Mitsubishi Electric Air Co nditioner Network System PI controller PAC-YG60MCA Installation/Instruction Manual Before using the PI controller, plea se read this installa tion/instruction manu al carefully to ensure proper operation. Keep this installation/instruction manual for futu re reference.
1 • Before using the device, thorou ghly read the follo wing safety precautions and use as dir ected. • Hazards and levels o f danger tha t can occur du e to in correct handling are classified by the following symbols. • After reading this manual, keep this ma nual for future reference.
2 • Confirm that the box contains the following parts. * In addition to the parts mentioned above, other par ts need to be procured locally in order to operate this device. Furthermore , oth er Mitsubishi optional parts may be required depending on how the device is to be used.
3 5 Example of System Configuration Note: • For the shield ground of the M-NET centralized control line for central control, use single-po int grounding at the power unit for the transmission line.
4 6-1. Parts to be Procured Locally Prepare the following parts to install th is device. [Parts to be Purchased Separately] [Recommended Pulse Specifications] Prepare a measuring instrumen t that measures the type of pulse sign als indicated in table below.
5 6-2. Installation Procedure The PI controller PAC-YG60MCA does not ha ve a waterpro of structure. Be sure to install the PI controller inside a control panel tha t is located indoors. Prepare a control panel capable of storing this device such as the one shown in the figure.
6 (3) Refer to "7 Wiring Method " and connect the wires for the po wer line, M-NET transmission line, and input/outpu t signal lines. 7-1. Names of Parts PAC - SC50KUA M-NET N FG L -V +V Diagram Image (Installed within a Contro l Panel) * The wiring in the diagram has bee n simplified.
7 7-2. Connecting the Power Line and M-NET Transmission Line CN16 V+/V -/FG CN17 A/B/S S FG M- NET S / B / A (M1) (M2) U U R Tightening to rque for term inal screws: 1 N·m Connect the device to a pow.
8 7-3. Connecting the Signal Lines • Separate ly procure items such as te rminal blocks and cables locally. • The maximum wire length is 10 0 m. However, since th e use of long wires makes th e device susceptible to noise, using wires shorter than 10 m is recommended.
9 After completing the p rocedures described in "6 Installation Method" and "7 Wiring Method", set the initial settings in accordance with the procedure descr ibed below. (1) M-NET address settin gs (2) Use the dip switches to select functions.
10 Set the dip switches for fu nction selection according to the system to be used. At the time of shipment, all dip switches are set to OFF and the M-NET ad dress is set to 01. *1: When using a system controller (G(B)-50A or T G-2000A), select the "SC setting" and set the pulse we ight value settings from a system controller.
11 The LEDs of this device indicate the pulse in put status and error status of this device. 10-1.Display Content List *1: If a communication error occurs, switch to "Communication Err o r Status Display".
12 Use the following pr ocedure to co nfirm operation of the system. (1) Configure the settings of this devi ce and the system controllers while refe rring to "8 Initial Setting Procedure". (2) Perform an operation from a system co ntroller and confirm whether a connected device can be operat ed normally.
.
.
WT04973X01 This product is designed and int ended fo r use in the residential, commercial and light-i ndustr ial environment. This product at hand is based on the following EU regulations: • Low Vol.
An important point after buying a device Mitsubishi Electronics PAC-YG60MCA (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Mitsubishi Electronics PAC-YG60MCA yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Mitsubishi Electronics PAC-YG60MCA - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Mitsubishi Electronics PAC-YG60MCA you will learn all the available features of the product, as well as information on its operation. The information that you get Mitsubishi Electronics PAC-YG60MCA will certainly help you make a decision on the purchase.
If you already are a holder of Mitsubishi Electronics PAC-YG60MCA, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Mitsubishi Electronics PAC-YG60MCA.
However, one of the most important roles played by the user manual is to help in solving problems with Mitsubishi Electronics PAC-YG60MCA. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Mitsubishi Electronics PAC-YG60MCA along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center