Manual No. H-502 2008-02-18 NHTC NORTEC LINKS 2 OPTIONS Inst allation Manual TM.
2008-02-18 PROPRIETARY NOTICE This document and the info rmation disclosed herei n are propriet ary data of W AL TER MEIER L TD. Neither this document nor the information cont ained herein shall be reproduced used, or disclosed to others without the written authoriza tion of W AL TER MEIER L TD.
2008-02-18 TABLE OF CONTENTS Subject Page 10-00 INT RODUCT ION 1. OVERVIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 10-10 INSTALLATIO N PROCEDURES 1.
2008-02-18 LIST OF FIGURES Figure Page 10-10 INST ALLATION Figure 1. Sample Humidification Applicati ons - Room-Sensed %R H Feedback with Du ct Hi-Limit Sensing . 16 Figure 2. Sample Humidification Applica tions - Control Fe edback (0-100%) with Duct Hi-Limit Sensing .
2008-02-18 THIS PAGE INTENTIONALLY LEFT BLANK.
10-00 Page 1 2008-02-18 10-00 INTRODUCTION.
10-00 Page 2 2008-02-18 (1) OVERVIEW (1) The NHTC Nortec LINKS 2 Option allows for the integration of a NHTC Series humidifier within a BACnet, Johnson N2 or LonWorks network and allows those units to concurrently be monitored via the Nortec OnLine interface.
10-10 Page 1 2008-02-18 10-10 INSTALLATION.
10-10 Page 2 2008-02-18 (1) NETWORKING (1) It is possible to network up to a maximum of 8 units to a single LINKS 2. Since each unit is separately addressed, it is possible to monitor and control each unit individually. Different networking configurations may be achieved and are mostly dependant on the type of network present at the site.
10-10 Page 3 2008-02-18 (2) WIRING (A) BACNET/MSTP, JOHNSON N2, AND LONWORKS (1) The necessary internal wiring for the Gateway is already present except for the BMS network connection that can be made via twisted-pair at terminals A and B.
10-10 Page 4 2008-02-18 (3) GATEWAY CONFIGURATION (1) Protocol configuration is made at the factory, prior to final testing. Baud rates are also adjusted to the following values: Table 2. Baud Rates Protocol Default Baud Rates BACnet MS/TP 38.4 kbps BACnet / IP 10BaseT Johnson N2 9.
10-10 Page 5 2008-02-18 (5) VARIABLE DEFINITION IMPORTANT: In the variable name, “_ x ” denotes the humidifier number. If there is only one GSTC humidifier, all variable names will end in “_1”. If two units are networked together (see Figure 4), the second unit’s variable names will end in “_2”.
10-10 Page 6 2008-02-18 Table 3. Variable Definitions Variable Name R=Read W=Write Description LonWorks SNVT nvoHourOpt_x R Analogue Value Indicates the number of hours the humidifier cylinder has bee n in operation. SNVT_count_inc nvoCapLimit R Analogue Value Reads to capacity limitation applied to the unit output.
10-10 Page 7 2008-02-18 Variable Name R=Read W=Write Description LonWorks SNVT nvoFault_ x R Binary Value Indicates unit fault status. 0=no fault, 1=fault. SNVT_switch nvoHWSensor_ x R Binary Value Indicates if a high-water level condition exists in the humidifier cylinder.
10-10 Page 8 2008-02-18 Table 4. Humidifier Variable Addresses Unit #1 NHTC LINKS 2 Variable Listing Default BACnet/IP Address: 192.168.10.11; Subnet: 255.
10-10 Page 9 2008-02-18 Table 5. Humidifier Variable Addresses Unit #2 Unit #2 BACnet Lonworks N2 Variable Name Type Instance SNVT SNVT # NV Index Type Instance nvoHourOpt_2 AV 16 time_hour 124 23 AI .
10-10 Page 10 2008-02-18 Table 6. Humidifier Variable Addresses Unit #3 Unit #3 BACnet Lonworks N2 Variable Name Type Instance SNVT SNVT # Element Type Instance nvoHourOpt_3 AV 31 time_hour 124 45 AI .
10-10 Page 11 2008-02-18 Table 7. Humidifier Variable Addresses Unit #4 Unit #4 BACnet Lonworks N2 Variable Name Type Instance SNVT SNVT # E lement Type Instance nvoHourOpt_4 AV 46 time_hour 124 67 AI.
10-10 Page 12 2008-02-18 Table 8. Humidifier Variable Addresses Unit #5 Unit #5 BACnet Lonworks N2 Variable Name Type Instance SNVT SNVT # Element Type Instance nvoHourOpt_5 AV 61 time_hour 124 89 AI .
10-10 Page 13 2008-02-18 Table 9. Humidifier Variable Addresses Unit #6 Unit #6 BACnet Lonworks N2 Variable Name Type Instance SNVT SNVT # E lement Type Instance nvoHourOpt_6 AV 76 time_hour 124 111 A.
10-10 Page 14 2008-02-18 Table 10. Humidifier Variable Addresses Unit #7 Unit #7 BACnet Lonworks N2 Variable Name Type Instance SNVT SNVT # Element Type Instance nvoHourOpt_7 AV 91 time_hour 124 133 A.
10-10 Page 15 2008-02-18 Table 11. Humidifier Variable Addresses Unit #8 Unit #8 BACnet Lonworks N2 Variable Name Type Instance SNVT SNVT # E lement Type Instance nvoHourOpt_8 AV 106 time_hour 124 155.
10-10 Page 16 2008-02-18 Figure 1. Sample Humidification Applications Room-Sensed %RH Feedback with Duct Hi-Limit Sensing Figure 2. Sample Humidification Applications Control Feedback (0-100%) with Du.
10-10 Page 17 2008-02-18 Figure 3. Sample Humidification Applications Room-Sensed %RH Feedback with Duct Hi-Limit Sensing (0-10V Signal Directly to Humidifier) nviDisable_x = 1 U nit Disabled = 0 Unit.
10-10 Page 18 2008-02-18 THIS PAGE INTENT IONALLY LEFT BLANK.
10-20 Page 1 2008-02-18 10-20 START-UP.
10-20 Page 2 2008-02-18 (1) NORTEC LINKS 2 START-UP CHECKLIST WIRING Humidifier-to-Humidifier Connection: Each individual humidifier linked to lead unit. Connection must be daisy-chained to other units. BMS Netwo rk Connection: Lead unit wired to BMS system (Twisted Pair or Ethernet).
10-30 Page 1 2008-02-18 10-30 TROUBLESHOOTING.
10-30 Page 2 2008-02-18 (1) TROUBLESHOOTING (1) When troubleshooting the communication process for OnLine and/or LINKS 2 modules should be kept in mind. Humidifier data is first received by the Nortec OnLine module using the modbus protocol over the serial port connection.
10-30 Page 3 2008-02-18 Figure 1. OnLine Diagnostic LED Locations Figure 2. BACnet Module LED Figure 3. LonWorks Module LED Figure 4. Ethernet Port Module Status Serial Port Activity Ethernet Activity.
10-30 Page 4 2008-02-18 Table 1. OnLine Diagnostic LED Description LED Name Color Function Module Status Off Indicates that the Online module is not receiving power. Green Indicates the Online module is operati ng normally. Orange Indicates that the Online module is load in g the firmware installed on the module.
10-30 Page 5 2008-02-18 Table 2. LINKS 2 Module Diagnostic LEDs LED Name Color Function Module Power Off Indicates that the Online module is not receiving power.
10-30 Page 6 2008-02-18 Table 3. Troubleshooting Communication Problems Problem Solution 1. The BMS network cannot read/write any informatio n to any of the networked humidifiers Verify that the network connection is made and is connecte d properly. Verify that the correct network settings are being used.
10-40 Page 1 2008-02-18 10-40 SPARE PARTS.
10-40 Page 2 2008-02-18 Table 1. Replacement Parts Nortec LINKS 2 Options Part Number Description Specify Unit Ty pe Protocol at time of order BACnet/MSTP BACnet/IP N2 LonWorks 2527101 LINKS 2 Replace.
10-40 Page 3 2008-02-18 Figure 1. BACnet or N2 Module Figure 2. LonWorks Module Figure 3. OnLine Module Figure 4. Ethernet Router.
10-40 Page 4 2008-02-18 Figure 5. Ethernet Switch.
10-50 Page 1 2008-02-18 10-50 TECHNICAL.
10-50 Page 2 2008-02-18 WID NHTC LINKS 2 BACnet/IP Option Suppleme nt a l W iring Di ag ram Diagram No. 25314 57 Rev . B Aug 22, 2007 Note: Use open LAN port when empl oying an internet connection for BACnet/IP and/or Nortec OnLine.
10-50 Page 3 2008-02-18 WID NHTC LINKS 2 LonWorks Option Supplemental W iring Diagram Diagram No. 2531433 Rev . B Aug 21, 2007 Note: Use Route r W AN port when employ ing an int ernet connection for OnLine . Use A and B ter minals for L onW orks feed back.
10-50 Page 4 2008-02-18 WID NHTC Nortec LINKS 2 Option Supplemental W iring Diagram Diagram No. 2525757 Rev . A Aug 1, 2007 Nortec LINKS 2 Te r m i n a l S t r i p (Unit 1) External wiring ‘by ot he.
10-50 Page 5 2008-02-18 THIS PAGE INTENTIONALLY LEFT BLANK.
WARRANTY (1) WALTER MEIER INC. and/or WALTER MEIER L TD. (hereinafter collectively referred to as THE COMPANY), warrant for a period of two years afte r installation or 30 months from manufacturer’s.
INST ALLA TION DA TE (MM/DD/YYYY) MODEL # SERIAL # U.S.A. W alter Meier (Climate USA) Inc. 826 Proctor Avenue Ogdensburg, NY 13669 TEL: 1-866-NORTEC-1 EMAIL: northamerica.climate@waltermeier .com WEBSITE: www .humidity .com CANADA W alter Meier (Cli mate Canada) Ltd.
An important point after buying a device Nortec Industries NHTC Series (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Nortec Industries NHTC Series yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Nortec Industries NHTC Series - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Nortec Industries NHTC Series you will learn all the available features of the product, as well as information on its operation. The information that you get Nortec Industries NHTC Series will certainly help you make a decision on the purchase.
If you already are a holder of Nortec Industries NHTC Series, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Nortec Industries NHTC Series.
However, one of the most important roles played by the user manual is to help in solving problems with Nortec Industries NHTC Series. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Nortec Industries NHTC Series along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center