Instruction/ maintenance manual of the product DC3002 Bard
Go to page of 22
Manual 2100-484E Page 1 of 22 DC3002 and DC3003 SOLID ST A TE LEAD/LAG CONTROLLER with DC F AN CONTROL INST ALLA TION INSTRUCTIONS & REPLACEMENT P ARTS LIST Manual No.: 2100-484E Supersedes: 2100-484D File: V ol. III T ab 19 Date: 08-29-1 1 Bard Manufacturing Company , Inc.
Manual 2100-484E Page 2 of 22 CONTENTS Getting Other Information and Publications 3 DC3000 General Information Shipping Damage .................................................. 4 General ...............................................................
Manual 2100-484E Page 3 of 22 Getting Other Information and Publications These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.
Manual 2100-484E Page 4 of 22 SHIPPING DAMAGE Upon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.
Manual 2100-484E Page 5 of 22 SPECIFICATIONS/FEATURES FOR BASIC CONTROLLER DC3000 Basic Controller •Input power: 18 to 32VAC, 60/50Hz, power is supplied from A/C #1 and/or A/C #2 •Isolation circui.
Manual 2100-484E Page 6 of 22 Note: All alarm relays are dry contacts rated 1A @ 24VAC, 120VAC or 150VDC. DC3002/3003 CONTROLLER CONNECTIONS Located on Main Controller Board Unit #1 C – 24V AC commo.
Manual 2100-484E Page 7 of 22 LOW VOLTAGE FIELD WIRING The DC3000 is powered from the air conditioners that it is controlling, 24VAC (18-32V) low voltage only. Circuitry in the DC3000 isolates the power supplies of all connected air conditioners so that no back feeds or phasing problems can occur.
Manual 2100-484E Page 8 of 22 SEQUENCE OF OPERATION – COOLING AIR CONDITIONERS – (NO ECONOMIZER) First stage cooling set point is the setting (SP) input into the controller. Factory default is 75F/24C. At Stage 1 cooling SP, the blower of the lead unit will come on (if not already operating because of continuous fan selection for lead unit).
Manual 2100-484E Page 9 of 22 SEQUENCE OF OPERATION – HEATING (AIR CONDITIONERS W/ELECTRIC HEAT) First stage heating set point is the dead band setting below first stage cooling set point (the SP entered into the program). The dead band is adjustable from 2-20F (1-10C), and the factory default is 10F (5C).
Manual 2100-484E Page 10 of 22 DC FAN CONTROL The primary reason the DC30002 or DC3003 controller system would be used is for additionally controlling a DC Fan ventilation system installed in the shelter in addition to controlling either 2 or 3 HV AC units.
Manual 2100-484E Page 11 of 22 FIGURE 1 DC3002 CONNECTION DIAGRAM 2 UNITS WITH ECONOMIZERS.
Manual 2100-484E Page 12 of 22 FIGURE 2 DC3002 CONNECTION DIAGRAM 2 UNITS NO ECONOMIZERS.
Manual 2100-484E Page 13 of 22 FIGURE 3 DC3003 CONNECTION DIAGRAMS 3 UNITS WITH ECONOMIZERS.
Manual 2100-484E Page 14 of 22 FIGURE 4 DC3003 CONNECTION DIAGRAMS 3 UNITS WITH ECONOMIZERS (NO ECONOMIZER A/C #3).
Manual 2100-484E Page 15 of 22 FIGURE 5 DC3003 CONNECTION DIAGRAMS 3 UNITS WITH NO ECONOMIZERS.
Manual 2100-484E Page 16 of 22 ALARM WIRING Alarm relays can be wired for NO (close on alarm) or NC (open on alarm) strategy. Alarm relays can be used individually if there are enough available building alarm points, or can be arranged into smaller groups or even a single group so that all alarm capabilities can be utilized.
Manual 2100-484E Page 17 of 22 FIGURE 6 ALARM BOARD CONNECTIONS FOR NORMALLY CLOSED "NC" OPEN-ON-ALARM STRATEGY.
Manual 2100-484E Page 18 of 22 FIGURE 7 ALARM BOARD CONNECTIONS FOR NORMALLY OPEN "NO" CLOSE-ON-ALARM STRATEGY.
Manual 2100-484E Page 19 of 22 PROGRAMMING INSTRUCTIONS To swap lead and lag unit positions, press the ADVANCE button. To enter the Program mode, press the PROGRAM button and release it when the message PROG appears on the display. When in Program mode, the DOWN and UP arrows are used to scroll through the programming steps.
Manual 2100-484E Page 20 of 22 7961-665C Cooling Heati ng 1st Stage 2nd Stage 3rd Stage 4th Stage 1st Stage 4th Stage 3rd Stage 2nd Stage Lead Unit Unit #1 Unit #2 Dehumid .
Manual 2100-484E Page 21 of 22 FIGURE 8 PARTS LIST DESCRIPTION DIAGRAM 5 7 3 4 6 9 2 11 SEXP- 445 B 8 1 10.
Manual 2100-484E Page 22 of 22 Parts List . o N . g w D. o N t r a Pn o i t p i r c s e D2 0 0 3 C D3 0 0 3 C D 14 - 3 4 3 - 7 2 1x o B l o r t n o CX X 27 3 0 - 2 1 6 8d r a o B r e l l o r t n o CX .
An important point after buying a device Bard DC3002 (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Bard DC3002 yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Bard DC3002 - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Bard DC3002 you will learn all the available features of the product, as well as information on its operation. The information that you get Bard DC3002 will certainly help you make a decision on the purchase.
If you already are a holder of Bard DC3002, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Bard DC3002.
However, one of the most important roles played by the user manual is to help in solving problems with Bard DC3002. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Bard DC3002 along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center