATURES FOR ALARM BOARDS MC4000-A w/Optional Base Alarm Board (Inputs/Outputs) NOTE: If this alarm board was not originally factory installed, it can be field-installed at anytime. Bard part number is AB3000-A.
Manual 2100-563C Page 7 of 40 LOW VOLTAGE FIELD WIRING The MC4000 is powered from the air conditioners that it is controlling, 24 VAC (18-32V) low voltage only. Circuitry in the MC4000 isolates the power supplies of the two air conditioners so that no back feeds or phasing problems can occur.
Manual 2100-563C Page 8 of 40 GENERAL PROGRAMMING OVER VIEW MC4000 CONTROLLER BUTTONS AND FUNCTION On/Off Button 1. Press and release the On/Off button to turn On controller , 4-character display will illuminate and Lead unit LED will light. 2. Press and release the On/Off button to turn Of f controller.
Manual 2100-563C Page 9 of 40 HUMIDITY CONTROL OPTION Note: This function is not available if controller is configured for heat pump. The standard air conditioning system can be adapted to perform deh.
Manual 2100-563C Page 10 of 40 4 th cooling set point is 2F (default setting, user selectable 2-3F) warmer than Stage 3. On a call for 4th S tage cooling the Stage 4 LED comes on solid (no delay), and the lag unit compressor will switch to compressor S tage 2 full capacity operation.
Manual 2100-563C Page 11 of 40 6. 2-S tage Compr essor Units with Newer ECONWMT Economizers (See Note A) 1 st stage cooling set point is the setting (SP) input into the controller .
Manual 2100-563C Page 12 of 40 3 rd cooling set point is 2F (default setting, user selectable 2-3F) warmer than Stage 2. On a call for 3 rd Stage cooling the blower of the lag unit is turned on (if no.
Manual 2100-563C Page 13 of 40 5. 2-S tage Compr essor Units with Newer ECONWMT Economizers (See Note A) 1 st stage cooling set point is the setting (SP) input into the controller .
Manual 2100-563C Page 14 of 40 SPECIFICATIONS FOR OPTIONAL REMOTE COMMUNICATION BOARD CB4000 COMMUNICATION BOARD Note: If this communication board was not originally factory installed it can be field-installed at anytime. Bard part number is CB4000. Either the –A or –B alarm board is required for CB4000 to operate properly.
Manual 2100-563C Page 15 of 40 USER P AGE 1. The designated Admin person can assign up to 9 additional users and set-up as Admin, W rite or Read authority . 2. User Name and password must be assigned, each must be at least 3 characters long, and are case sensitive.
Manual 2100-563C Page 16 of 40 CONTROLLER WIRING The MC4000 can be used for controlling two (2) air conditioners with or without economizers. It can also be configured for two (2) heat pumps without economizers.
Manual 2100-563C Page 17 of 40 m e t s y S e p y T l e d o M s e i r e S o N r e z i m o n o c E B - 0 0 0 4 C M r o A - 0 0 0 4 C M n o i t a c i n u m m o C h t i w r e z i m o n o c E o N – d r a.
Manual 2100-563C Page 18 of 40 FIGURE 2 CONTROLLER CONNECTIONS 2-STAGE (WA*S/WL*S SERIES) AIR CONDITIONERS – NO ECONOMIZERS.
Manual 2100-563C Page 19 of 40 FIGURE 3 CONTROLLER CONNECTIONS 1-STAGE (WA/WL, W**A/W**L SERIES) AIR CONDITIONERS – NO ECONOMIZER WITH ALARM BOARD & CB4000 COMMUNICATION BOARD.
Manual 2100-563C Page 20 of 40 FIGURE 4 CONTROLLER CONNECTIONS 2-STAGE (WA*S/WL*S SERIES) AIR CONDITIONERS – NO ECONOMIZERS WITH ALARM BOARD & CB4000 COMMUNICATION BOARD.
Manual 2100-563C Page 21 of 40 FIGURE 5 CONTROLLER CONNECTIONS 1-STAGE (WA/WL, W**A/W**L SERIES) AIR CONDITIONERS WITH OLDER STYLE EIFM ECONOMIZERS.
Manual 2100-563C Page 22 of 40 FIGURE 6 CONTROLLER CONNECTIONS 2-STAGE (WA*S/WL*S SERIES) AIR CONDITIONERS WITH OLDER STYLE EIFM ECONOMIZERS.
Manual 2100-563C Page 23 of 40 FIGURE 7 CONTROLLER CONNECTIONS 1-STAGE (WA/WL, W**A/W**L SERIES) AIR CONDITIONERS WITH OLDER STYLE EIFM ECONOMIZERS AND WITH ALARM BOARD & CB4000 COMMUNICATION BOAR.
Manual 2100-563C Page 24 of 40 FIGURE 8 CONTROLLER CONNECTIONS 2-STAGE (WA*S/WL*S SERIES) AIR CONDITIONERS WITH OLDER STYLE EIFM ECONOMIZERS AND WITH ALARM BOARD & CB4000 COMMUNICATION BOARD.
Manual 2100-563C Page 25 of 40 FIGURE 9 CONTROLLER CONNECTIONS 1-STAGE (WA/WL, W**A/W**L SERIES) AIR CONDITIONERS WITH (ECONWMT) ECONOMIZERS.
Manual 2100-563C Page 26 of 40 FIGURE 10 CONTROLLER CONNECTIONS 2-STAGE (WA*S/WL*S SERIES) AIR CONDITIONERS WITH (ECONWMT) ECONOMIZERS.
Manual 2100-563C Page 27 of 40 FIGURE 11 CONTROLLER CONNECTIONS 1-STAGE (WA/WL, W**A/W**L SERIES) AIR CONDITIONERS WITH (ECONWMT) ECONOMIZERS AND WITH ALARM BOARD & CB4000 COMMUNICATION BOARD.
Manual 2100-563C Page 28 of 40 FIGURE 12 CONTROLLER CONNECTIONS 2-STAGE (WA*S/WL*S SERIES) AIR CONDITIONERS WITH (ECONWMT) ECONOMIZERS AND WITH ALARM BOARD & CB4000 COMMUNICATION BOARD.
Manual 2100-563C Page 29 of 40 FIGURE 13 CONTROLLER CONNECTIONS HEAT PUMPS – NO ECONOMIZER.
Manual 2100-563C Page 30 of 40 FIGURE 14 CONTROLLER CONNECTIONS HEAT PUMPS – NO ECONOMIZER WITH OPTIONAL ALARM BOARD & CB4000 COMMUNICATION BOARD.
Manual 2100-563C Page 31 of 40 ALARM WIRING Alarm relays can be wired for NO (close on alarm) or NC (open on alarm) strategy. Alarm relays can be used individually if there are enough available building alarm points, or can be arranged into smaller groups or even a single group so that all alarm capabilities can be utilized.
Manual 2100-563C Page 32 of 40 FIGURE 15 ALARM BOARD CONNECTIONS FOR NORMALLY CLOSED "NC" OPEN-ON-ALARM STRATEGY IMPOR T ANT! LED display boar d is shipped loo se to protect it fr om possible damage during installation of the wiring to main contr oller board and/or the alarm boar d.
Manual 2100-563C Page 33 of 40 FIGURE 16 ALARM BOARD CONNECTIONS FOR NORMALLY OPEN "NO" CLOSE-ON-ALARM STRATEGY IMPOR T ANT! LED display board is shipped loose to pr otect it fr om possible damage during installation of the wiring to main contr oller board and/or the alarm boar d.
Manual 2100-563C Page 34 of 40 PROGRAMMING INSTRUCTIONS To swap lead and lag unit positions, press the ADVANCE button. To enter the Program mode, press the PROGRAM button and release it when the message PROG appears on the display. When in Program mode, the DOWN and UP arrows are used to scroll through the programming steps.
Manual 2100-563C Page 35 of 40 7961-731 Comfort Mode Press “Comfort” button once to reset to 72F/22C Cooling and 68F/20C Heating for 1-hour . Display will flash during override period. Press 2nd-time to cancel during override if desired, or controller will automatically revert to selected SP after 1-hour .
Manual 2100-563C Page 36 of 40 FIGURE 17 PARTS LIST DESCRIPTION DIAGRAM MIS-2954 12 9 3 4 5 7 6 11 2 1 10 8.
Manual 2100-563C Page 37 of 40 . g w D . o N . o N t r a Pn o i t p i r c s e D0 0 0 4 C MA - 0 0 0 4 C MC A - 0 0 0 4 C MB - 0 0 0 4 C MC B - 0 0 0 4 C MA - 0 0 0 3 B AB - 0 0 0 3 B A 0 0 0 4 B C 1 4.
Manual 2100-563C Page 38 of 40 This page intentionally lef t blank..
Manual 2100-563C Page 39 of 40 This page intentionally lef t blank..
Manual 2100-563C Page 40 of 40 This page intentionally lef t blank..
An important point after buying a device Bard MC4000 (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Bard MC4000 yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Bard MC4000 - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Bard MC4000 you will learn all the available features of the product, as well as information on its operation. The information that you get Bard MC4000 will certainly help you make a decision on the purchase.
If you already are a holder of Bard MC4000, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Bard MC4000.
However, one of the most important roles played by the user manual is to help in solving problems with Bard MC4000. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Bard MC4000 along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center