Instruction/ maintenance manual of the product MAXIM INTEGRATED WATER HEATING SYSTEM PVI Industries
Go to page of 12
PV500 - 17 05 - 2000 Section 17 1 INSTALLATION & MAINTENANCE MANUAL FOR MAXIM INTEGRATED WATER HEATING SYSTEM TABLE OF CONTENTS Start - up Procedures 2 Maintenance & Safety Inspections 3 - 5 Wiring Diagrams 6,7 Burner 8 Burner Start - up 9 - 12 Burner Troubleshooting 13.
PV500 - 17 05 - 2000 Section 17 2 START - UP PROCEDURES CAUTION: DO NOT RELIGHT PILOT OR START BURNER WITH COMBUSTION CHAMBER FULL OF GAS OR OI L VAPOR, OR WITH VERY HOT COMBUSTION CHAMBER. 1. Study the burner start - up information included in this manual carefully.
PV500 - 17 05 - 2000 Section 17 3 MAXIM MAINTENANCE AND SAFETY INSPECTIONS 1. Establ ish a preventive maintenance program to assure a longer water heater life. 2. The tank should be flushed at two - or three - month intervals depending on water conditions in your location.
PV500 - 17 05 - 2000 Section 17 4 MAXIM MAINTENANCE AND SAFETY INSPECTIONS (continued) Periodic Inspection of Operation Components (continued) CAUTION: THE RELIEF VA LVE IS A PRIMARY SAFETY DEVICE.
PV500 - 17 05 - 2000 Section 17 5 MAINTENANCE & SAFETY INSPECTION REPORT DATE BURNER INSPECTION COMBUSTION ANALYSIS TANK INSPECTION TANK FLUSH & CLEANOUT TANK FITTING INSPECTION VENT INSPECTIO.
PV500 - 17 05 - 2000 Section 17 6 MAXIM AXIAL FLOW GAS BURNER CARBON MONOXIDE WARNING: CAUTION: IMPROPER COMBUSTION MAY CAUSE SERIOUS INJURY. PVI recommends a s easonal or annual combustion check - out be performed by a qualified service agency to ensure safe and efficient operation.
PV500 - 17 05 - 2000 Section 17 7 MAXIM AXIAL FLOW GAS BURNER START - UP (Refer to Figure 17 - 2, page 6 to identify burner parts) 1. Remove the enclosure panel cover on the water heater or boiler to expose the control circuit. A wiring diagram, included in this packet, will show the controls used in our circuitry.
PV500 - 17 05 - 2000 Section 17 8 MAXIM AXIAL FLOW GAS BURNER START - UP (continued) PRESSURE PLATE Set up and Tolerances Figure 17 - 3 13. Connect a test meter to the control for reading the flame response signal. NOTE: Some controls read the flame signal in micro amps and some in volts DC.
PV500 - 17 05 - 2000 Section 17 9 MAXIM AXIAL FLOW GAS BURNER START - UP (continued) This section pertains to MC120 control only. When the blower motor starts, the air proving light on the MC - 120 should be on. This indicates a positive air flow condition.
PV500 - 17 05 - 2000 Section 17 10 MAXIM AXIAL FLOW GAS BURNER START - UP (continued) 17. Check flue gases with a flue analyzer to make final settings of the air shutter. a. The readings need to be taken from a hole in the vent several inches above the heater vent connection, but before draft regulator.
PV500 - 17 05 - 2000 Section 17 11 MAXIM TROUBLESHOOTING SUGGESTIONS AXIAL FLOW GAS BURNER 1. BURNER FAILS TO START Defective On/Off switch. Replace switch. A. Control circuit has an open control contact. Check limits, low water cutoff, proof of closure switch and others as applicable.
PV500 - 17 05 - 2000 Section 17 12 MAXIM TROUBLESHOOTING SUGGESTIONS AXIAL FLOW GAS BURNER (continued) C. Defective automatic main or auxiliary gas shut off valves. Check electrical circuitry to valves. Replace valves or correct circuitry a s required.
An important point after buying a device PVI Industries MAXIM INTEGRATED WATER HEATING SYSTEM (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought PVI Industries MAXIM INTEGRATED WATER HEATING SYSTEM yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data PVI Industries MAXIM INTEGRATED WATER HEATING SYSTEM - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, PVI Industries MAXIM INTEGRATED WATER HEATING SYSTEM you will learn all the available features of the product, as well as information on its operation. The information that you get PVI Industries MAXIM INTEGRATED WATER HEATING SYSTEM will certainly help you make a decision on the purchase.
If you already are a holder of PVI Industries MAXIM INTEGRATED WATER HEATING SYSTEM, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime PVI Industries MAXIM INTEGRATED WATER HEATING SYSTEM.
However, one of the most important roles played by the user manual is to help in solving problems with PVI Industries MAXIM INTEGRATED WATER HEATING SYSTEM. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device PVI Industries MAXIM INTEGRATED WATER HEATING SYSTEM along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center