Instruction/ maintenance manual of the product ED6000T Minuteman UPS
Go to page of 23
Para Systems, Inc. 1455 LeMay Driv e Carrollton, TX 75007 Phone: 1-972-446-7363 Fax: 1-972-446-9011 Internet: minutemanups.com UPS Sizing: sizemyups.com PN – 34000355 R2 ED6000T & ED6200T Parall.
1 Table of Contents 1 Important Safety Instructions ................................................... 2 1.1 An Important Notice ............................................................... 2 1.2 Life Support Policy ...............................
2 1 Important Safety Instruction 1.1. An Important Notice 1.1.1 T o ensure safety in all applications where a UPS system is hardwired to the electrical supply the UPS must be in stalled by a Qualified Electrical Contractor . 1.1.2 The UPS has its own internal ener gy source (battery).
4 2 Product Introduction 2.1. System Overview This On-Line UPS protects computer s, servers, internetworking, and telecommunications equipment from blackouts, brownouts, overvoltages, and surges. This On-Line UPS converts the input AC to DC and then back to a True Sine Wave AC output.
6 15 ON and Alarm Silencer Switch 16 OFF Switch 17 Previous Page or Setting Change 18 Next Page 19 Special Function Log in /out 20 Enter or Reconfirmed 21 Utility Input Normal LED 22 Bypass Input Norm.
8 48 Er24 Bypass Input found when running on CVCF mode (CVCF mode not supported) 49 Er26 PFC Over-current 50 Er27 The UPS must be operated in normal mode in parallel system 51 Er28 Bypass Overload Time out and cut off output.
10 2.5. Rear Panel A Casters. B Terminal Block for Input/Output Connections. C Maintenance Bypass Switch. D Input Circuit Breaker. E EPO (Emergency Power Off) Port. F Option Slot 2 is for the SNMP card and the Programmable Relay card only. G Option Slot 1 is for other option cards except the SNMP card and the Programmable Relay card.
12 3.2. Installation Placement This UPS system is intended to be install in a temperature controlled environment that is free of conductive c ontaminants. Select a location, which will provide good air circulation for the UPS at all times. Keep at least 12 inches (30cm) clearance from the rear panel of the UPS to the wall.
14 3.5. Wiring the Input and Output Connections (Qualified Electrical Contractor Only) 3.5.1 A Qualified Electrical Contractor must perform the hardwiring when connecting the Input and Output wire s to the terminal block on the ED6000T UPS. Apply 22.1lb-in of torque force when connecting to the terminal blocks.
16 3.5.1.1.4 Configuration # 3: Output: One 208VAC 6KVA circuit. Total output load not to exceed 6KVA. 1. Connect a jumper wire from L22 to N21. 2. Circuit1 (208VAC): L23 - L1, N22 - L2, G2 - Ground. 3.5.1.1.5 Configuration # 4: Output: One 240VAC 6KVA circuit.
18 3.5.2 A Qualified Electrical Contractor must perform the hardwiring when connecting the Input and Output wire s to the terminal block on the ED6200T UPS. Apply 22.1lb-in of torque force when connecting to the terminal blocks. The Input and Output of the UPS MUST be Hardwired.
20 3.6.1.6 The UPS will perform another se lf-test and the LCD display will change from drawing C to drawing D. During the self-test the UPS will switch to the Battery mode for approximately 4-seconds, then the LCD display will change from drawing D to drawing E1.
22 I * It shows the UPS is providing power to the “load”. 3.6.3 Measured V alues detected by UPS 3.6.3.1 If you would like to check the measured values detected by the UPS, please use the scroll down and scroll up keypads.
24 P * It shows the Internal Temperature of the UPS System. 3.6.4 UPS Default Data and S pecial Function Features 3.6.4.1 Once the UPS has successfully started up, press the Special Function keypad to change the LCD display screen to drawing Q1. Q1 * It shows the Buzzer is “Enabled”.
26 U * It shows the Inverter Output Voltage setting. V1 * It shows the UPS is operated in the “Normal mode”. V2 * It shows the UPS is operated in the “Eco mode”. W *It shows the Fine Tune Adjustment % from 0% to 3% or -0% to -3%. X * It shows the UPS Identification Number.
28 3.6.5.10 When all of the setting changes are complete, press the enter keypad to save all the changes. Then the LCD screen will display drawing Z, then the LCD screen will change to drawing AA to confirm the changes.
30 3.6.8.1.12 Press and hold the On Switch (on the front panel of the UPS) for approximately 3-seconds, then release. The audible alarm will sound 2- beeps. The UPS will perform its normal st artup test. Once the startup is complete the UPS will be in the normal On-Line mode.
32 6 Troubleshooting Guide If the UPS malfunctions, check the followings: a. Is the wiring of the input and the output correct? b. Is the input voltage within the acceptable window of the UPS? If items a. and b. above are correct then proceed with the following chart.
34 7.1. Battery Replacement Procedure (QUALIFIED SERVICE PERSONNEL ONLY) This UPS system does not have Hot- swappable batteries. The UPS system must be turned Off to perform the Battery Replacement. 7.1.1 Turn Of f all the equipment that is connected to the UPS.
36 7.1.21 Looking from the front of the U PS on the lef t-hand side (FIG . 4), disconnect the battery negative (Black) wire. Place a piece of electrical tape over the end of battery negative (Black) wire. 7.1.22 Disconnect battery jumper “A” and plac e a piece of electrical t ape over the end of battery jumper wire “A”.
38 8 Specifications MODEL ED6000T (Has an internal Galvanic isolation step-down transformer) ED6200T Topology Double Conversion On-Line, True Sine Wave Maximum Power Capacity 6000VA/4200Watts INPUT Nu.
40 9 Obtaining Service 9.1.1 Use the troubleshooting secti on to eliminate obvious causes. 9.1.2 V erify there are no circuit breakers tripped. A tripped circuit breaker is the most common problem.
42 11 Declaration of Conformity Application of Council Dire ctive(s): 89/336/EEC, 73/23/EEC Standard(s) to which Conformity is declared: EN62040-1-1, EN62040-2, EN61000-3-2, EN61000-3-3, UL 1778, cUL (CSA 22.2 no. 107.1) Manufacturer’s Name: Para Systems, Inc.
An important point after buying a device Minuteman UPS ED6000T (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Minuteman UPS ED6000T yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Minuteman UPS ED6000T - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Minuteman UPS ED6000T you will learn all the available features of the product, as well as information on its operation. The information that you get Minuteman UPS ED6000T will certainly help you make a decision on the purchase.
If you already are a holder of Minuteman UPS ED6000T, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Minuteman UPS ED6000T.
However, one of the most important roles played by the user manual is to help in solving problems with Minuteman UPS ED6000T. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Minuteman UPS ED6000T along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center