R Installation Guide Softswitch128 TM (XPS) and GRAFIK Systems TM (XP) Switching Panels Please Read Contents P P a a n n e e l l M M o o d d e e l l N N u u m m b b e e r r G G u u i i d d e e Softswi.
XPS24-1204ML-20-CGP____ R 2 Installation Guide for Switching Panels Panel Model Number Guide Softswitch128 TM (XPS) XPS24-120FT -CGP____ Feed-Through Model Numbers Example Number of Circuits in Panel .
Number of Circuits in Panel Indicates number of switching circuits in the panel: 4, 8, 12, 16, 20, 24, 28, 32, 36, 40, 44, or 48 Feed V oltage 1, 2 Omit for dual voltage 120 for 120 V 230 for 230 V (C.
Panel Dimensions Mini Panel Bottom View T op View Right Side Left Side Dimensions are in inches (mm). Front View 14.38 (365) 15.875 (403) 8.00 (203) 2.2 (56) 4.2 (107) 0.15 (4) 1.34 (34) 21.50 (546) 24.50 (622) 24.00 (610) 2.21 (56) 15.13 (384) 10.75 (273) 4.
R Installation Guide for Switching Panels 5 Dimensions are in inches (mm). Panel Dimensions (continued) Bottom View T op View Right Side Standar d Panel Left Side Front View 14.375 (365) 15.875 (403) 2.43 (62) 8.00 (203) 4.21 (107) 0.15 (4) 2.69 (68) 41.
R 6 Installation Guide for Switching Panels Panel Dimensions (continued) Large Panel (120/277/347 V only) Dimensions are in inches (mm). Bottom View T op View Right Side Left Side Front View 22.0 (559) 23.50 (597) 2.50 (64) 3.34 (85) 6.30 (160) 0.15 (4) 45.
R Installation Guide for Switching Panels 7 Panel Dimensions (continued) Extra-Large Panel (277/347 V only) Bottom View T op View Right Side Dimensions are in inches (mm). Left Side Front View 22.0 (559) 23.50 (597) 3.0 (76) 3.45 (88) 6.3 (160) 0.15 (4) 68.
Panel Mounting Panel and TUB Mounting Mounting Guidelines • For Indoor Use Only! NEMA, T ype 1 enclosure, IP20. • Large and extra-large panels for surface mount only . • Panel generates heat. Mount where ambient temperature is 32-104 ºF (0-40 ºC).
R Installation Guide for Switching Panels 9 Panel Mounting (continued) Rough-In Panel Inter ior Mounting (Rough-in Panels ONL Y) (120/277/347 V only) Mounting for SINT or XINT Plate: • Insert interior into TUB. • Rest interior on bottom of TUB. • Press inter ior flat into back of TUB.
R 10 Installation Guide for Switching Panels • Use a trough when the switching panel is far away fr om the distribution panel. Splice neutrals in trough. • Wire the switching panel similar to a lighting distribution panel. Run feed and load wir ing.
R Installation Guide for Switching Panels 11 Wir ing (continued) H SH H SH H SH H SH H SH Panel with Branch Cir cuit Br eakers: Feed and Load Wir ing (120/277/347 V only) Bypass jumpers - do not remov.
R 12 Installation Guide for Switching Panels Wir ing (continued) L SL N L SL N L SL N L SL N Panel with Isolation Switch: Feed and Load Wir ing (230/220-240 V only) Bypass jumpers - do not remove Load Ground bus Main feeds: Phase A, B, C, and Neutral Wiring Tips • Wire the switching panel similar to wiring a lighting distr ibution panel.
R Installation Guide for Switching Panels 13 System Wir ing Overview Review the options below for information on wiring your panel corr ectly into your specific system. A. Softswitch128 TM (XPS) panel: Refer to the Softswitch128 Setup and Operation Manual for detailed wiring information.
R 14 Installation Guide for Switching Panels Ratings Softswitch128 TM (XPS) 3Ø 4W or 1Ø 3W Main Lug Accepts: #4 AWG to 250 KCMIL (MCM) (25-120 mm 2 ) 120 V Panels with Branch Circuit Br eakers XPS M.
R Installation Guide for Switching Panels 15 Ratings (continued) GRAFIK Systems TM (XP) 3Ø 4W or 1Ø 3W Main Lug Accepts: #4 AWG to 250 KCMIL (MCM) (25-120 mm 2 ) 120 V Panels with Branch Circuit Br .
R 16 Installation Guide for Switching Panels Activate Loads in Bypass A. Complete load wiring. B. Check that the bypass jumpers ar e in place. These jumpers protect fr om load faults and must be used to check load wiring when it is installed or modified.
R Installation Guide for Switching Panels 17 Complete Installation Remove Bypass Jumpers A. After all load wiring has been checked, turn circuit breakers OFF . B. Remove and store the bypass jumpers for possible future use. C. T ur n cir cuit breakers ON.
R 18 Installation Guide for Switching Panels Notes.
R Installation Guide for Switching Panels 19 W arranty L L u u t t r r o o n n E E l l e e c c t t r r o o n n i i c c s s C C o o . . , , I I n n c c .
R Lutron Electronics Co., Inc. Made and printed in U.S.A. 09/06 P/N 032-162 Rev . A Contact Information Internet: www .lutron.com E-mail: product@lutr on.com WORLD HEADQUARTERS USA Lutron Electr onics Co., Inc. 7200 Suter Road, Coopersburg, P A 18036-1299 TEL +1.
An important point after buying a device Lutron Electronics Switch (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Lutron Electronics Switch yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Lutron Electronics Switch - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Lutron Electronics Switch you will learn all the available features of the product, as well as information on its operation. The information that you get Lutron Electronics Switch will certainly help you make a decision on the purchase.
If you already are a holder of Lutron Electronics Switch, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Lutron Electronics Switch.
However, one of the most important roles played by the user manual is to help in solving problems with Lutron Electronics Switch. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Lutron Electronics Switch along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center