3 Contents Fluid Cooler Location ............................................................................. 5 Fluid Cooler Shipment ............................................................................ 6 Receiving Fluid Cooler ..............
4 Preparation The Marley MH Fluid Cooler with CoolBoost™, purchased for this instal- lation repr esents the current state of the art in crossflow , induced draft fluid cooler design. Thermally and operationally , it is the most efficient fluid cooler of its class.
5 Preparation It is not intended nor assumed that access to the fan deck on single-ow models—Models MHF702 thru MHF705—is needed or necessary . Those are only some of the safety issues that may arise in the design process.
6 The fluid cooler must be located at such distance and direction to avoid the possibility of contaminated fluid cooler discharge air be - ingdrawn intobuilding freshair intakeducts.
7 Hoisting clips are provided for ease of unloading and positioning the uid cooler . For overheadlifts or whereadditional safety is required, safety slings should also be placed under the fluid cooler modules.
8 Fasteners and components provided by others that are to be attached to the tower must be compatible with the cooling tower materials— i.e. fasteners in a stainless steel cold water basin must be stainless steel. 6. Attach pr ocess fluid supply and return piping to the coil.
9 • Do not start the motor more than six times per hour . Short cycling the tower will cause fuses, breakers or O.L.s to operate and will decrease motor life. When using a two-speed starter: • Motor rotation must be the same at slow speed and high speed.
10 equipment. Electrical savings can be large during periods of low ambient temperature when the cooling requirement can be satisfied at reduced speeds. T o benefit from these advantages, it is important that the drive be installed correctly . Marley supplies VFD and VFD contr ols specically designed for our cooling products.
11 Mechanical Equipment: The fluid cooler is designed to operate at full speed and half speed. W arranty is void if the tower is operated at speeds which cause damagingvibrationstothe towerandassociatedequipment.
12 It is essential that the fan cylinder and fan guard be installed in ac - cordance with the drawings shipped with the tower . Do not force the fan cylinder out of round. 4. Momentarily bump (energize) the motor(s) and observe r otation of the fan(s).
13 Fluid Cooler Start-Up Among other sources, outbreaks of Legionnaires’ Disease have report - edly been traced to cooling towers and fluid coolers.
14 7. While operating the recir culating water pump(s) and prior to operat- ing the cooling tower fan, execute one of the two alter native biocidal treatment pr ograms described in the following: • Resume tr eatment with the biocide which had been used prior to shutdown.
15 Fluid Cooler Operation General: The cold process fluid temperatur e obtained from an operating fluid cooler will vary with the following influences: 1. Heat load: With the fan in full operation, if the heat load increases, the cold process fluid temperature will rise.
16 4. Air flow rate: Reducing air flow thr ough th e fluid co oler causes the col d process fluid temperature to rise. This is the recommended method by which to control leaving pr ocess fluid temperature.
17 Slushy , transitor y ice forms routinely in the colder regions of the fill of low temperature towers, and is visible through the tower louvers. Such ice normally has no adverse effect on fluid cooler operation, but its appearance should be a signal to the operator to undertake ice control procedures.
18 Reversal may be at either full or half speed; however , reversal at half speed is recommended. Reverse operation of the fan should be used sparingly and should only be used to control ice, not to prevent it. Reverse fan operation should not need to exceed 1 or 2 minutes.
19 When the use of industrial antifreeze solutions is not possible, the system must be operated to meet both of the following conditions. 1. Maintain sufficient flow rate through the coil. 2. Maintain sufficient heat load on the process fluid. Fluid exiting the coil must be maintained at or above 7°C.
20 W ater T reatment and Blowdown Maintaining W ater Quality: The steel used in MH Fluid Cooler's has been galvanized with a heavy zinc coating averaging .051mm in thickness. Other materials used (PVC fill, drift eliminators, and louvers, aluminum fans, cast iron Geareducer , etc.
21 Fluid Cooler Cleaning: Any evaporative-type uid cooler must be thoroughly cleaned on a regular basis to minimize the growth of bacteria, including Legionella Pneumophila, to avoid the risk of sickness or death.
22 (percent of flow) required to maintain differ ent concentrations with various cooling ranges*: * Range = Differ ence between hot water temperature and cold water temperature. EXAMPLE: 44.2 L/s circulating rate, 10°C cooling range. T o maintain 4 concentrations, the required blowdown is 0.
23 Maintenance See Figure 3 for MH Fluid Cooler models MHF706 and MHF707.The belts are adjusted by turning the threaded rod. Before tightening or loosening the belt, the double nuts holding the motor support in place must be loosened. There ar e two jam nuts at the end of the rod next to the casing.
24 Maintenance sion is the lowest tension at which the belt will not slip under peak load conditions. Check tension frequently during the first 24-48 hours of run-in operation. Overtensioning shortens belt and bearing life. Keep belts free from foreign material which may cause slipping.
25 Fluid Cooler Maintenance Some maintenance procedur es may require maintenance personnel to enter the fluid cooler . Each cased face of the fluid cooler has a door for access to the interior of the tower . The optional fan deck ladder—models MHF706 and MHF707— is de- signed and intended solely for personnel to gain access to the fan deck.
26 W eekly: Inspect for bacterial growth and general operation conditions. Bacterial growth should be reported to your water treatment expert for immediate attention. Monthly (W eekly at start up): Observe, touch, and listen to the fluid cooler . Become accustomed to its normal appearance, sound, and level of vibration.
27 Clean and disinfect cooling tower with biocides. Systems with biofouling, high general bacterial counts, or positive cultures of legionella may requir e additional cleaning. Refer to “Fluid Cooler Cleaning” section—page 21. Consult your water treatment expert as to prudent biological evaluation testing.
28 wire. 3. Insert gr ease fittings in grease fill openings and add gr ease until gr ease is forced out thr ough relief openings. 4. Replace fill plugs and operate mechanical equipment 30 minutes to one hour to pur ge excess grease at grease r elief opening.
29 Maintenance bright metal can be exposed by cleaning, consider that the galvanizing has remained effective. Unless there is evidence of a generalized failure of the galvanizing, localized touch-up should be all that is requir ed.
30 repr esentative for additional information. SPX Cooling T echnologies Services Our interest in your MH Fluid Cooler does not end with the sale. Having conceived, designed, and manufactured the most reliable and longest- lasting fluid cooler of its class, we want to make sure that you gain the maximum possible benefit from its pur chase.
31 Maintenance Schedule Maintenance Service Monthly Semi-annually Seasonal Startup or Annually Inspect General Condition and Operation x x Observe Operation of: Mechanical–motor , fan and drive mech.
32 T roubleshooting T rouble Cause Remedy Motor will not start Power not available at motor terminals Check power at starter . Correct any bad connections between the control apparatus and the motor . Check starter contacts and control cir cuit. Reset overloads, close contacts, reset tripped switches or r eplace failed control switches.
33 T roubleshooting T rouble Cause Remedy Geareducer noise. (If equipped). Geareducer bearings If new , see if noise disappears after one week of operation. Drain flush, and refill Gear educer oil. See Geareducer User Manual. If still noisy , replace.
34 Additional Information the norm. This service is not intended to replace the important function performed by your maintenance staff. Their attention assures the fluid coolers’ s routine operating performance, and is invaluable.
.
sea_M05-116E U NIT 505, B L O CK B, P HI LEO DAMANSARA 2 | NO. 15 JALAN 16/11, OF F JALAN D AMAN SARA | 46350 PET ALIN G JA Y A, MALASIA | 60 3 7 665 1018 | spxcooling.com In the interest of technological progress, all products are subject to design and/or material c hange without notice.
An important point after buying a device SPX Cooling Technologies MHF702 (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought SPX Cooling Technologies MHF702 yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data SPX Cooling Technologies MHF702 - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, SPX Cooling Technologies MHF702 you will learn all the available features of the product, as well as information on its operation. The information that you get SPX Cooling Technologies MHF702 will certainly help you make a decision on the purchase.
If you already are a holder of SPX Cooling Technologies MHF702, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime SPX Cooling Technologies MHF702.
However, one of the most important roles played by the user manual is to help in solving problems with SPX Cooling Technologies MHF702. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device SPX Cooling Technologies MHF702 along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center