Instruction/ maintenance manual of the product U37-NG NATURAL GAS Regency
Go to page of 32
WARNING: If the information in these instructions are not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life. FOR YOUR SAFETY Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
2 U37 Regency ULTIMATE Rear Vent Direct Vent Freestanding Gas Heater To the New Owner: Congratulations! You are the owner of a state-of-the-art ULTIMATE Rear Vent Direct Vent Gas Stove by FPI Fireplace Products International.
U37 Regency ULTIMATE Rear Vent Direct Vent Freestanding Gas Heater 3 T ABLE OF CONTENTS Page Page Louver Installation ...................................................... 2 0 Optional Wall Thermostat .......................................... 2 0 Optional Remote Control Installation .
4 U37 Regency ULTIMATE Rear Vent Direct Vent Freestanding Gas Heater This is a copy of the label that accompanies each ULTIMATE Rear Vent Direct Vent Free- standing Gas Stove. We have printed a copy of SAFETY LABEL the contents here for your review. The safety label is located on the inside of the drop down pedestal door.
U37 Regency ULTIMATE Rear Vent Direct Vent Freestanding Gas Heater 5 IMPORT ANT : SA VE THESE INSTRUCTIONS The ULTIMATE Rear Vent Direct Vent Free- standing Gas Stove must be installed in accord- ance with these instructions. Carefully read all the instructions in this manual first.
6 U37 Regency ULTIMATE Rear Vent Direct Vent Freestanding Gas Heater COMBUSTION AND VENTILA TION AIR The combustion air from this appliance is drawn from outside the building through the outer flue. Extra provision for combustion air inside the room is not required.
U37 Regency ULTIMATE Rear Vent Direct Vent Freestanding Gas Heater 7 INST ALLA TION EXTERIOR VENT TERMINAL LOCA TIONS . B B B B A C V V V V V V V A A V Fixed Fixed Openable Closed Closed Openable N L .
8 U37 Regency ULTIMATE Rear Vent Direct Vent Freestanding Gas Heater PLANNING YOUR VENTING INST ALLA TION INST ALLA TION IMPORTANT Read all instructions carefully before starting the installation. Failure to follow these instruc- tions may create a fire or other safety hazard, and will void the warranty.
U37 Regency ULTIMATE Rear Vent Direct Vent Freestanding Gas Heater 9 INST ALLA TION RIGID PIPE VENTING COMPONENTS LIST All Simpson Dura-Vent components are available directly from FPI.
10 U37 Regency ULTIMATE Rear Vent Direct Vent Freestanding Gas Heater INST ALLA TION RIGID PIPE VENTING - VERTICAL TERMINA TIONS FOR BOTH RESIDENTIAL & MANUF ACTURED HOMES/MOBILE HOMES Offset to V.
U37 Regency ULTIMATE Rear Vent Direct Vent Freestanding Gas Heater 11 INST ALLA TION Diagram 2a HORIZONT AL INST ALLA TIONS Diagram 1 *Dia 2a & 2b: As specified in CGA B149 Instal- lation Code. Local codes or regulations may require different clearances.
12 U37 Regency ULTIMATE Rear Vent Direct Vent Freestanding Gas Heater Diagram 5 Diagram 4 Below Grade Snorkel Installation If the Snorkel Termination must be in- stalled below grade, i.e. basement ap- plication, proper drainage must be pro- vided to prevent water from entering the Snorkel Termination.
U37 Regency ULTIMATE Rear Vent Direct Vent Freestanding Gas Heater 13 Flex Liner Exhaust Flue Air Intake Co-Linear Flex Adapter with Kit# 946-563 Co-linear DV V ertical T ermination Cap # 946-529 Inne.
14 U37 Regency ULTIMATE Rear Vent Direct Vent Freestanding Gas Heater CONVERTING A CLASS-A MET AL CHIMNEY OR MASONR Y CHIMNEY T O A DIRECT VENT SYSTEM General There are two different types of direct vent conversion systems listed below. Follow the appropriate directions for your installation.
U37 Regency ULTIMATE Rear Vent Direct Vent Freestanding Gas Heater 15 Converting a Masonry Chimney Important: The existing masonry flue opening needs to have an area of at least a 36 sq.
16 U37 Regency ULTIMATE Rear Vent Direct Vent Freestanding Gas Heater INST ALLA TION Burner Orifice Conversion Kit from Natural Gas to Propane THIS CONVERSION MUST BE DONE BY A QUALIFIED GAS FITTER IF IN DOUBT DO NOT DO THIS CONVERSION !! Conversion Kit # 680-969 Contains: Qty.
U37 Regency ULTIMATE Rear Vent Direct Vent Freestanding Gas Heater 17 INST ALLA TION AERA TION ADJUSTMENT The burner aeration is factory set but may need adjusting due to either the local gas supply, air supply or altitude.
18 U37 Regency ULTIMATE Rear Vent Direct Vent Freestanding Gas Heater Cutout Pin Notch D)02-46 B)02-56 A)02-65 E)02-45 Bracket A)02-65 The bottom right edge of Log G)02-48 must sit snugly against the bracket Side View G)02-48 E)02-45 F)02-47 7) Place the Left Top Log D)02-46 on the pin on Log B)02-56 and on top of the cutout on Log A)02-65.
U37 Regency ULTIMATE Rear Vent Direct Vent Freestanding Gas Heater 19 INST ALLA TION GAS PIPE PRESSURE TESTING The appliance must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig.
20 U37 Regency ULTIMATE Rear Vent Direct Vent Freestanding Gas Heater OPTIONAL W ALL THERMOST A T A wall thermostat may be installed if desired. Connect the wires as per the wiring diagrams. Note that the wires are connected to the "TH" on the gas valve.
U37 Regency ULTIMATE Rear Vent Direct Vent Freestanding Gas Heater 21 WIRING DIAGRAM This heater does not require a 120V A.C. supply for operation. In case of a power failure, the burner switch and the optional remote control/ thermostat will continue to operate.
22 U37 Regency ULTIMATE Rear Vent Direct Vent Freestanding Gas Heater OPERA TING INSTRUCTIONS OPERA TING INSTRUCTIONS 1) Read and understand these instructions before operating this appliance. 2) Check to see that all wiring is correct and enclosed to prevent possible shock.
U37 Regency ULTIMATE Rear Vent Direct Vent Freestanding Gas Heater 23 COPY OF THE LIGHTING PLA TE INSTRUCTIONS OPERA TING INSTRUCTIONS 1 ) Push in the gas control knob slightly and turn clockwise to “OFF”.
24 U37 Regency ULTIMATE Rear Vent Direct Vent Freestanding Gas Heater MAINTENANCE MAINTENANCE INSTRUCTIONS 1) Always turn off the valve before cleaning. For relighting, refer to lighting instructions. Keep the burner and control compartment clean by brushing and vacuuming at least once a year.
U37 Regency ULTIMATE Rear Vent Direct Vent Freestanding Gas Heater 25 MAINTENANCE LA TCH ADJUSTMENT The door latch may require adjustment as the door gasket material compresses after a few fires and after glass replacement. Turn the handle on the adjustable catch to tighten or loosen the latch.
26 U37 Regency ULTIMATE Rear Vent Direct Vent Freestanding Gas Heater REMOVING VAL VE If your valve requires maintenance or replace- ment, use the following instructions: Note: Always close off the gas supply before removing the valve. 1) Open front pedestal door.
U37 Regency ULTIMATE Rear Vent Direct Vent Freestanding Gas Heater 27 4) Remove the two outside frame pieces by removing two screws per side. See dia- gram below.
28 U37 Regency ULTIMATE Rear Vent Direct Vent Freestanding Gas Heater P ARTS LIST 1 ) 560-920 Louver Assy - Gold 560-921 Louver Assy - Brush Nickel 560-922 Louver Assy - Black 9 ) 730-560 Relief Door .
U37 Regency ULTIMATE Rear Vent Direct Vent Freestanding Gas Heater 29 P ARTS LIST U37 BURNER & LOG ASSEMBL Y 51) 910-241 Bu rn er ON/ OF F S wi tc h (3-way) 52) 910-190 Piezo Ignitor & Nut 53).
30 U37 Regency ULTIMATE Rear Vent Direct Vent Freestanding Gas Heater U37 DOOR ASSEMBLIES Part # Description 730-923 Brush Nickel Mitred Door - Complete 730-924 Gold Mitred Door - Complete 730-926 Bla.
U37 Regency ULTIMATE Rear Vent Direct Vent Freestanding Gas Heater 31 W ARRANTY Regency Fireplace Products are designed with reliability and simplicity in mind. In addition, our internal Quality Assurance Team carefully inspects each unit thoroughly before it leaves our facility.
Installer: Please complete the following information Dealer Name & Address: ______________________________________________ __________________________________________________________________ Instal.
An important point after buying a device Regency U37-NG NATURAL GAS (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Regency U37-NG NATURAL GAS yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Regency U37-NG NATURAL GAS - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Regency U37-NG NATURAL GAS you will learn all the available features of the product, as well as information on its operation. The information that you get Regency U37-NG NATURAL GAS will certainly help you make a decision on the purchase.
If you already are a holder of Regency U37-NG NATURAL GAS, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Regency U37-NG NATURAL GAS.
However, one of the most important roles played by the user manual is to help in solving problems with Regency U37-NG NATURAL GAS. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Regency U37-NG NATURAL GAS along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center