Instruction/ maintenance manual of the product XPC 1624 Studer Innotec
Go to page of 22
STUDER INNOTEC XP- COMPACT User and installer Manual Combi Inverter, Battery charger and Transfersystem XP-COMPACT XPC 1112 XP-COMPACT XPC 1624 XP-COMPACT XPC 1648 Remote control RCC-01 Temperature sensor CT-35 Solar charge controller XPCxxxx-S AC cable cover CFC-01 IP-23 top cover C-IP23 User manual XP-COMPACT V2.
STUDER INNOTEC XP- COMPACT Summary 1 General Information ............................................................................................................ ..... 3 1.1 O PERATING INSTRUCTIONS .................................................
STUDER INNOTEC XP- COMPACT 4.8.3 Delaye d mode of th e Transfer System ............................................................................................ ............. 15 4.9 T HE S OLAR CHARGE CONTROLLER ( OPTION ) .........................
STUDER INNOTEC XP- COMPACT 1 General Information 1.1 Operating instructions This manual is a part of the delivery package of every XP-COMPACT inverter-charger.
STUDER INNOTEC XP- COMPACT 1.5 Precautions This manual must be readily available for the user at all times. The user must be familiar with the precautions and safety aspects. During operation of XP-COMPACT, high voltages are generated at the connections and inside of the appliance which could be deadly fatal.
STUDER INNOTEC XP- COMPACT 2 Introduction The XP-COMPACT is a sine wave inverter with integrated battery charger and solar charge con- troller with many additional functions, it has been developed to be used as stand-alone (no grid feeding) AC provider, or as continuous / break-free current supply provider (UPS).
STUDER INNOTEC XP- COMPACT technical specification (chap.6). The battery ch arger is meant for the lead-acid and lead-gel batter- ies. Thanks to the floating charge system the ba ttery can remain continuously connected.
STUDER INNOTEC XP- COMPACT 2.3.3 Connection in parallel and in serie 12V 12V 12V 12V 24V 3 Mounting and installing 3.1 Installation place The location of the XP-COMPACT must be chosen by the following.
STUDER INNOTEC XP- COMPACT Connecting must be done by qualified staff. Material such as cab l e, connectors and distribution boxes, fuses etc. used in the installation must comply with the respective valid low-voltage installa- tion rules and regulations.
STUDER INNOTEC XP- COMPACT 3.6 Cabling/wiring Connecting of the XP-COMPACT is a very important step in the installation. You must take care that all connecting work is carried out in a clean and correct manner and that under no circum- stance a cable is connected to a wrong terminal.
STUDER INNOTEC XP- COMPACT 3.6.6 Connection to Auxiliary Contact On these three terminals is a potential free change-over contact. The maximal permitted current and voltage for this is 16A/250Vac. The LED 5 “Contac t active” shows the position of them: alight means active and off means non-active .
STUDER INNOTEC XP- COMPACT 4.2 Display and control parameters on remote control panel (optional) 16 0 OFF AC OUT Over Temp. Overload AC IN SOLAR CHARGE Contact manual Contact active Program COMPA CT A.
STUDER INNOTEC XP- COMPACT 13 OFF XP-COMPACT is turned off. Turn- ing it back on is only possible manually. XP-COMPACT is for the time be- ing turned off.
STUDER INNOTEC XP- COMPACT User manual XP-COMPACT V2.0 E 13 perature synchronizes the relay with the alarm signal. In this way, for exa m ple, an emergency back up system can be started without any break in the energy supply. 4.6.4 Battery Condition Deep discharging of the lead-acid batteries leads to high losses in capacity and early aging.
STUDER INNOTEC XP- COMPACT 4.7.2 Equalization charging Before you program the XP-COMPACT for Equalizat ion-charge you must check with your supplier that the batteries are suitable for this process. Equalization is recommended for the lead-acid batteries in order to mix well the electrolyte fluid and to clean the lead plates.
STUDER INNOTEC XP- COMPACT the transfer contact is active, then you have at the output AC OUT the same voltag e as that at the input. This voltage can not be modified by the XP-COMPACT! 4.8.1 Set the transfer voltage threshold The voltage threshold of the transfer is factory settled at 200Vac.
STUDER INNOTEC XP- COMPACT 4.10 The Multifunctional Contact In the XP-COMPACT there is a built-in power rel ay. The potential-free change-over contact (NO – NC) of this power relay is connected to the screw terminal AUX CONTACT. Maximum Contact load: 230V ac /12Vdc/24Vdc/16Amp 60Vdc/3 Amp.
STUDER INNOTEC XP- COMPACT 5.3 Battery Condition Built-in microprocessor calculates the actual state of charge of the battery and displays it on L ED 15 – 18. The LED 14 is lit when the system is carrying out a charge cycle with equalization. The voltage levels and charge characteristics can be changed through Programming.
STUDER INNOTEC XP- COMPACT 6.1 Standard setting The XP-COMPACT is delivered with the following default setting: 6.1.1 Battery voltage Low voltage 11.6V / 23.2V / 46.4V Float Charge 13.5V / 27.0V / 54.0V End of Charge Voltage 14.4V / 28.8V / 57.6V Equalization 15.
STUDER INNOTEC XP- COMPACT table 6.3.1. If desired, repeat the operation with any other parameter (voltage or time) to be changed. If during 10 seconds no buttons are pressed, the selected values are automatically stored and the XP-COMPACT switches back in to the normal operating status.
STUDER INNOTEC XP- COMPACT 6.4.3.3 Second priority cut-off The Auxiliary Contact can use to cut-off second priori ty load with the criteria of the battery status or overtemp. One of the 4 LED 15 to 18 or 10 will be chosen as the cut off criteria. The second prior- ity loads will be supply only if the ba ttery as a sufficient residual capacity 6.
STUDER INNOTEC XP- COMPACT User manual XP-COMPACT V2.0 E 21 9 Technical Data Model XPC1112 XPC1624 XPC1648 Inverter Nominal battery voltage 12 V 24 V 48 V Input voltage range 9.5 – 17 V 19 – 34 V 38 – 68 V Nominal power 1100 W 1600 W 1600 W Maximum power load 30 min.
An important point after buying a device Studer Innotec XPC 1624 (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Studer Innotec XPC 1624 yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Studer Innotec XPC 1624 - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Studer Innotec XPC 1624 you will learn all the available features of the product, as well as information on its operation. The information that you get Studer Innotec XPC 1624 will certainly help you make a decision on the purchase.
If you already are a holder of Studer Innotec XPC 1624, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Studer Innotec XPC 1624.
However, one of the most important roles played by the user manual is to help in solving problems with Studer Innotec XPC 1624. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Studer Innotec XPC 1624 along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center