Instruction/ maintenance manual of the product FM200 Sea-Fire
Go to page of 14
FM200 ® MODEL FT FIRE EXTINGUISHERS INST ALLA TION INSTRUCTIONS OWNER’S MANUAL THIS MANUAL IS AN INTEGRAL P AR T OF THE SYSTEM AND AS SUCH, THE EXTINGUISHER MUST BE INST ALLED AND MAINT AINED ACCORDINGL Y . READ AND COMPL Y WITH THESE INSTRUCTIONS, W ARNINGS AND LIMIT A TIONS BEFORE INST ALLING.
W ARNING CONCENTRA TED AGENT AND BY-PRODUCT OF APPLICA TION TO FIRE ARE T OXIC. A VOID BREA THING OF FUMES OR PROLONGED EXPOSURE. ACCIDENT AL DIS- CHARGE MA Y OCCUR DURING HANDLING OR INST ALLA TION OF THIS DEVICE, READ AND COMPL Y WITH INSTRUCTIONS, WARNINGS, AND LIMIT A TIONS CONT AINED IN THIS MANUAL.
REMINDER: Sea-Fire systems shall be considered as supplementary to the number of portable fire extinguishers required on-board and are designed and intended for enclosed unoccupied compartment installations that are not subject to direct weather or water .
OTHER APPLICA TIONS • Engine Compartments (maximum 150 cubic feet) • Bow Thrusters • Small Generator Set Enclosures • Consoles • Electrical Enclosures • Flammable Liquid Storage Areas • Pump Enclosures • Alternative Fuel Storage Areas In case of a fire and system discharged, the electrical supply to the motor must be discon- nected.
Figure 5 Step 8 Secure the detection tubing to the bulkhead by using the clips and screws supplied. Nylon wire ties may be used in lieu of the clips and screws.
Figure 6 THE FT EXTINGUISHER INST ALLA TION IS COMPLETE. INDICA TOR LIGHT OPERA TION All Sea-Fire extinguishers approved for marine applications are packaged with an indicator light and escutcheon. ‘‘The U.S. Coast Guard approval requires an indicator light if this unit is installed for the protection of a boat’s engine compartment.
ELECTRICAL SWITCH INDICA TOR LIGHT GROUND IN-LINE FUSE IGNITION IGNITION SWITCH ST ARTER BA TTERY Figure 9 Figure 3 WHILE MAKING ELECTRICAL CONNECTION CAN RESUL T IN INJUR Y FROM FIRE OR ELECTRICAL BURNS. The indicator light is rated for 12 VDC (contact factory for other voltages).
Before operating the protected vessel, visually inspect pressure gauge for compliance and ensure the supervisory (indicator) light is lit. If gauge reads low in pressure, and or the indica- tor light is extinguished, remove, and replace the system immediately .
CONDITIONS All Sea-Fire products are tested after manufacture and shipped in perfect working order . Damage noted upon receipt of shipment should be addressed as a shipping claim, the filing of which is the sole responsibility of the consignee for which the total compensatory award will be limited to that appropriated by the carrier .
ALL FT (STINGER) MODELS ARE APPROVED FOR VERTICAL MOUNTING ONL Y . INTENDED OPERA TING TEMPERA TURE RANGE : 32°F –130°F (0°C – 54°C ) ST ANDARD EQUIPMENT LIST SUPPLIED WITH EACH SYSTEM 1. ONE TUBING KIT , P ART # 130-121 – 10 FOOT TUBE OR 130-122 – 15 FOOT TUBE.
FG/FD/FT/MD/R/C-MODEL Fire Extinguisher MSDS No. SF002 MA TERIAL SAFETY DA T A SHEET Section 1 — Company and Chemical Identification MET ALCRAFT/SEA-FIRE MARINE EMERGENCY PHONE: 1-800-535-5053 9331-A PHILADELPHIA ROAD PHONE: 1-800-445-7680 BAL TIMORE, MARYLAND 21237DA TE: NOVEMBER 10, 2005 http://www .
Section 7 — Handling and Storage Handle, transport and store carefully and securely to avoid accidental knocking over or other severe physical impacts.
Section 15 — Regulatory Information U.S. Federal Regulations: The components of this product are either on the TSCA Inventory or exempt (i.e. impurities, a polymer complying with the exemption rule at 40 CFR 723.
SEA-FIRE MARINE SEA-FIRE EUROPE L TD Division of Metalcraft Inc. Unit 7. io Centre. Stephenson Road 9331-A Philadelphia Road Fareham, Hampshire Baltimore, Maryland 21237 USA PO15 5RU, United Kingdom Website: www .
An important point after buying a device Sea-Fire FM200 (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Sea-Fire FM200 yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Sea-Fire FM200 - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Sea-Fire FM200 you will learn all the available features of the product, as well as information on its operation. The information that you get Sea-Fire FM200 will certainly help you make a decision on the purchase.
If you already are a holder of Sea-Fire FM200, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Sea-Fire FM200.
However, one of the most important roles played by the user manual is to help in solving problems with Sea-Fire FM200. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Sea-Fire FM200 along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center