Instruction/ maintenance manual of the product DCA300SSC Multiquip
Go to page of 92
THIS MANU AL MUST A CCOMP ANY THE EQ UIPMENT A T ALL TIMES. To fi nd the latest revision of this publication, visit our website at: www .mqpo wer .com WHISPER W A TT™ SERIES MODEL DCA300SSC 60HZ GENERA TOR (CUMMINS QSL9-G3 DIESEL ENGINE) P AR TS LIST NO.
P A GE 2 — DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) PROPOSITION 65 W ARNING Diesel engine exhaust and some of.
DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) — P A GE 3 If you believe that your vehicle has a defect that could cause a crash or could cause injury or death, you should immediately inform the National Highway T raffi c Safety Administration (NHTSA) in addition to notifying Multiquip at 1-800-421-1244.
P A GE 4 — DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) T ABLE OF CONTENTS DCA300SSC 60 Hz Generator Proposition 65 warning ............................................ 2 Repor ting Safety Def ects ................
DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) — P A GE 5 P AR TS ORDERING PROCEDURES www .mqpo w er .com Or dering par ts has never been easier! Choose fr om three .
P A GE 6 — DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) SAFETY INFORMA TION Do not operate or service the equipment before reading the entire manual. Saf ety precautions should be f ollow ed at all times when operating this equipment.
DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) — P A GE 7 SAFETY INFORMA TION GENERAL SAFETY CA UTION NEVER operate this equipment without proper protectiv e clo.
P A GE 8 — DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) SAFETY INFORMA TION ENGINE SAFETY D ANGER The engine fuel e xhaust gases contain poisonous carbon mono xide. This gas is colorless and odorless, and can cause death if inhaled.
DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) — P A GE 9 SAFETY INFORMA TION FUEL SAFETY D ANGER DO NO T star t the engine near spilled fuel or combustib le fl uids. Diesel fuel is extremely fl ammable and its v apors can cause an e xplosion if ignited.
P A GE 10 — DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) SAFETY INFORMA TION ELECTRICAL SAFETY D ANGER DO NO T touch output ter minals during operation. Contact with output terminals during operation can cause electrocution, electrical shock or b urn.
DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) — P A GE 11 SAFETY INFORMA TION B A TTER Y SAFETY D ANGER DO NO T drop the batter y . There is a possibility that the batter y will e xplode. DO NO T e xpose the batter y to open fl ames, sparks, cigarettes, etc.
P A GE 12 — DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) Generator Specifi cations T able 1. Model DCA300SSC T ype Rev olving fi eld, self v entilated, Drip proo.
DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) — P A GE 13 DIMENSIONS Dimensions Figure 1. Dimensions T able 3. Reference Letter Dimension in. (mm) Reference Letter Dimension in. (mm) A 39.76 in. (1,010 mm) F 43.90 in.
P A GE 14 — DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) INST ALLA TION T ypical Generator Grounding Application Figure 2.
DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) — P A GE 15 INST ALLA TION OUTDOOR INST ALLA TION Install the generator in a area that is free of debris, bystanders , and ov erhead obstr uctions. Make sure the generator is on secure le v el ground so that it cannot slide or shift around.
P A GE 16 — DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) GENERA TOR The MQ P ower Model DCA300SSC is a generator (Figure 3) that is designed as a high quality por .
DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) — P A GE 17 MAJOR COMPONENTS Generator Major Components T able 4. ITEM NO .
P A GE 18 — DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) GENERA TOR CONTROL P ANEL Generator Control P anel Figure 4. The defi nitions belo w describe the controls and functions of the DCA300SSC Generator Control P anel (Figure 4).
DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) — P A GE 19 GENERA TOR CONTROL P ANEL MPEC Control Switc h — This switch controls the running of the unit. If this switch is set to the OFF/RESET position, the unit will not run.
P A GE 20 — DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) ENGINE OPERA TING P ANEL The defi nitions belo w describe the controls and functions of the DCA300SSC Engine Operating P anel (Figure 5). T achometer 1. — Indicates engine speed in RPM’ s for 60 Hz operation.
DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) — P A GE 21 NOTES.
P A GE 22 — DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) OUTPUT TERMINAL P ANEL F AMILIARIZA TION OUTPUT TERMINAL P ANEL The Output T er minal Panel (Figure 6) sho wn below is located on the right-hand side (left from control panel) of the generator .
DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) — P A GE 23 OUTPUT TERMINAL P ANEL F AMILIARIZA TION 120 V A C GFCI Receptacles There are two 120 V AC , 20 amp GFCI (Duple x Nema 5-20R) receptacles provided on the output terminal panel.
P A GE 24 — DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) OUTPUT TERMINAL P ANEL F AMILIARIZA TION Connecting Loads Loads can be connected to the generator b y the Output T erminal Lugs or the conv enience receptacles (Figure 10).
DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) — P A GE 25 LOAD APPLICA TION SINGLE PHASE LO AD Alwa ys be sure to check the nameplate on the generator and equipment to insure the wattage , amperage, frequency , and voltage requirements are satisf actor ily supplied by the generator f or operating the equipment.
P A GE 26 — DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) GENERA TOR OUTPUTS GENERA TOR OUTPUT V OL T A GES A wide range of v oltages are av ailable to supply v oltage f or many diff erent applications. V oltages are selected by applying jumpers (6) to the v oltage change-over boar d (Figure 12).
DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) — P A GE 27 GENERA TOR OUTPUTS/GAUGE READING HO W TO READ THE A C AMMETER AND AC V OL T A GE GA UGES The A C ammeter and A C v oltmeter gauges are controlled by the A C ammeter and AC v oltmeter change-ov er s witches.
P A GE 28 — DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) OUTPUT TERMINAL P ANEL CONNECTIONS UVWO TERMINAL OUTPUT V OL T A GES V ar ious output voltages can be obtained using the UVW O output ter minal lugs.
DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) — P A GE 29 OUTPUT TERMINAL P ANEL CONNECTIONS 3Ø-480V UVWO T erminal Output V oltages Jumper the v oltage change-over board f or 480V 1. operation as shown in Figure 23.
P A GE 30 — DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) INSPECTION/SETUP CIRCUIT BREAKERS T o protect the generator from an ov er load, a 3-pole, 800 amp , main circuit break er is provided to protect the U,V , and W Output T erminals from overload.
DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) — P A GE 31 INSPECTION/SETUP Refueling Procedure: Level T anks 1. — Mak e sure fuel cells are le v el with the ground. F ailure to do so will cause fuel to spill from the tank bef ore reaching full capacity (Figure 29).
P A GE 32 — DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) COOLANT (ANTIFREEZE/SUMMER COOLANT/ W A TER) Cummins recommends antifreeze/summer coolant f or use in their engines, which can be purchased in concentrate (and mix ed with 50% demineralized w ater) or pre-diluted.
DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) — P A GE 33 B A TTER Y This unit is of negative g round DO NO T connect in rev erse. Alwa ys maintain batter y fl uid lev el between the specifi ed marks. Batter y life will be shortened, if the fl uid le v el are not properly maintained.
P A GE 34 — DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) GENERA TOR ST AR T -UP PROCEDURE (MANUAL) BEFORE ST ARTING Place the 1. main, G.F .C.I., and aux. circuit breakers ( Figure 35 ) in the OFF position prior to star ting the engine.
DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) — P A GE 35 GENERA TOR ST AR T -UP PROCEDURE (MANUAL) The generator’ s frequency meter (Figure 42) should be 6. displa ying the 60 cycle output frequency in HERTZ. Frequency Meter Figure 42.
P A GE 36 — DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) GENERA TOR ST AR T -UP PROCEDURE (AUTO MODE) ST ARTING (A UT O MODE) D ANGER Bef ore connecting this generator to any building’ s electrical system, a licensed electrician must install an isolation (transfer) switc h.
DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) — P A GE 37 GENERA TOR SHUT -DOWN PROCEDURES NORMAL SHUTDO WN PROCEDURE T o shutdown the generator , use the following procedure: Place both the 1. MAIN, GFCI and LO AD circuit breakers as shown in Figure 35 to the OFF position.
P A GE 38 — DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) * 1 Replace engine oil and fi lter at 100 hours, fi rst time only . * 2 Add “Supplemental Coolant Additiv es (SCA’S)” to recharge the engine coolant.
DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) — P A GE 39 MAINTENANCE If the engine is operating in v ery dusty or dr y grass conditions, a clogged air cleaner will result. This can lead to a loss of power , excessiv e carbon buildup in the comb ustion chamber and high fuel consumption.
P A GE 40 — DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) T o restar t after r unning out of fuel, tur n the s witch to the “ON” position f or 15-30 seconds. T r y again, if needed. This unit is equipped with an automatic air bleeding system.
DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) — P A GE 41 MAINTENANCE JA CKET W A TER HEA TER AND INTERNAL B A TTER Y CHARGER 120 V A C INPUT RECEPT ACLES (OPTIONAL) This generator can be optionally equipped with two 120 V AC , 20 amp input receptacles located on the output ter minal panel.
P A GE 42 — DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) TRAILER MAINTENANCE TRAILER MAINTENANCE This section is intended to provide the user with generic trailer service and maintenance information. The ser vice and maintenance guidelines ref erenced in this section ref er to a wide range of trailers .
DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) — P A GE 43 TRAILER MAINTENANCE BRAKES T railer brak es should be inspected the fi r st 200 miles of operation. This will allow the brake shoes and drums to seat properly .
P A GE 44 — DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) TRAILER MAINTENANCE TIRES/WHEELS/LUG NUTS Tires and wheels are a very impor tant and cr itical components of the trailer . When specifying or replacing the trailer wheels it is impor tant the wheels, tires, and axle are properly matched.
DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) — P A GE 45 TRAILER MAINTENANCE Lug Nut T orque Requirements It is e xtremely impor tant to apply and maintain proper wheel mounting torque on the trailer . Be sure to use only the f asteners matched to the cone angle of the wheel.
P A GE 46 — DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) TRAILER WIRING DIAGRAM T railer/T owing V ehicle Wiring Diagram Figure 63.
DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) — P A GE 47 GENERA TOR WIRING DIAGRAM Generator Wiring Diagram Figure 64.
P A GE 48 — DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) ENGINE WIRING DIAGRAM Engine Wiring Diagram Figure 65..
DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) — P A GE 49 NOTES.
P A GE 50 — DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) TROUBLESHOOTING (GENERA TOR) Practically all breakdowns can be pre vented b y proper handling and maintenance inspections, b ut in the e v ent of a breakdown, use T able 19 sho wn below f or diagnosis of the Generator .
DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) — P A GE 51 TROUBLESHOOTING (ENGINE CONTROLLER) Practically all breakdowns can be pre vented b y proper handling and m.
P A GE 52 — DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) TROUBLESHOOTING (DIAGNOSTIC LAMP) The engine controller of this generator diagnoses prob lems that arise from the engine control system and the engine itself .
DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) — P A GE 53 NOTES.
P A GE 54 — DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) EXPLANA TION OF CODE IN REMARKS COLUMN The f ollowing section e xplains the different symbols and remarks used in the Parts section of this manual. Use the help numbers f ound on the bac k page of the manual if there are any questions .
DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) — P A GE 55 SUGGESTED SP ARE P AR TS DCA300SSC WHISPER W A TT GENERA T OR WITH CUMMINGS QSL9-G3 DIESEL ENGINE 1 to 3 units QTY . P/N DESCRIPTION 1............0602015120 .
P A GE 56 — DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) GENERA TOR ASSY ..
DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) — P A GE 57 NO . P ART NO . P ART NAME QTY . REMARKS 1 C2110000002 RO T OR ASSY .
P A GE 58 — DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) GENERA TOR ASSY . (CONTINUED).
DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) — P A GE 59 GENERA TOR ASSY . (CONTINUED) NO . P ART NO . P ART NAME QTY .
P A GE 60 — DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) CONTROL BOX ASSY ..
DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) — P A GE 61 NO . P ART NO . P ART NAME QTY . REMARKS 1 M5213000002 CONTROL BO X 1 2 0601809659 CURRENT TRANSFORMER 3 3.
P A GE 62 — DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) CONTROL BOX ASSY . (CONTINUED).
DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) — P A GE 63 CONTROL BOX ASSY . (CONTINUED) NO . P ART NO . P ART NAME QTY .
P A GE 64 — DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) ENGINE AND RADIA TOR ASSY ..
DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) — P A GE 65 ENGINE AND RADIA TOR ASSY . NO . P ART NO . P ART NAME QTY . REMARKS 1 C2923200204 ENGINE, QSL9-G3 1 1A 0602015244 BEL T , F AN .............................
P A GE 66 — DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) ENGINE AND RADIA TOR ASSY . (CONTINUED).
DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) — P A GE 67 ENGINE AND RADIA TOR ASSY . (CONTINUED) NO . P ART NO . P ART NAME QTY . REMARKS 33 0603306395 HOSE JOINT 1 34 0602021070 CAP 1 35 0269200800 DRAIN HOSE 1 36 0602010220 RESER VER T ANK .
P A GE 68 — DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) ENGINE OPERA TING P ANEL ASSY ..
DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) — P A GE 69 ENGINE OPERA TING P ANEL ASSY . NO . P ART NO . P ART NAME QTY .
P A GE 70 — DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) OUTPUT TERMINAL ASSY ..
DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) — P A GE 71 OUTPUT TERMINAL ASSY . NO . P ART NO . P ART NAME QTY . REMARKS 1 C2231700403 SET BOARD , OUTPUT TERMINAL .
P A GE 72 — DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) BA TTER Y ASSY ..
DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) — P A GE 73 BA TTER Y ASSY . NO . P ART NO . P ART NAME QTY . REMARKS 1 0165614551 BA TTERY 2 145G51 2 C9109100604 BA .
P A GE 74 — DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) MUFFLER ASSY ..
DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) — P A GE 75 MUFFLER ASSY . NO . P ART NO . P ART NAME QTY . REMARKS 1 C2331100002 MUFFLER 1 2 0019210025 HEX HEAD BOL .
P A GE 76 — DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) FUEL T ANK ASSY ..
DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) — P A GE 77 FUEL T ANK ASSY . NO . P ART NO . P ART NAME QTY . REMARKS 1 C2363000303 FUEL T ANK 1 1-1 0810105004 CAP ,.
P A GE 78 — DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) ENCLOSURE ASSY ..
DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) — P A GE 79 ENCLOSURE ASSY . NO . P ART NO . P ART NAME QTY . REMARKS 1 C2413003202 BASE 1 2 C3414100104 FLOOR P ANEL .
P A GE 80 — DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) ENCLOSURE ASSY . (CONTINUED).
DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) — P A GE 81 ENCLOSURE ASSY . (CONTINUED) NO . P ART NO . P ART NAME QTY .
P A GE 82 — DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) ENCLOSURE ASSY . (CONTINUED).
DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) — P A GE 83 ENCLOSURE ASSY . (CONTINUED) NO . P ART NO . P ART NAME QTY .
P A GE 84 — DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) RUBBER SEALS ASSY ..
DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) — P A GE 85 RUBBER SEALS ASSY . NO . P ART NO . P ART NAME QTY . REMARKS 1 0229201400 SEAL R UBBER 4 2 0228901015 SEAL.
P A GE 86 — DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) NAMEPLA TE AND DECALS ASSY ..
DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) — P A GE 87 NAMEPLA TE AND DECALS ASSY . NO . P ART NO . P ART NAME QTY . REMARKS 1-1 C3550000703 DECAL : HANDLING PROCEDURES ......................... 1 ...............
P A GE 88 — DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) NAMEPLA TE AND DECALS ASSY . (CONTINUED).
DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) — P A GE 89 NAMEPLA TE AND DECALS ASSY . (CONTINUED) NO . P ART NO . P ART NAME QTY . REMARKS BA TTER Y GROUP 6-1 0800689404 DECAL : + ..................................
P A GE 90 — DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) TERMS AND CONDITIONS OF SALE — P AR TS P A YMEN T TERMS T er ms of payment for parts are net 3 0 days. FREIGHT P OLIC Y All parts orders will be shipped collect or prepaid with the c harges add ed to the invoice.
DCA300SSC GENERA T OR • OPERA TION AND P ARTS MANU AL — REV . #0 (06/25/09) — P A GE 91 NOTES.
Y our Local Dealer is: HERE’S HOW TO GET HELP PLEASE HA VE THE MODEL AND SERIAL NUMBER ON-HAND WHEN CALLING © COPYRIGHT 2009, MUL TIQUIP INC. MQ P ower and the MQ P ower logo are registered trademarks of Multiquip Inc. and ma y not be used, reproduced, or altered without written permission.
An important point after buying a device Multiquip DCA300SSC (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Multiquip DCA300SSC yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Multiquip DCA300SSC - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Multiquip DCA300SSC you will learn all the available features of the product, as well as information on its operation. The information that you get Multiquip DCA300SSC will certainly help you make a decision on the purchase.
If you already are a holder of Multiquip DCA300SSC, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Multiquip DCA300SSC.
However, one of the most important roles played by the user manual is to help in solving problems with Multiquip DCA300SSC. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Multiquip DCA300SSC along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center