Instruction/ maintenance manual of the product A900 Series Murphy
Go to page of 28
SERIES A900 MURPHYMA TIC ® GENERA TOR ENGINE CONTROL SYSTEM DESIGN, INST ALLA TION AND OPERA TING MANUAL A900-9025N Revised 10-99 Section 40 (00-02-0197).
WARNING BEFORE BEGINNING INST ALLA TION OF THIS MURPHY PRODUCT ✔ Disconnect all electrical power to the machine. ✔ Make sure the machine cannot operate during installation. ✔ Follow all safety warnings of the machine manufacturer . ✔ Read and follow all installation instructions.
T able of Contents Section 1: Introduction page 1 1-1 System 1 1-2 Models 1 1-3 Purpose 1 1-4 Definitions 1 1-5 How T o Use This Manual 1 Section 2: Specifications 1 2-1 Enclosure T ype 1 2-2 Power Re.
Section 1: Introduction 1-1 System. 1-1.1 The MURPHYMA TIC ® Generator Engine Control System, Series A900 is designed to meet the requirements of the engine control, shutdown and alarm section of NFP A-1 10 “Emer gency And Standby Power Systems” specification.
an automatic-start, two-cycle, engine-driven generator , and include the shutdown and alarm points recommended in NFP A- 1 10-1988 “Emer gency and Standby Generator Systems” for Level 1 installations.
T able 3-1.7 3 Level 1 C.V . S L.A. R.A. R.V . Level 2 C.V . S L.A. R.A. R.V . NFP A-1 10 NFP A99 C.V . S L.A. R.A. R.V . ② CAN/CSA C282-M89 C.V . S L.A. R.A. R.V . A901 C.V . S L.A. R.A. R.V . A902 C.V . S L.A. R.A. R.V . ④ ④ A903 C.V . S L.A. R.
(d) Overcrank circuit; will stop automatic cranking and indicate overcrank if engine fails to start after 3 attempts. The number of cranks are selectable for 1, 2, 3, 4 or 5 cycles before shutdown. The overcrank circuit may also be turned off so no overcrank shutdown occurs.
energize the battery char ging alternator field. 3-2.2.2 Shutdown Relay; this relay is operated by the shutdown circuits of the Control / Display Module and provides an output that can be used to trip the generator circuit breaker on an emergency shutdown.
(f) Overspeed Speed Switch; 1. Provides a signal to the overspeed shutdown circuit if the engine exceeds the preset speed. The factory setting is approximately 3894 Hz, or 1980 RPM on an engine with 1 18 teeth on the flywheel ring gear . The adjustment range is 300 Hz to 10,000 Hz.
7 to operate a local audible alarm as required by NFP A- 110, Level 1 and Level 2. 3-3.2.5 Remote Audible Alarm Relay; provides a contact closure to operate a remote audible alarm as required by NFP A- 1 10, Level 1. 3-3.2.6 Remote V isual Alarm Relay; provides a contact closure to operate a remote visual alarm as required by NFP A- 1 10, Level 1.
8 setting until the overspeed trips. When switch is released, the set point will be 10% above normal running speed. This is the method used to make the factory setting.
9 (c) TEST ; turns on the engine controls and shutdown circuits. A start signal is applied to the automatic control and the engine start sequence begins.
of cause of alarm. These circuits activate the alarm relay . Alarm circuits are active as long as power is applied to the A902-2. All are active when the engine is running, shutdown or on standby . T wo (2) Amber Alarm Indicating Lights are provided. (a) Low W ater T emperature; operated by low water temperature SWICHGAGE ® .
3-6.1.2 Lamp T est Pushbutton: T ests the lights on the A903 module. 3-6.1.3 Alarm Silence Pushbutton: T urns of f any audible alarm that is connected to the Local or Remote Audible Alarm Relays. The indicating light will remain on as long as the condition exists.
(h) #8 Spare Alarm; operated by an external switch. This circuit is provided for an additional alarm that may be required by the user . (i) #9 Spare Alarm; operated by an external switch. This circuit is provided for an additional alarm that may be required by the user .
audible alarm will turn off when the alarm contact clears. 3-7.1.4 The A903-2 SELECTRONIC ® Control Module includes the following engine control features: (a) Cycle crank circuit; will crank the engine for 15 seconds then rest for 15 seconds until the engine starts.
make up the generator engine control. Relays are available for operation on either 12 or 24 volt battery systems. Four (4) relays are included for: 3-7.2.1 Fuel Relay; this relay provides two outputs, one to energize the engine fuel solenoid and a separate circuit to energize the battery char ging alternator field.
5-1/2 in. (140 mm) 3-3/4 in. (95 mm) 3/16 in. (5 mm) dia. 4 places 5-5/8 in. (143 mm) 2-13/16 in. (71 mm) 3 in. (76 mm) 3-3/8 in. (86 mm) 6-3/4 in. (171 mm) 9-3/8 in. (238 mm) 6 in. (152 mm) 4-15/32 in. (114 mm) Mounting Holes 1/8 in. (3 mm) diameter 1-1/2 in.
15 26 4 27 28 4 29 30 31 32 33 34 47 48 49 50 51 52 B+ OUT HOURMETER B- MANUAL START START PICKUP PICKUP OIL PRESSURE LO WATER TEMP. HI WATER TEMP. REMOTE S.D. SPARE ALARM 35 36 37 38 39 40 41 42 43 44 45 46 ALARM SILENCE AUDIBLE ALARM OVERCRANK OVERSPEED OIL PRESSURE HI WATER TEMP.
Figure 4-2.3.2: A902 wiring 15 26 4 27 28 4 29 30 31 32 33 34 B+ OUT HOURMETER B- MANUAL START START PICKUP PICKUP OIL PRESSURE LO WATER TEMP. HI WATER TEMP. REMOTE S.D. SPARE ALARM 35 36 37 38 39 40 41 42 43 44 45 46 ALARM SILENCE AUDIBLE ALARM OVERCRANK OVERSPEED OIL PRESSURE HI WATER TEMP.
Figure 4-2.3.3: A903 wiring 15 26 4 27 28 4 29 30 31 32 33 34 47 48 49 50 51 52 B+ OUT HOURMETER B- MANUAL START START PICKUP PICKUP OIL PRESSURE LO WATER TEMP. HI WATER TEMP. REMOTE S.D. SPARE ALARM 35 36 37 38 39 40 41 42 43 44 45 46 ALARM SILENCE AUDIBLE ALARM OVERCRANK OVERSPEED OIL PRESSURE HI WATER TEMP.
current rating that is equal to or greater than the forward current that the coil draws to operate. For example, a relay less than 1 A, use a 1 A diode since they are readily available. The wiring shown in Figures 4-2.3.1, 4-2.3.2 and 4-2.3.3 have examples of the places that a reverse diode is required.
6. While engine is cranking, turn crank disconnect adjustment counter clockwise slowly until “ Crank Disconnect Speed ” light turns on and cranking stops. 7. T urn crank disconnect adjustment clockwise 1/4 turn. This sets crank disconnect speed at approximately 125 RPM above cranking speed.
(c) “ W ater T emperature ” light will come on and engine will stop. (d) T urn Mode Selector switch OFF . 4-4.9 Low W ater T emperature; to test the low water temperature alarm circuit: (a) Engine does not have to be running. (b) Use a jumper wire and short from terminal 31 to 4.
T able 7-2.1 22 Mode Selector OFF Mode Selector AUTO Stand-by Mode Selector AUTO Cranking Mode Selector AUTO Running Mode Selector AUTO Shutdown Input V oltage Input V oltage Input V oltage Input V oltage Input V oltage 13.8 27.6 13.8 27.6 13.8 27.6 13.
to the table for examples. (c) V oltages less than battery also may vary due to tolerances of the electronic components in the A900. Minor variations, 1 or 2 volts, normally will have no effect on the A900 operation. (d) The AC voltage at terminal 29 must be a minimum of 2 V AC to drive the speed sensing circuits of the A900.
local audible (K-4) terminal 20 and 21, remote audible (K-5) terminal 22 and 23 and remote visual (K- 6) terminal 24 and 25 close to operate the alarm devices wired to them. 7-3.3 An alarm silence pushbutton is wired between terminal 35 and ground. This switch is provided on the A901 and can be externally connected on the A902 series.
0690040 CONTROL SYSTEMS & SER VICES DIVISION P .O. Box 1819; Rosenberg, Texas 77471; USA (281) 342-0297 fax (281) 341-6006 e-mail sales@fwmurphy .com MURPHY DE MEXICO, S.A. DE C.V . Blvd. Antonio Rocha Cordero 300, Fracción del Aguaje San Luis Potosí, S.
An important point after buying a device Murphy A900 Series (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Murphy A900 Series yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Murphy A900 Series - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Murphy A900 Series you will learn all the available features of the product, as well as information on its operation. The information that you get Murphy A900 Series will certainly help you make a decision on the purchase.
If you already are a holder of Murphy A900 Series, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Murphy A900 Series.
However, one of the most important roles played by the user manual is to help in solving problems with Murphy A900 Series. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Murphy A900 Series along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center