Instruction/ maintenance manual of the product PCFY-P30NKMU-E Mitsubishi Electronics
Go to page of 36
TECHNICAL & SER VICE MANUAL CONTENTS 1. P ART NAMES AND FUNCTIONS .......... 2 2. SPECIFICA TION ..................................... 4 3. OUTLINES AND DIMENSIONS .............. 8 4. WIRING DIAGRAM ............................... 11 5 . REFRIGERANT SYSTEM DIAGRAM .
Indoor unit 1 P ART NAMES AND FUNCTIONS Air outlet Louver V ane Air intake Filter (Inside of Air intake) 2.
3 °F°C °F°C ERROR CODE AFTER TIMER TIME SUN MON TUE WED THU FRI SA T ON OFF Hr AFTER FIL TER FUNCTION ONL Y1Hr . WEEKL Y SIMPLE AUTO OFF P AR-21MAA ON/OFF FIL TER CHECK OPERA TION CLEAR TEST TEMP . MENU BACK DA Y MONITOR/SET CLOCK ON/OFF ● ● Display Section For purposes of this explanation, all parts of the display are shown as lit.
4 2 SPECIFICA TION 2-1. SPECIFICA TIONS * 1 Nominal cooling conditions Note : Indoor : Outdoor : Pipe length : Level difference : 80 °FDB/67°FWB (26.7°CDB/19.4°CWB) 95°FDB ( 35 °CDB) 25 ft. (7.6 m) 0 ft ( 0 m) * 2 Nominal heating conditions 70 °FDB(21°CDB) 47 °FDB/43°FWB (8.
5 Parts name Symbol TH21 TH22 TH23 FUSE MF MV DP FS LEV TB2 TB5 TB15 Resistance 30°F/15.8k Ω , 50°F/9.6k Ω , 70°F/6.0k Ω , 80°F/4.8k Ω , 90°F/3.9k Ω , 100°F/3.2k Ω Resistance 30°F/15.8k Ω , 50°F/9.6k Ω , 70°F/6.0k Ω , 80°F/4.8k Ω , 90°F/3.
6 PCFY -P15NKMU-E External static pressure : 0Pa Power source : 208V , 230V , 60Hz PCFY -P24NKMU-E External static pressure : 0Pa Power source : 208V , 230V , 60Hz PCFY -P30NKMU-E External static pressure : 0Pa Power source : 208V , 230V , 60Hz PCFY -P36NKMU-E External static pressure : 0Pa Power source : 208V , 230V , 60Hz 10.
7 2-5. FRESH AIR INT AKE AMOUNT & ST A TIC PRESSURE CHARACTERISTICS Q 0 B A C 1 Curve in the graphs Duct characteristics at site Q A EC 2 Q Qa AD 3 Q … Designed amount of fresh air intake <CMM(CFM)> A … Static pressure loss of fresh air intake duct system with airflow amount Q <Pa(in.
8 3 OUTLINES AND DIMENSIONS PCFY -P15NKMU-E Unit : inch(mm) Drainage When drain socket is installed When drain socket is installed Drainage 9-3/16(233) 9-1 1/16(246) 14 i-see sensor 9-5/16(236) [FRONT.
9 PCFY -P24NKMU-E Unit : inch(mm) When drain socket is installed 9-3/16(233) Drainage When drain socket is installed 9-1 1/16(246) i-see sensor 14 liquid Φ3/8(Φ9.
10 When drain socket is installed 9-3/16(233) When drain socket is installed Drainage 9-1 1/16(246) 14 NOTES. 1.Use M10 or W3/8 screw for anchor bolt. 2.Please be sure when installing the drain lift up mechanism (option parts),refrigerant pipe will be only upward.
11 4 WIRING DIAGRAM CN27 CN32 CN51 CN52 SW2 SW3 SW4 SWE ZNR01,02 DSA FUSE X1 MF MV DP FS TB2 TB5 TB15 TH22 TH23 LEV SW1 SW1 1 SW12 SW14 SWA SWC W. B RU BZ LED1 LED2 SW1 SW2 POWER SUPPL Y TRANSMISSION MA-REMOTE CONTROLLER PIPE TEMP . DETECTION / LIQUID (32°F/15ΚΩ, 77°F/5.
12 5 REFRIGERANT SYSTEM DIAGRAM Refrigerant flow in cooling Refrigerant flow in heating Strainer (#100 mesh) Strainer (#100 mesh) Strainer1 (#50 mesh) Strainer2 (#100 mesh) Heat exchanger Room tempara.
13 MICROPROCESSOR CONTROL 6 PAR-21MAA ON/OFF FILTER CHECK OPERA TION CLEAR TEST TEMP . MENU BACK DA Y MONITOR/SET CLOCK ON/OFF ûF ûC ûF ûC ERROR CODE AFTER TIMER TIME SUN MON TUE WED THU FRI SAT ON OFF Hr AFTER FILTER FUNCTION ONLY1Hr . WEEKLY SIMPLE AUTO OFF INDOOR UNIT CONTROL 6-1.
14 → Control modes Control details 3-1. Drain pump control •Drain pump is always ON during the COOL and DRY mode operation. (Regardless of the thermo ON/OFF) •When the operation mode has changed from the COOL or DRY to the others (including Stop), the drain pump will be kept on for 3 minutes, then turns OFF .
15 Control modes Control details 1-1. Thermo regulating function (Function to prevent restarting for 3 minutes) Setting the Dry thermo by the thermo regulating signal and the room temperature (TH21). Dry thermo ON Room temperature desired temperature + 2°F Dry thermo OFF Room temperature desired temperature 1-2.
16 Control modes Control details Set by remote controller . When [Auto] is set, fan speed becomes [Low]. 2. Drain pump Remarks 1. Fan Ty p e Fan speed notch 4 speeds + Auto type [Low], [Med2], [Med1], [High], [Auto] 3. V ane (up/down vane change) 2-1.
17 Control modes Control details 1-1. Thermoregulating function (Function to prevent restarting for 3 minutes) • Room temperature desired temperature -2°F ···Thermo ON • Room temperature desired temperature ···Thermo OFF 1. Thermoregulating function Remarks 2-1.
18 → Control modes Control details 2. Fan Remarks 2-3. Thermo OFF mode When the thermoregulating function changes to OFF , the indoor fan operates in [Extra low].
19 1. Drain pump Control modes Control details HEA T mode for room temperature < Desired temperature COOL mode for room temperature Desired temperature (1) HEA T mode → COOL mode Room temperature Desired temperature + 3°F . or 3 min. has passed (2) COOL mode → HEA T mode Room temperature Desired temperature - 3°F .
20 7 TROUBLESHOOTING 7-1. HOW TO CHECK THE P ARTS PCFY -P15NKMU-E PCFY -P24NKMU-E PCFY -P30NKMU-E PCFY -P36NKMU-E Parts name Check points Disconnect the connector then measure the resistance using a tester . (At the ambient temperature 50 " F~86 " F) (Refer to the next page for a detail.
21 4 Φ 4 3 6 5 Φ 3 2 Φ 2 1 Φ 1 Φ 4 Φ 3 Φ 2 Φ 1 Controller board Drive circuit Connector(CN60) DC12V Brown Red Blue Orange Y ellow White M 4 6 2 3 5 1 Blue Brown Y ellow Orange Red White Linear.
22 6 5 4 3 2 1 LED 1k Ω Symptom Check points Operation circuit failure of the micro processor Disconnect the connector on the controller board, then con- nect LED for checking.
23 Notes · High voltage is applied to the connecter (CNMF) for the fan motor . Pay attention to the service. · Do not pull out the connector (CNMF) for the motor with the power supply on. (It causes trouble of the indoor controller circuit board and fan motor .
24 SW3-5 Note : 4 SW3-5 V ane setting Initial setting ● Setting V ane position OFF Set up Standard Standard ON Set up Less draft Upward position than the standard Switch Function Remarks Effective t.
25 0 5 9 4 8 3 7 2 6 1 0 5 9 4 8 3 7 2 6 1 0 5 9 4 8 3 7 2 6 1 0 5 9 4 8 3 7 2 6 1 0 8 F 7 E 6 D 5 C 4 B 3 A 2 9 1 0 8 F 7 E 6 D 5 C 4 B 3 A 2 9 1 Switch SW A Ceiling height selector SWC Option selector Rotary switch Rotary switch SW14 Branch No.
26 • T o operate each indoor unit by each remote controller when installed 2 indoor units or more are near , Pair No. setting is necessary . Pair No. setting is available with the 4 patterns (Setting patters A to D) . Make setting for J41, J42 of indoor controller board and the Pair No.
27 7-3. TEST POINT DIAGRAM 7-3-1. Indoor controller board PCFY -P15NKMU-E PCFY -P24NKMU-E PCFY -P30NKMU-E PCFY -P36NKMU-E CN52 Remote indicator CN51 Centrally controlled CN4Y i-See sensor CN2M Connect.
28 7-3-2. Address board PCFY -P15NKMU-E PCFY -P24NKMU-E PCFY -P30NKMU-E PCFY -P36NKMU-E SW1 Function setting SW12 Address setting 10ths DIGIT SW1 1 Address setting 1st DIGIT SW14 Branch No.
OPERA TING PROCEDURE PHOTOS & ILLUSTRA TIONS 29 8 DISASSEMBL Y PROCEDURE 1. Removing the air intake grille (1) Slide the air intake grille holding knobs (at 2 or 3 loca- tions) to the rear to open the air intake grille.
OPERA TING PROCEDURE PHOTOS & ILLUSTRA TIONS 30 3. Removing the room temperature thermistor (TH21) (1) Remove the air intake grille. (See Figure 1,2) (2) Remove the screw from the beam and remove the beam. (See Photo 1) (3) Remove 2 screws from the electrical cover , and remove the electrical cover .
OPERA TING PROCEDURE PHOTOS & ILLUSTRA TIONS 31 Screw Side panel (Right) Side panel (Left) Sliding the panel to the front Figure 3 6. Removing the side panel (1) Remove the air intake grille. (See Figure 1,2) (2) Remove the screw from the side panel, and remove the side panel by sliding the panel to the front.
OPERA TING PROCEDURE PHOTOS & ILLUSTRA TIONS 32 8. Removing the under panel (1) Remove the air intake grille. (See Figure 1,2) (2) Remove the left and right side panels. (See Figure 3) (3) Remove the beam. (See Photo 1) (4) Remove the electrical cover .
OPERA TING PROCEDURE PHOTOS & ILLUSTRA TIONS 33 12. Removing the Auto vane (1) Remove the intake grille. (See Figure 1,2) (2) Remove the right side panel. (See Figure 3) (3) Remove the vane motor and cover . (See Photo 12) (4) Slide the auto vane to the vane motor side.
OPERA TING PROCEDURE PHOTOS & ILLUSTRA TIONS 34 13. Removing the heat exchanger and LEV (1) Remove the air intake grille. (See Figure 1,2) (2) Remove the beam. (See Photo 1) (3) Remove the electrical cover . (See Photo 1) (4) Pull the electrical box downward.
35.
Copyright 2009 MITSUBISHI ELECTRIC ENGINEERING CO., L TD. Distributed in Feb. 2009 No. OCH450 PDF 7 Made in Japan New publication, effective Feb. 2009 Specifications subject to change without notice HEAD OFFICE : TOKYO BLDG.
An important point after buying a device Mitsubishi Electronics PCFY-P30NKMU-E (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Mitsubishi Electronics PCFY-P30NKMU-E yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Mitsubishi Electronics PCFY-P30NKMU-E - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Mitsubishi Electronics PCFY-P30NKMU-E you will learn all the available features of the product, as well as information on its operation. The information that you get Mitsubishi Electronics PCFY-P30NKMU-E will certainly help you make a decision on the purchase.
If you already are a holder of Mitsubishi Electronics PCFY-P30NKMU-E, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Mitsubishi Electronics PCFY-P30NKMU-E.
However, one of the most important roles played by the user manual is to help in solving problems with Mitsubishi Electronics PCFY-P30NKMU-E. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Mitsubishi Electronics PCFY-P30NKMU-E along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center