SITE MONITORING SiteGate-232 U SER ’ S M ANUAL.
Rev. (08-JULY-98) © 1996-98 Liebert Corporation 2 SiteGate-232 Technical Instructions Contents Introduction .................................................................................................. 3 Specifications ..........................
© 1996-98 Liebert Corporation 3 Rev. (08-JULY-98) Introduction The SiteGate-232 is part of the Liebert SiteScan gateway family and provides communications between a workstation and a control module network (CMnet) consisting of fewer than 50 modules.
Rev. (08-JULY-98) © 1996-98 Liebert Corporation 4 Battery: Seven-year lithium battery provides a minimum of 10,000 hours of data retention during power outages. Fault Detection: Hardware watchdog timer. Software Requirements: One LGM module driver as FB #15.
© 1996-98 Liebert Corporation 5 Rev. (08-JULY-98) segment. A segment is defined as the network of modules between main nodes. Main nodes can be represented by a gateway module, or a repeater (part no. REPOPT). A repeater can be used to end one segment and begin another, all on the same CMnet.
Rev. (08-JULY-98) © 1996-98 Liebert Corporation 6 Power Wiring CAUTION: The SiteGate-232 modules are Class 2 devices (less than 30 VAC). Take appropriate isolation measures when mounting a SiteGate-232 module in a control panel where Class 1 devices or wiring are present.
© 1996-98 Liebert Corporation 7 Rev. (08-JULY-98) Addressing, Baud Rates, and Console Settings The SiteGate-232 module's address is factory-set as control module #1 and cannot be changed. NOTE: The CMnet Baud Rate jumper (see Figure 1 for location) is only used to configure the CMnet for 156k bps.
Rev. (08-JULY-98) © 1996-98 Liebert Corporation 8 Procedure 1. Turn the SiteGate-232's power switch OFF. 2. Set the module's baud rates and console port settings using the 8-position dip switch (see Figure 1 for switch location). 3. Turn the SiteGate-232's power switch ON.
© 1996-98 Liebert Corporation 9 Rev. (08-JULY-98) The "SETGCM" Command The "SETGCM" command initializes the SiteGate-232 with system parameters including Maxnet, the workstation t.
Rev. (08-JULY-98) © 1996-98 Liebert Corporation 10 Cables Several cables, which vary depending upon the communication requirements, are available. The following is a description and wiring configuration of each cable (the arrows indicate direction of data flow).
© 1996-98 Liebert Corporation 11 Rev. (08-JULY-98) Sit e G a t e - 2 32 C ons ole Port # 2 Term ina l N umb e r TX RX GND RX TX GND 1 2 3 4 5 3 2 7 N o conne c ti o n requ i re d N o conne c ti o n r.
Rev. (08-JULY-98) © 1996-98 Liebert Corporation 12 Common Problems Modem connected to the SiteGate-232 will not answer. Make sure the TR light on the modem is ON; if it is OFF check the modem cables. Verify connection and baud rate with the SiteGate-232.
© 1996-98 Liebert Corporation 13 Rev. (08-JULY-98) Figure 11: SiteGate-232 LED Identification RUN LED ERROR LED CONDITION 2 flashes per sec. Off All normal 2 flashes per sec. 2 flashes per sec. 5 minute auto-restart delay after system error. 2 flashes per sec.
Rev. (08-JULY-98) © 1996-98 Liebert Corporation 14 LED Power-up Sequence During power-up, the module goes through an initialization and self test sequence. Proper module power-up can be verified by observing the LEDs as follows: 1. The Run and Error LEDs turn on and begin blinking.
© 1996-98 Liebert Corporation 15 Rev. (08-JULY-98) LGM Module Driver Parameter Page Function Block Type: LGM (LGM Module Driver) Name SiteGate-232 Line 1 LG 2 CM 1 FB 15 Flags — ID ID14 Tele NB All.
Rev. (08-JULY-98) © 1996-98 Liebert Corporation 16 If not connected, and with no alarms pending delivery, reset modem every 5:00 (mm:ss). Note: the minimum value for this is 5:00. If connected, but no activity has been detected for 20:00 (mm:ss), hang up and reset modem.
© 1996-98 Liebert Corporation 17 Rev. (08-JULY-98) Output character pacing? If set to YES, this parameter reduces CMnet transmission speed by 50%. This may be necessary when operating at 38.
Rev. (08-JULY-98) © 1996-98 Liebert Corporation 18 Modem Control Parameters Modem Reset : This is a user definable parameter that sends a reset string to the modem. Dial Prefix : This parameter sets the dial prefix used for dialing out alarms. Phone Number : This parameter sets the number to be dialed out for alarms.
© 1996-98 Liebert Corporation 19 Rev. (08-JULY-98) Status Page Function Block Type: LGM (LGM Module Driver) Name SiteGate-232 Line 1 LG 1 CM 1 FB 15 Flags --- ID CM01_15 Tele DC26 All Options Y Type .
Rev. (08-JULY-98) © 1996-98 Liebert Corporation 20 LGM Module Driver Status This is the overall module status. Function Block Type: This the Module Driver's three-character filename. Name: This is the name referring to the space or equipment used.
© 1996-98 Liebert Corporation 21 Rev. (08-JULY-98) Module Halted : All GFB related tasks have stopped. This can only happen if there have been 3 or more frequent System Errors. System Errors are errors that are severe enough to cause the module to reset.
Rev. (08-JULY-98) © 1996-98 Liebert Corporation 22 Module time and date: Shows the current module date and time. Time since last reset: The amount of time that has elapsed since the last module reset. CMnet Communication lost: If "YES", this module has detected that it is alone on this CMnet.
SiteGate-232 - User's Manual A World Leader in Computer Support Systems Environmental Control • Power Protection • Site Monitoring/Control Service • Parts • Training Liebert Corporation designs, manufactures, and markets complete systems for improvement of computer uptime and performance.
An important point after buying a device Liebert 232 (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Liebert 232 yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Liebert 232 - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Liebert 232 you will learn all the available features of the product, as well as information on its operation. The information that you get Liebert 232 will certainly help you make a decision on the purchase.
If you already are a holder of Liebert 232, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Liebert 232.
However, one of the most important roles played by the user manual is to help in solving problems with Liebert 232. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Liebert 232 along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center