Instruction/ maintenance manual of the product MSZ-GF60VE-E1 Mitsubishi
Go to page of 42
SER VICE MANUAL CONTENTS 1. TECHNICAL CHANGES ··································· 3 2. P ART NAMES AND FUNCTIONS ····················· 4 3. SPECIFICA TION ················································ 5 4.
2 Use the speci fi ed refrigerant only Never use any refrigerant other than that specified. Doing so may cause a burst, an explosion, or fire when the unit is being used, serviced, or disposed of. Correct refrigerant is specified in the manuals and on the spec labels provided with our products.
3 MUZ-GF60VE - E1 MUZ-GF71VE - E1 1. New model TECHNICAL CHANGES 1 OBH635.
4 P ART NAMES AND FUNCTIONS 2 ACCESSORIES Model MUZ-GF60/71VE Drain socket 1 MUZ-GF60VE MUZ-GF71VE Piping Air outlet Drain outlet Air inlet (back and side) Drain hose OBH635.
5 SPECIFICA TION 3 Outdoor model MUZ-GF60VE MUZ-GF71VE Power supply Single phase, 230 V , 50 Hz Capacity Rated frequency (Min. - Max.) Cooling kW 6.1 (1.
6 Speci fi cations and rated conditions of main electric parts Model Item MUZ-GF60VE MUZ-GF71VE Smoothing capacitor (CB1, CB2, CB3) 560 μ F 450 V Fuse (F601, F880, F901) T3.
7 NOISE CRITERIA CUR VES 4 MUZ-GF60VE MUZ-GF71VE T est conditions Cooling: Dry-bulb temperature 35°C Heating: Dry-bulb temperature 7°C Wet-bulb temperature 6°C OUTDOOR UNIT MICROPHONE 1 m 90 80 70 60 50 40 30 20 10 63 125 250 500 1000 2000 4000 8000 NC-60 NC-50 NC-40 NC-30 NC-20 NC-70 OCT A VE BAND SOUND PRESSURE LEVEL, 0dB re 0.
8 Unit: mm OUTLINES AND DIMENSIONS 5 MUZ-GF60VE MUZ-GF71VE 417.5 40 42 Drain hole 175 500 330 50 Air in Air out 2-holes 10 21 360 840 109 81 880 452 Service panel 99.5 164.5 195 35 44 Liquid refrigerant pipe joint Refrigerant pipe (flared) Ø 6.35 ( MUZ-GF60VE ) Ø 9.
9 WIRING DIAGRAM 6 MUZ-GF60VE MUZ-GF71VE OBH635.
10 REFRIGERANT SYSTEM DIAGRAM 7 MUZ-GF60VE Unit: mm Outdoor heat exchanger Flared connection Defrost thermistor RT6 1 Discharge temperature thermistor RT6 2 Flared connection Stop valve Stop valve (with service port) Capillary tube ø 4.
11 Max. Length A Max. Height difference B Indoor unit Outdoor unit MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE Refrigerant piping: m Piping size O.D: mm Max. Length A Max. Height difference B Gas Liquid MUZ-GF60 30 15 15.88 6.35 MUZ-GF71 9.
12 The standard specifications apply only to the operation of the air conditioner under normal conditions. Since operating condi- tions vary according to the areas where these units are installed, the.
13 NOTE: The above broken lines are for the heating operation without any frost and defrost operation. 0.8 0.9 1.0 1.1 1.2 1.3 - 1 0 - 5 0 5 1 01 52 02 53 03 54 04 5 Outdoor intake air Dry-bulb temperature (°C) Input correction factors 26 24 22 20 18 Indoor intake air Wet-bulb temperature( ) Indoor air Wet-bulb temperature difference (°C) 7.
14 8-2. CAP ACITY AND INPUT CORRECTION BY OPERA TIONAL FREQUENCY OF COMPRESSOR Correction of Cooling capacity Capacity correction factors Correction of Cooling input Input correction factors Correctio.
15 15 20 50 25 60 30 70 35 4.0 5.0 6.0 7.0 8.0 9.0 15 20 50 25 60 30 70 35 4.0 5.0 6.0 7.0 8.0 9.0 MUZ-GF60VE MUZ-GF71VE Ambient temperature(°C) Ambient humidity(%) Am bient temperature ( °C) Amb ien t h umid it y(% ) O ut door current ( A) O ut door current ( A) Outdoor unit current 0 5 10 15 20 25 3.
16 PERFORMANCE DA T A COOL operation a t Rated frequency MUZ-GF60VE CAP ACITY : 6.1 kW SHF: 0.79 INPUT : 1790 W INDOOR DB (°C) INDOOR WB (°C) OUTDOOR DB (°C) 21 25 27 30 Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 18 7.17 4.37 0.
17 PERFORMANCE DA T A COOL operation a t Rated frequency MUZ-GF60VE CAP ACITY : 6.1 kW SHF: 0.79 INPUT : 1790 W INDOOR DB (°C) INDOOR WB (°C) OUTDOOR DB (°C) 35 40 46 Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 18 5.98 3.65 0.61 1754 5.49 3.
18 PERFORMANCE DA T A COOL operation a t Rated frequency MUZ-GF71VE CAP ACITY : 7.1 kW SHF: 0.78 INPUT : 2130 W INDOOR DB (°C) INDOOR WB (°C) OUTDOOR DB (°C) 21 25 27 30 Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 18 8.34 5.01 0.
19 PERFORMANCE DA T A COOL operation a t Rated frequency MUZ-GF71VE CAP ACITY : 7.1 kW SHF: 0.78 INPUT : 2130 W INDOOR DB (°C) INDOOR WB (°C) OUTDOOR DB (°C) 35 40 46 Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 18 6.96 4.17 0.60 2087 6.39 3.
20 PERFORMANCE DA T A HEA T operation at Rated frequency MUZ-GF60VE CAP ACITY : 6.8 kW INPUT : 1810 W INDOOR DB (°C) OUTDOOR WB (°C) -10 -5 0 5 10 15 20 Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT 15 4.28 1 177 5.17 1412 6.05 1593 6.94 1720 7.
21 MUZ-GF60VE MUZ-GF71VE 9-2. R.V . COIL CONTROL Heating . . . . . . . . . . . . . . . . . ON Cooling . . . . . . . . . . . . . . . . . OFF Dry . . . . . . . . . . . . . . . . . . . . OFF NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor .
22 10-1. CHANGE IN DEFROST SETTING Changing defrost finish temperature <JS> T o change the defrost finish temperature, cut/solder the JS wire of the outdoor inverter P .C. board. (Refer to 1 1-6-1.) Jumper wire Defrost fi nish temperature ( °C ) MUZ-GF 60VE 71VE JS Soldered (Initial setting) 10 10 None (Cut) 18 18 10-2.
23 Outline of the function This air conditioner can memorize the abnormal condition which has occurred once. Even though LED indication listed on the troubleshooting check table (1 1-3.) disappears, the memorized failure details can be r ecalled. 1 1-2.
24 2. Flow chart of the detailed outdoor unit failure mode recall function 2.Blinking pattern when outdoor unit is abnormal: ON OFF No beep Beeps Repeated cycle 2.5-second OFF 3-second ON Blinking at 0.5- second interval No beep Beeps Repeated cycle 2.
25 3. Outdoor unit failure mode table The upper lamp of OPERA TION INDICA TOR lamp (Indoor unit) Abnormal point (Failure mode / protection) LED indication (Outdoor P .C. board) Condition Remedy Indoor/outdoor unit failure mode recall function Outdoor unit failure mode recall function OFF None (Normal) —— — — — 1-time fl ash 2.
1 1-3. TROUBLESHOOTING CHECK T ABLE No. Symptom LED indication Abnormal point/ Condition Condition Remedy 1 Outdoor unit does not op- erate. 1-time fl ash every 2.5 seconds Outdoor power sys- tem Overcurrent protection cut-out operates 3 consecutive times within 1 minute after the compressor gets started.
No. Symptom LED indication Abnormal point/ Condition Condition Remedy 19 Outdoor unit operates. 8-time fl ash 2.5 seconds OFF Zero cross detecting circuit Zero cross signal cannot be detected. It occurs with following cases. 1 Instantaneous power voltage drop.
28 1 1-5. TROUBLESHOOTING FLOW Are the voltages balanced? Disconnect the connector between compressor and the IGBT module (IC700). Replace the inverter P .C. board. Check the voltage between terminals. Check the compressor . See 1 1-5. “Check of compressor”.
29 F Check of compressor start failure D Check of compressor winding E Check of compressor operation time ● Disconnect the connector between the compressor and the IGBT module (IC700), and measure the resistance between the compressor terminals.
30 G Check of outdoor thermistors H Check of R.V . coil Replace the thermistor except RT64. When RT64 is abnormal, replace the inverter P .C. board. Replace the inverter P .C. board. No No Is the resistance of thermistor normal? (Refer to 1 1-6.1.) Reconnect the connector of thermistor .
31 I Check of outdoor fan motor Is the resistance between each ter- minal of outdoor fan motor normal? (Refer to 1 1-4.) Disconnect CN932 from the inverter P .C. board, and turn on the power supply . Rotate the outdoor fan motor manually and measure the voltage of CN931.
32 J Check of power supply Is there voltage 230 V AC between the indoor terminal block S1 and S2? No Ye s Replace the indoor electronic control P .C. board. Rectify indoor/outdoor connecting wire. Ye s If light up, OK. If fl ash, refer to 1 1-3. Does the upper lamp of OPERA TION INDICA TOR on the indoor unit light up? Does LED on the inverter P .
33 Press OPERA TE/ST OP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. 1 Expansion valve operates in full-opening direction. OK NOTE : After check of LEV , do the undermentioned operations.
34 Check the outdoor fan motor . (Refer to 1 1-5. .) Is the fuse (F901) blown on the in- verter P .C. board? Check the connection of the connectors (CN931, CN932) of the outdoor fan motor . If the connection is poor , make it correct. Operate the outdoor unit by starting EMERGENCY OPERA TION.
35 M How to check miswiring and serial signal error T urn the power supply OFF . Is there rated voltage in the power supply? Ye s No Check for incorrect indoor-outdoor connecting wiring.
36 N Electromagnetic noise enters into TV sets or radios Ye s Is the unit earthed? No Earth the unit. Ye s Is the distance between the antennas and the indoor unit within 3 m, or is the distance betwe.
37 1. Inverter P .C. board 1 1-6. TEST POINT DIAGRAM AND VOL T AGE MUZ-GF60VE MUZ-GF71VE -20 -10 0 10 20 30 40 0 10 20 30 40 50 60 70 80 90 100 T emperature( ) Defrost thermistor(RT61) Ambient tempera.
38 2. Relay P .C. board MUZ-GF60VE MUZ-GF71VE T o inverter P .C. board CN681 (CN680) CN60 L68B(-) L68A(+) 10 VDC OBH635.
39 12-1. MUZ-GF60VE MUZ-GF71VE NOTE: T urn OFF power supply before disassembly . OPERA TING PROCEDURE PHOTOS 1. Removing the cabinet (1) Remove the screws of the service panel. (2) Remove the screws of the top panel. (3) Remove the screw of the valve cover .
OPERA TING PROCEDURE PHOTOS 2. Removing the inverter assembly , inverter P .C. board and relay P .C. board (1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following con- nectors: <Inverter P .C. board> CN602 (R.
OPERA TING PROCEDURE PHOTOS 4. Removing the discharge temperature thermistor , defrost thermistor , outdoor heat exchanger tempera- ture thermistor and ambient temperature thermistor (1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following connectors: <Inverter P .
© Copyright 2013 MITSUBISHI ELECTRIC CORPORA TION Distributed in Mar . 2013. No. OBH635 Made in Japan New publication, effective Mar . 2013 Specifications are subject to change without notice.
An important point after buying a device Mitsubishi MSZ-GF60VE-E1 (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Mitsubishi MSZ-GF60VE-E1 yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Mitsubishi MSZ-GF60VE-E1 - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Mitsubishi MSZ-GF60VE-E1 you will learn all the available features of the product, as well as information on its operation. The information that you get Mitsubishi MSZ-GF60VE-E1 will certainly help you make a decision on the purchase.
If you already are a holder of Mitsubishi MSZ-GF60VE-E1, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Mitsubishi MSZ-GF60VE-E1.
However, one of the most important roles played by the user manual is to help in solving problems with Mitsubishi MSZ-GF60VE-E1. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Mitsubishi MSZ-GF60VE-E1 along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center