Instruction/ maintenance manual of the product MELSEC FX1S Mitsumi electronic
Go to page of 92
HARD W ARE MANU AL FX 1S SERIES PROGRAMMA BLE CONTROLLERS.
FX1S Ser ies Program mable Controllers Forew or d • This man ual c ontains t e xt, diag rams and e xp lanatio ns which will guide t he reader in the c orrect insta llation and oper ation of the FX 1S Series Progr ammable Cont rollers . It should be read a nd understood bef ore attempt ing to install or use the uni t.
i FX 1S Series Pr ogrammab le Contr oller s Har d w are Man ual This manua l confers no in dustria l proper ty rights or an y rights of any other kind, n or does it confer any patent licenses .
FX1S Ser ies Program mable Controllers ii Guidelines for the Safety of the User and Pr otection of the FX 1S . This manual pro vides inf or mation f or the use of the FX 1S . The man ua l has been wr itten to be used b y train ed and co mpetent pe rsonne l.
FX1S Ser ies Program mable Controllers iii Notes on the Symbols U sed in th is Manua l At v arious times throughout th is manual cer tain symbols will be used to highlight poi nts which are intended to ens ure the users personal saf ety and prot ect the integrity of equipment.
FX1S Ser ies Program mable Controllers iv • Under no ci rcumstances will Mitsubishi Elec tr ic be liab le responsib le f or an y consequenti al damage that m ay ar ise as a result of the installation or use o f this equipment.
FX1S Ser ies Program mable Controllers v Marine standard The FX 1S Series conf or ms to the marine standards lis ted below . Ov erall, regulation c onf or mity restr ictions on v ar ious equipment are reduced when the FX 1S Series installation setup complies with m ar ine standards .
FX1S Ser ies Program mable Controllers vi Note Conce rning the CE Mark ing This note does not guar antee that an entire mechanical module produced in acc ordance with the contents of this note will compl y with the f ollowin g standards.
FX1S Ser ies Program mable Controllers vii EMC The f ollowing products ha ve shown compli ance through direct testing (of the i dentified standards belo w) and design analysis (through the creation of.
FX1S Ser ies Program mable Controllers viii Models : MELSEC FX 2NC se r ies man uf actured from Octobe r 1st, 2002 FX 2NC -232ADP FX 2NC -485ADP Standar d Remark EN50081-2:199 3 Electro ma gnetic compatibility EN61000-6-4:20 07 - Gener ic emission standard Industrial environment Compliance with all rele v ant aspects of the standard.
FX1S Ser ies Program mable Controllers ix LV D The f ollowing products ha ve shown compli ance through direct testing (of the i dentified standards belo w) and design analysis (through the creation of a technical construction file) to the European Direc tive f or Lo w V oltage (73/23/EEC) when used a s directed b y the appropriate doc umen tati on.
FX1S Ser ies Program mable Controllers x Associated Manuals The f ollowing man uals are recommended as essent ial ref erence material f or the correct oper a tion of a FX 1S ser ies Programmab le controller .
FX1S Ser ies Program mable Controllers xi FX 1N -2AD-BD Users Man ual JY992D96201 This ma nu al contai ns e xpla nat ion f or i nsta llat ion, specification and special au xiliar y rela y allocation.
FX1S Ser ies Program mable Controllers xii MEMO.
xiii T able of Contents Guideline ........... ............. ....... ........... .............. ...... ........... .............. ....... ..... ii Associated Man u als ....... .............. ........... ............. ........... .............. ....... .
FX1S Ser ies Program mable Controllers xiv 3. Installation Notes ....... ..... ....... ..... ....... ....... ..... ....... ..... ....... ..... ....... ..... ....... .. 3-1 3.1 Product Ou tline ................... .................................... .
FX1S Ser ies Program mable Controllers xv 5. Inputs .... ....... ..... ....... ..... .... ....... ..... ..... ....... ..... ....... ..... .... ........ .... ..... ....... ..... 5-1 5.1 24V DC Input Specificatio ns .......................... ..........
FX1S Ser ies Program mable Controllers xvi 7. Diagnostics ................ ............ ........................ ..................... .......... .............. 7-1 7.1 Prelimina ry Checks ...................... .................. .................. .
1 2 3 4 5 6 7 8 xvii 1 INTR ODUCTION 2 TERMINAL LA Y O UTS 3 INST A LLA TION NO TES 4 PO W ER SU PPL Y 5 INPUTS 6O U T P U T S 7 DIA GNOSTICS 8 DISCO NTINUE D MODEL FX1S Seri es Progr ammable Controll.
FX1S Ser ies Program mable Controllers xviii 1 INTR ODUCTION 2 TERMINAL LA Y O UTS 3 INST A LLA TION NO TES 4 PO W ER SU PPL Y 5 INPUTS 6O U T P U T S 7 DIA GNOSTICS 8 DISCO NTINUE D MODEL.
FX1S Ser ies Program mable Controllers Introduction 1 1-1 1 2 3 4 5 6 7 8 1. Intr od uction This man ual cov ers the hardware installati on instructions f or the FX 1S Series Progr ammab le (Logic) Control l er .
FX1S Ser ies Program mable Controllers Introduction 1 1-2 T able 1.3: DC P ower , Rela y Output Units MODEL INPUT OUTPU T PO WER SUPPL Y DIME NSION S mm (inc hes) MA SS (WEIGHT ) kg (l bs) QTY TYPE QTY TYPE W H D FX 1S -10MR-DS 6 24V DC Sink / Source 4 Rela y 24 VDC +10% , -15% 60 (2.
FX1S Ser ies Program mable Controllers Introduction 1 1-3 1 2 3 4 5 6 7 8 Figure 1.1: FX 1S Ou tline Drawing Dimen sions: mm (inches) The distance betw een the v er tical centerlines is 8mm (0.32") l ess than the width of the unit. Please see pre vious page f or each model’ s width meas urement.
FX1S Ser ies Program mable Controllers Introduction 1 1-4 *1 The co mmunica tion adap ter needs to c onnect via an FX 1N -CNV -BD to the FX 1S Series PLC .
FX1S Ser ies Program mable Controllers Introduction 1 1-5 1 2 3 4 5 6 7 8 1.1 Model Name T able 1.6: Model T able FX 1S -14MR-ES/UL C) A) B) D) F) E) A) PLC type: FX 1S B) T otal number of I / O chann.
FX1S Ser ies Program mable Controllers Introduction 1 1-6 1.2 W orld Specification T able 1.7: W orld / Japanese Specificatio ns Input Sink / Sour ce W orl d spec models: SINK / SOURCE J a panese mo d.
FX1S Ser ies Program mable Controllers Introduction 1 1-7 1 2 3 4 5 6 7 8 1.3 Serial Numbers T able 1.8: Notes on Serial Numbe r s 1) Production year 2) Production month 3) Production ser ial number SERIAL NO .
FX1S Ser ies Program mable Controllers Introduction 1 1-8 1.4 Configuration Figure 1.2: Sch e matic System B A D C H H' E G 1 1' 1 1" 2 F F' FX 1S -10MR-ES/UL FX 1S -14MR-ES/UL FX .
FX1S Ser ies Program mable Controllers Introduction 1 1-9 1 2 3 4 5 6 7 8 *1 A v ailab le f or use with FX 1S v ersion 2.00 or later . *2 Wh en using the FX 1N -EEPR OM-8L with an e x pansio n board in g roup C , only t he loader function (transf er progr am) can be used.
FX1S Ser ies Program mable Controllers Introduction 1 1-10 T able 1.9: Configuration Notes A FX 1S Series Main Unit B FX 1N Expansion Boards f or Analog I/O C FX 1N Expansion Boards without Analog I/O.
FX1S Ser ies Program mable Controllers Introduction 1 1-11 1 2 3 4 5 6 7 8 Note When connect ing per ipheral equipment (progr amming tool or GO T [dire ct connectio n to CPU]) via the FX 1N -232-BD , FX 1N -422-BD , FX 2NC -232ADP or the FX 0N -232ADP , FX 1S main unit should be the f ollo wing setting condi tion.
FX1S Ser ies Program mable Controllers Introduction 1 1-12 1.5 Bac kup Da ta 1.5.1 D ata Ba c kup Data includes the Progr am, Comment, File Register (D1000 ~ D2499), and parameter data. This will be s t ored as long as the EEPR OM is not damaged. Mitsubishi El ectr ic has guar anteed a lif e cycle time of 10,000 wr ites to the EEPR OM memor y .
FX1S Ser ies Program mable Controllers Terminal Layouts 2 2-1 1 2 3 4 5 6 7 8 2. T e rminal La y outs The f ollow ing sel ection of terminal la y outs are tak en from th e FX 1S product r ange . Note: All la y outs are schematic only an d are intended to aid in the creatio n of wiring diagr ams .
FX1S Ser ies Program mable Controllers Terminal Layouts 2 2-2 2.2 FX 1S -**MR-DS Figure 2.2: T erminal La y outs, Rela y Outputs, DC P o wer S/S X1 - X0 X4 X6 FX 1S -14MR-DS X5 X7 Y0 Y1 Y2 Y4 X3 X2 CO.
FX1S Ser ies Program mable Controllers Terminal Layouts 2 2-3 1 2 3 4 5 6 7 8 2.3 FX 1S -**MT -DSS Figure 2.3: T erminal La y outs, T ransistor Outputs, DC P o wer S/S X1 - X0 X4 X6 FX 1S -14MT-DSS X5.
FX1S Ser ies Program mable Controllers Terminal Layouts 2 2-4 2.4 FX 1S -**MT -ESS/UL Figure 2.4: T erminal La y outs, T ransistor Outputs, A C P o wer S/ S X1 N X0 X4 X6 FX 1S - 1 4 M T- ESS/ UL X5 X.
FX1S Ser ies Program mable Controllers Installation Notes 3 3-1 1 2 3 4 5 6 7 8 3. Installation No tes The installation of FX 1S products has be en designed t o be saf e and easy . When t he products associated with this manual are us ed as a system or indiv idually , the y must be installed in a suitab le enclosure .
FX1S Ser ies Program mable Controllers Installation Notes 3 3-2 3.1 Pr oduct Outline Figure 3.1: Features of the FX 1S PLC T able 3.1: Feature T able 1 Direct Mou nting Holes (4.
FX1S Ser ies Program mable Controllers Installation Notes 3 3-3 1 2 3 4 5 6 7 8 3.2 FX 1S RU N/ST OP Contr ol R UN or ST OP of the FX 1S can be controlled b y: n The R UN/ST OP s witch mounted ne xt to the prog r amming por t. o A standard inp ut (X000 to X017) defined b y the syste m param eters .
FX1S Ser ies Program mable Controllers Installation Notes 3 3-4 3.3 General Spec ifications T able 3.3: General Specification s *1 Th e criter ion is sho wn in IEC61131-2. *2 Do not use the PLC under pre ssure higher than the atmospher ic pressu re. Do ing so ma y damage the P LC .
FX1S Ser ies Program mable Controllers Installation Notes 3 3-5 1 2 3 4 5 6 7 8 3.4 PLC Mounting Arrang eme nts T o pre vent a r ise in temperat ure, mount t he unit s to walls. Ne v er moun t them t o the f loor or ceiling of an enclosu re. Figure 3.
FX1S Ser ies Program mable Controllers Installation Notes 3 3-6 Caution • Units should not be installed in areas subject to th e f ollowing conditions: e xcessiv e or conductiv e dust, corrosiv e gas (salt air , Cl 2 , H 2 S, S O 2 , NO 2 , etc.
FX1S Ser ies Program mable Controllers Installation Notes 3 3-7 1 2 3 4 5 6 7 8 • Replace the ter minal co v er provi ded, after installation o r wir ing work is complete d, and bef ore supplying po wer and operating the unit to a v oid electric shoc k.
FX1S Ser ies Program mable Controllers Installation Notes 3 3-8 3.5 DIN Rail Mounting Units can be snap mounted to 35m m(1.37") DIN rail . T o release , pull the spring loaded clips a wa y from the r ail and sli de the unit off and up . 3.6 Direct Mounting ∅ = 4.
FX1S Ser ies Program mable Controllers Installation Notes 3 3-9 1 2 3 4 5 6 7 8 ∅ = 4.5 mm (0. 17") T a ble 3.5: Hole positions UNIT mm inc hes ± 0.2 ± 0.01 B = W FX 0N -232ADP 2- ∅ ( → ) 43 1.70 FX 0N -485ADP C = W -24.5mm (0.97") FX 2N C -232ADP 2- ∅ ( → ) 65.
FX1S Ser ies Program mable Controllers Installation Notes 3 3-10 3.7 T ermination o f Screw T erminals T er min al screws should b e tighte ned to between 0.5 to 0 .8 N m . T er minal screws must be secured to p re v ent a loose connection thus a v oiding a malfunc tion.
FX1S Ser ies Program mable Controllers Installation Notes 3 3-11 1 2 3 4 5 6 7 8 1) Handle the crimp ter m inal of the f ollowin g size when 1 wire is us ed per ter minal. Ref er to Figure 3.5 f or installatio n instr uctions . Figure 3.4: Crimp T erminal f or M3 Screws Figure 3.
FX1S Ser ies Program mable Controllers Installation Notes 3 3-12 2) Handle the crimp ter minal of the f ollo wing siz e when 2 wires are used per ter minal. Ref er to Figure 3.7 f or installatio n instr uctions . Figure 3.6: Crimp T erminal f or M3 Figure 3.
FX1S Ser ies Program mable Controllers Installation Notes 3 3-13 1 2 3 4 5 6 7 8 3.8 Installing Optional Units 3.8.1 Exp ansion Boar ds The f ollow ing i s a generic e xplanation of ho w to install an e xpansion board ont o the FX 1S PLC .
FX1S Ser ies Program mable Controllers Installation Notes 3 3-14 Alw a ys mak e sure the po wer is tur ned off , bef ore installing a special funct ion board. Only one board can b e used at one time , do not tr y to stac k multip le boards. A) Special funct ion or optional equi pment board.
FX1S Ser ies Program mable Controllers Installation Notes 3 3-15 1 2 3 4 5 6 7 8 3.8.2 FX 1N -5DM Displa y Module Alw a ys make sure the pow er is tur ned off , bef ore installing the 5 D M. A) T op co v er f or DM B) Optional equi pment connector . C) M3 scre w to secure top cov er .
FX1S Ser ies Program mable Controllers Installation Notes 3 3-16 MEMO.
FX1S Ser ies Program mable Controllers Power Supp ly 4 4-1 1 2 3 4 5 6 7 8 4. P o wer Supply 4.1 Wiring T echniques Wir ing f or FX 1S products has been designed to be saf e and easy .
FX1S Ser ies Program mable Controllers Power Supp ly 4 4-2 4.3 P o w er Suppl y • When wir ing an A C supply , the “Liv e” cab le should be connected to th e “L” ter minal and the “Neutr al” cabl e should be connected to the “N” ter minal.
FX1S Ser ies Program mable Controllers Power Supp ly 4 4-3 1 2 3 4 5 6 7 8 4.4 P o w er Suppl y Characteristics *1 In cludes the i nput current (5 or 7mA per poi nt). T able 4.2: DC Input P o wer Requirements, FX 1S -* *M*-DS, DSS *1 In cludes the i nput current (5 or 7mA per poin t).
FX1S Ser ies Program mable Controllers Power Supp ly 4 4-4 4.5 P o w er Suppl y Wiring Figure 4.1: A C P ower Suppl y Example Wiring ➊ ➌➍ ➎ ➏ ➐ ➑ ➒ ➋ ➓ MC L 24V N 0V AC/ DC Co nver.
FX1S Ser ies Program mable Controllers Power Supp ly 4 4-5 1 2 3 4 5 6 7 8 Figure 4.2: DC P ower Suppl y Example Wiring ➊ ➐ ➑ ➒ ➋ ➓ DC/DC Co nver ter 24V DC ➌➍ ➎ ➏ MC ➏ ➊ P ow .
FX1S Ser ies Program mable Controllers Power Supp ly 4 4-6 4.6 Ser vice P ower supply An A C pow ered FX 1S can supply a s er vice cu rrent of 24V DC at 40 0mA. A DC po wered FX 1S does not ha v e the capa city to supply a serv ice curren t. 4.7 Ear thing / Grounding Use a cab le at least 0.
FX1S Ser ies Program mable Controllers Inputs 5 5-1 1 2 3 4 5 6 7 8 5. Inputs 5.1 24V DC Input Spec ifications T able 5.1: FX 1S Input Specifications FX 1S Main Unit X0 - X7 X10 - X17 Input v oltage 24V DC +10% - 15% Input current 24V DC , 7mA 24V DC , 5mA Input s witching current OFF ➔ ON >4.
FX1S Ser ies Program mable Controllers Inputs 5 5-2 5.2 Wiring Diagrams 5.2.1 Input Wiring Figure 5.1: Input Wiri ng Diagrams ➊ 24V DC Ser vice Supply ➋ PNP Sensor ➌ NPN Sensor ➍ Input De vice.
FX1S Ser ies Program mable Controllers Inputs 5 5-3 1 2 3 4 5 6 7 8 5.2.2 Input Cir c uit Connection Figure 5.2: Input Cir cuit Diag rams (Sour ce/Sink) 5.2.3 Diode s and Inputs Conn ected in Series Figure 5.3: Diode Connection Dia gram V ol tage drop across the dio de is Max.
FX1S Ser ies Program mable Controllers Inputs 5 5-4 5.2.4 Res istor s and Inputs Connecte d in P arallel P arall el resis tance Rp: FX 1S = 15k Ω . If resistance Rp is le ss than the stated v alue , then add the Rb v alue using th e Equation 1 calculati on.
FX1S Ser ies Program mable Controllers Outputs 6 6-1 1 2 3 4 5 6 7 8 6. Outputs 6.1 Output Specificati ons T able 6.1: Outp ut Specifications Description Rela y Output T ransistor Output Switched v oltages (resistive load) ≤ 240V A C , ≤ 30V DC 5 - 30V DC Rated current / N points (resistiv e load) 2A/1 point, 8A/COM 0.
FX1S Ser ies Program mable Controllers Outputs 6 6-2 6.2 Rela y Output Example Figure 6.1: T ypical Rela y Wiring Diagram ➊ Do not use this ter minal ➐ Inductiv e load ➋ Fuse ➑ Incandescent Lamp ➌ Re v erse-current pr otection diode (See section 6.
FX1S Ser ies Program mable Controllers Outputs 6 6-3 1 2 3 4 5 6 7 8 6.2.1 Pr oduct lif e of rela y contacts The pr oduct li f e of re la y contac ts consider ab ly v ar ies depend ing on the loa d type use d.
FX1S Ser ies Program mable Controllers Outputs 6 6-4 T able 6.2: The product lif e of rela y contacts becomes considerab ly shor ter th an the abov e conditions when the rush o verc urrent is shut do wn. * F or counter measures while using indu ctiv e loads , ref er to "Output circuit configur ation" belo w in this section.
FX1S Ser ies Program mable Controllers Outputs 6 6-5 1 2 3 4 5 6 7 8 6.2.2 Output c ir cuit configuration An inter nal protection circuit f or the rela ys is not pro vided in the rela y output circuit f or this product. It is recommended to use ind uctive loads with b uilt-in protection ci rcuits.
FX1S Ser ies Program mable Controllers Outputs 6 6-6 3) Interloc k 4) In- pha se F or loads such as f orward/re v erse contactors, etc., where a hazardous condition could result i f s witched ON simul taneously , an e x ter nal interl oc k should be provided f or interlocking the PLC's inter nal progr ams as sho wn to the right.
FX1S Ser ies Program mable Controllers Outputs 6 6-7 1 2 3 4 5 6 7 8 6.3 T ransis tor Output Examples Figure 6.2: T ransistor Output Wiring Dia gram Figure 6.3: Japanese M odel T ransistor Output ➊ Do not use this ter minal ➋ Emergency Stop ➌ Fus e ➍ Exter nal Mechanical Interlock (See Section 6.
FX1S Ser ies Program mable Controllers Outputs 6 6-8 6.3.1 Res ponse Times OFF times inc rease as the load current decreases . F or improv ed response times use a 'dumm y' resistor , see Figure 6.
FX1S Ser ies Program mable Controllers Outputs 6 6-9 1 2 3 4 5 6 7 8 6.3.2 Exte rnal wiring precau tion 1) Contact protection c ircuit f or inductiv e loads T r a nsisto r output s use i nter nal zener d iode (50V ) as protection circuitr y .
FX1S Ser ies Program mable Controllers Outputs 6 6-10 MEMO.
FX1S Ser ies Program mable Controllers Diagnostics 7 7-1 1 2 3 4 5 6 7 8 7. Diagnostics 7.1 Preliminar y Checks T able 7.1: Prelimina ry Chec ks Chec k power supply , ground and I/O cab les are wired correctly . T ur n the power supply on. Check that the pow er LED is lit.
FX1S Ser ies Program mable Controllers Diagnostics 7 7-2 7.2 ERROR LED O N (C PU ERROR) T able 7.2: Err or LED Chec ks Fa u l t ERR OR LED ON Remedy Reset PLC .
FX1S Ser ies Program mable Controllers Diagnostics 7 7-3 1 2 3 4 5 6 7 8 7 . 3 Co m m o n E r ro rs - Corroded contact po ints at some point in an I/O line . - An I/O de vice has been us ed outside its speci fied operati ng range . - An input signal occurs in a shor ter time pe r iod than tha t taken b y one progr am scan.
FX1S Ser ies Program mable Controllers Diagnostics 7 7-4 7.5 Operation and Error Flags T able 7.3: O per atio n and Er r o r Flags Para llel link error Parameter error Sy nta x error Program (circuit) e rror Program execution e rror Execution erro r latch M8063 (ref.
FX1S Ser ies Program mable Controllers Diagnostics 7 7-5 1 2 3 4 5 6 7 8 7.6 PLC Status Registe rs T able 7.4: PLC Status Register s 02H=EEPROM pro tect switch OFF 0AH=EEPROM protect switch ON 10H=MPU memory D8000 (default 200ms ec) D8001 D8002 D8003 D8004 Watchdog timer PLC ve rsio n 22100 = FX 1S Versi on 1.
FX1S Ser ies Program mable Controllers Diagnostics 7 7-6 7.7 Err or Registers T able 7.5: Err or Registers D8061 D8063 D8064 D8065 D8066 D8067 D8068 D8069 Error code for PLC har dwa re erro r Err or c.
FX1S Ser ies Program mable Controllers Diagnostics 7 7-7 1 2 3 4 5 6 7 8 7.8 Err or Codes T able 7.6: Err or Codes D8061 No e rror 0000 RAM erro r 6101 Operat ion cir cuit er ror 6102 D8063 Check bot .
FX1S Ser ies Program mable Controllers Diagnostics 7 7-8 7.9 Instruction List T able 7.7: Numericall y Sor ted 000 010 020 030 040 050 060 070 080 TRAN SFERS, COMP PROGRAM FL OW +- ×÷ , LOGI CS SHIFT DATA OPERATION 1 HIGH -SPEED HANDY INS TR.
FX1S Ser ies Program mable Controllers Diagnostics 7 7-9 1 2 3 4 5 6 7 8 T able 7.8: Alphabeticall y sor ted A Symbol ABS ABSD ADD AND ASCI FNC No . 155 062 020 066 232-238 082 D P B BCD BIN BMO V 018 019 015 CALL CCD 010 084 C CJ CMP 000 001 DEC DECO 025 041 D DI DIV DRVA 005 023 159 E DRVI DSW 158 072 F Symbol FNC No .
FX1S Ser ies Program mable Controllers Diagnostics 7 7-10 P Symbol PID PLSR PLSV PLSY PRUN PWM RAM P FNC No. 088 059 157 057 081 058 067 D P R S SFW R 038 S T Symbol FNC No.
FX1S Ser ies Program mable Controllers Diagnostics 7 7-11 1 2 3 4 5 6 7 8 7.10 Device List T able 7.9: Devic e List De vice T ype Specif icat ion Remarks Program capaci ty 2k steps by FX1S inter na l .
FX1S Ser ies Program mable Controllers Diagnostics 7 7-12 Counters (C) General 16 poi nts Range: 1 to 32,767 counts C0 to C15 T ype: 16 bit up coun ter Lat ched (EEPROM bac k ed-up ) 16 poi nts Range: 1 to 32,767 counts C16 to C31 T ype: 16 bit up coun ter High speed counters (C) Max.
FX1S Ser ies Program mable Controllers Diagnostics 7 7-13 1 2 3 4 5 6 7 8 Data registers (D) General 128 points D0 to D127 T ype: 16 bit data storage register pair f or 32 b it de vice Lat ched (EEPRO.
FX1S Ser ies Program mable Controllers Diagnostics 7 7-14 Constants Deci mal K 16 b it: -32,76 8 to +32,76 7 32 bit: -2,147,4 83,648 to +2,147,48 3,647 He xadeci mal H 16 bit: 0000 to FFFF 32 bit: 000.
FX1S Ser ies Program mable Controllers Discontinued model 8 8-1 1 2 3 4 5 6 7 8 8. D isconti nued mod el The tab le below sho ws discontinued models of MELSEC-F Series PLCs descr ibed in thi s manual.
FX1S Ser ies Program mable Controllers Discontinued model 8 8-2 MEMO.
1 2 3 4 5 6 7 8 1 INTR ODUCTION 2 TERMINAL LA Y O UTS 3 INST A LLA TION NO TES 4 PO W ER SU PPL Y 5 INPUTS 6O U T P U T S 7 DIA GNOSTICS 8 DISCO NTINUE D MODEL FX1S Seri es Progr ammable Controllers.
FX1S Ser ies Program mable Controllers 1 INTR ODUCTION 2 TERMINAL LA Y O UTS 3 INST A LLA TION NO TES 4 PO W ER SU PPL Y 5 INPUTS 6O U T P U T S 7 DIA GNOSTICS 8 DISCO NTINUE D MODEL.
.
HEAD OFFICE: TOKYO BUILDING, 2-7-3 MA RUNOUCHI, CHIYO DA-KU, TOKYO 10 0-8310, JAPAN HIMEJI WORKS:840, C H IYODA CHO, HI M EJI, JAPAN JY992D8 3901L (MEE) Eff ecti ve J une 2009 Specificatio ns are subject to chan ge without notice.
An important point after buying a device Mitsumi electronic MELSEC FX1S (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Mitsumi electronic MELSEC FX1S yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Mitsumi electronic MELSEC FX1S - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Mitsumi electronic MELSEC FX1S you will learn all the available features of the product, as well as information on its operation. The information that you get Mitsumi electronic MELSEC FX1S will certainly help you make a decision on the purchase.
If you already are a holder of Mitsumi electronic MELSEC FX1S, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Mitsumi electronic MELSEC FX1S.
However, one of the most important roles played by the user manual is to help in solving problems with Mitsumi electronic MELSEC FX1S. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Mitsumi electronic MELSEC FX1S along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center