Instruction/ maintenance manual of the product 1000kVA Liebert
Go to page of 120
AC P OWER S YSTEMS S ERIES 610™ UPS O PERATION & M AINTENANCE M ANUAL 100 - 1000kV A, 60Hz Three Phase Multi-Module.
B ATTERY C ABINET P RECAUTIONS The following warning appl ies to all battery cabine ts supplied with UPS syst ems. Additional warn- ings and cautions applicab le to battery cabinets may be found in Important Safety Instructions and 4.4 - Battery Maintenance .
i T ABLE OF CONTENTS B ATTERY C ABINET P RECA UTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . I NSIDE F RONT C OVER C ONTACTIN G L IEBERT FOR S UPPORT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . I NSIDE F RONT C OVER I MPORT ANT S AFETY I NSTRUCTION S .
ii 3.3 Modes of Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73 3.3.1 Load on Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
iii FIGURES Figure 1 Multi-Module UPS, 100-500kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Figure 2 Multi-Module UPS, 500-750kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
iv Figure 50 Batte ry equalize screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62 Figure 51 SCC status and alarm message areas . . . . . . . . . . . . . . . . . . . . . . . . .
1 I MPORT A NT S AFETY I NSTRUCTIONS SAVE THESE INSTRUCTIONS This manual co ntains important ins tructions that shou ld be followe d during insta llation and mainte- nance of your Series 610 UPS and batteries. ! WARNING Exercise extreme care when hand ling UPS cabi nets to avoid equipment damage or i njury to personnel.
Introd uction 2 1.0 I NTRODUCTION 1.1 System Description The role of the parallel-redundan t multi-module UPS system is to supply uni nterruptible, clean power to the critical load. The UPS maintains a full -voltage, low -distortion outp ut, even if the ut ility source power sags, becomes distorted or fails.
Introd uction 3 In the unlikely event of a fault wi thin the UPS, the SCC control logic, which continuously monitors all critical circuits within the UPS system, transfers the load to bypa ss without interruption and simul- taneously activates local and remote al arms.
Introd uction 4 Figure 3 System Control Cabinet s T ypes of System Control Cabinet s (SCCs) • SCCT —A stand-alone cabi net containing system contro l logic for up t o six UPS modules, a sta tic bypass switch, manual ly operated disconnects for the stat ic bypass switch and two motor-oper- ated system circuit breakers.
Introd uction 5 Other Factors to Consider Reliability depends on more than just UPS module desig n. Improper installa tion can cause any sys- tem to fail.
Introd uction 6 1.4.3 Recharge After the utility source power is re stored or an alternate power source becomes available, each recti- fier/charger slowly walks-in to once agai n power the inverters and recharge the battery plant .
Introd uction 7 Figure 4 SCC controls and display screen wi th ex ample of the Monitor/Mimic screen © 1989-2003.
Introd uction 8 The operator controls and Monitor/Mimic screen for the System Co ntrol Cabine t (SCC) are shown in Figure 4 . The controls and display screen for each UPS module are shown in Figure 5 . Each cabinet (SCC or module) has the display s and controls required to monitor an d perform its functions.
Introd uction 9 2. Battery Racks or Cabinets The battery racks are specifically designed for stationary service batteries. They are painted with electrolyte-resistant paint f or corrosion resistance. Ba ttery cabinets are available f or 150 through 600kVA modules.
Theory of Operati on 10 2.0 T HEORY OF O PERATION 2.1 General Compone nt Descriptions The UPS system includes all of the equipment necessary to continuously provide computer-grade AC power to a critical load, even when there is an inte rruption of the utility power.
Theory of Operati on 11 Figure 6 UPS module block diagram 2.1.2 UPS Module The UPS module consists of module controls, a rect ifier/charger, an inverter , protective devices and other accessories. Module Controls: The module control logic monitors performance of the UPS module.
Theory of Operati on 12 2.2 Det ailed Component Descrip tions 2.2.1 Controls Hardware The Series 610 UPS Operator Interface Display System is designed to provide all of t he information that is required for the operation of each UPS cabi net (the System Control Cabinet and each module).
Theory of Operati on 13 2.2.2 Rectifier/Charger The UPS module rectifier/charger consists of an in put circuit breaker, AC cu rrent limiting circuit, battery equalize charge circuit, DC filter, battery charge current limiti ng circuit and bridge rectifiers.
Theory of Operati on 14 2.2.3 Battery Charging Circuit The UPS module charging circuit is capab le of recharging the battery plant to 95% of full capacity within 10 times the discharge time . Recharging the last 5% takes lo nger because of characteristics inherent in the battery.
Theory of Operati on 15 2.2.4 Inverter The inverter is a s olid state devi ce that converts th e DC output of the rectifier/charger or the battery to AC power. Operation The inverter converts DC power—from either the battery or the rectifier/ charger—into three pulse- width-modulated/six-step waveforms.
Theory of Operati on 16 2.2.5 St atic Bypas s A static bypass is an integral part of the UPS System Control Cabinet (SCC). Refer to Figure 7 . The static bypass consists of two re v erse-paralleled SC.
Theory of Operati on 17 St atic Switch Isolation The motor-operated system bypass ci rcuit breaker (SBB), wired in paral lel with the static switch, automatically closes in approximat ely 200 milliseconds aft er the load is transferred to the bypass power source, removing the static switch from the power flow.
Theory of Operati on 18 T ransfer and Retransfer Con ditions 1. Automatic Transfers to Bypass Critical bus con ditions that w ill initiate an au tomatic transfer of the critical load from the UPS system to the bypass source are: a. System Overload: overcurrent co ndition in excess o f the overload rating of the System Control Cabinet (SCC).
Theory of Operati on 19 6. Retran sfer Inhibited A retransfer from the bypass source to the UPS system shall be i nhibited if any of the following conditions exist: a. Manual (and Automatic) Retransfer Inhibitions: 1. UPS system-to-bypass voltag e difference ( ∆ V) exceeds a predetermined percentage (normally 5%).
Operation 20 3.0 O PERATION 3.1 Display Screen a nd Operator Controls Each Liebert Series 610 UPS cabine t is equipped with a microprocessor-based Operator Control Pane l and Display Screen and System Control Panel design ed for convenient and reliable operation.
Operation 21 Figure 8 T ypical operator controls T able 1 T ypical operator controls Item Description Function 1 Input Circuit Breaker (CB1 ) This manually operated circuit breaker prov ides power to the UPS module re ctifier. In 625-750kVA modules and some 500kVA modu le s, this breaker is l ocated in the transformer ca binet.
Operation 22 Figure 9 Operator controls, typical SCCT Syst em Control Cabinet T able 2 T ypical SCCT System Contro l Cabinet operator contro ls Item Description Function 1 UPS Output Circuit Breaker This motorized circuit breaker connects the critical load to the UPS system output.
Operation 23 Figure 10 Series 610 UPS and SCC operator control p anels T able 3 Ser ies 610 UPS and SCC operator control p anels Item Description (Location) Function 1 Display Screen (SCC and modules) This screen displays all vi tal UPS informati on in one convenient lo cation.
Operation 24 Figure 1 1 Switches behind SCC control p anel door T able 4 Ser ies 610 UPS and SCC operator control p anels Item Description (Location) Function 1 Interlock Button (on rear of Control Panel) Press this button to make authorized change s to any site parameter protected by the Security Access function.
Operation 25 3.2 Menu T ree Navigation The Operator Interface Display is a blue-backg round display with white text. The display is alwa ys on, but the backli ght will remain l it for 15 minut es followin g any display act ivation. After 1 5 minutes, the backlight will go out and the display may ap pear very dim.
Operation 26 Figure 12 illustrates the primary screen s that you can access through the Operator In terface Display System. The liqu id crystal display (LCD) screen pro vides a full 80 characters by 25 l ines of informa- tion for easy re adability. The following section s describe wh at these screens disp lay and how and when to use them.
Operation 27 From any primary screen (accessed directly from th e Master Menu), pushing the Select pad once will return you to the Master Menu. Fr om any secondary screen, pushing th e Select pad twice will return you to the Master Menu. Please note that some screens ha ve multiple pages.
Operation 28 • Battery Test (MMU Only)— The optional battery te st screen allows the operator to perform manual battery tests to determine the general condition of the ba ttery system. The results of the last 10 tests are recorded in no n-volatile storage and can be re trieved through the battery test results screen.
Operation 29 St atus/Alarm Message Areas The status/alarm message areas display vital informati on about the operation of the UPS system. During normal operation no alarm messages should be present. Change s in the status of the system and possible alarm conditions can be monitored.
Operation 30 3.2.3 Module Monitor/Mimic Display Screen From modul e Master Me nu move the highlighted cursor to MONITOR/MIMIC DISPLAY. Press the Select pad and the Monitor/Mimic screen is displayed. The Monitor/Mimic display screen is a simplified block diagram of the UPS module and power connec- tions.
Operation 31 Alarm Messages The alarm message area displa ys vital informati o n about the operatio n of the UPS system. During normal operation no alarm messages should be pr esent. Alarm conditions can be monitored. The alarm messages are display ed in reverse video (hig hlighted— light on dark).
Operation 32 Figure 16 Monitor/Mimic displa y example: Normal power f low UPS INPUT PWR UPS RA TINGS A-B B-C C- A BYP AS S INPUT A-B B-C C-A LOAD AB C A-B B-C C-A OK to T ransfer Static Sw itch Connec.
Operation 33 Figure 17 Monitor/Mimic disp lay example: Utility fail UPS RA TIN GS LOAD Byp Not A vail Static Sw Unable Module Sum Alm UPS INPUT PW R BYP ASS INPUT A-B B-C C-A 0V 0V 0V 0H z 0V 0V 0V A-.
Operation 34 Figure 18 Monitor/Mimic display example: Load on byp ass, UPS modules on and chargin g battery UPS INPUT PWR BA TTERY VOL TS 540 AMPS 75 CHARG UPS RA T INGS A-B B-C C- A OUTPUT VOL T AGE LOAD AB C 0K V A/ 0 K W 0A 0A 0A A-B B-C C- A 480V 480V 480V 480V 480V 480V 90A 90A 90A AP648-84 RA TED 40 0 KV A 60.
Operation 35 Figure 19 Monitor/Mimic display exampl e: Load on UPS, one UPS module off line UPS INPUT PWR BA TTERY VOL TS 540 AMPS 75 CHARG UPS RA TINGS A-B B-C C -A O U T P U T V O LTA G E LOAD AB C 0K V A/ 0K W 0A 0A 0A A-B B-C C -A 380V 380V 380V 380V 380V 380V 75A 75A 75A AP658-71 RA TED 500 KV A 50.
Operation 36 Figure 20 Monitor/Mimic Disp lay example: Load on byp ass, all UPS modules off line UPS INPUT PWR BA TTERY VOL TS 540 AMPS 75 CHARG UPS RA TINGS A-B B-C C-A O U T P U T V O LTA G E LOAD AB C 0K V A/ 0K W 0A 0A 0A A-B B-C C-A 380V 380V 380V 380V 380V 380V 75A 75A 75A AP658-71 RA TE D 500 KVA 50.
Operation 37 3.2.4 W alk-In Display Screen From the module Master Menu, highlight WALK-IN DISPLAY and then press the Select pad. Note that this screen is displayed at the UPS modules but is not required at the System Control Cabinet (SCC).
Operation 38 3.2.5 St atus Reports Scree ns Go to the Master Menu and mo ve the highlighted cursor to STATUS REPORTS. Press the Select button and the Status Reports screen is displayed. The Status Report screen is divided into four submenu reports: PRESENT STATUS, EV ENT HIS- TORY, HISTORY STATUS and SYSTEM STATUS.
Operation 39 Figure 23 Present st atus report screens, SCC (above) and module Event History The Event History screen lists the activ e alarms pr esent in the UPS syste m (SCC) or modu les.
Operation 40 History St atus The History Status screen displ ays 64 frames, of 4 milliseconds each, from th e Present Status screen. Note that the va lues for output volts and amps are updated on ce each millisecon d. Alarms are listed in the sequence they occurred, with in 1 millisecond resolution.
Operation 41 Table 5 shows the alarm conditions that stop the History Status buffer from gathering data. The History Status buffer does not resume collecti ng new frames until the fault is cleared and the Alarm Reset pad is pressed for more than 5 se conds (or until th e screen clears).
Operation 42 System St atus The System Status scre en displays the modu le Total Opera ting Hours, Enab le Backlight and th e Bat- tery Cycle Monitor. Battery Cycle Monitor—Module Only Selecting the Battery Cycle Monitor gives you access to detailed inf o rmation about the module’s most recent battery discharge ev ents.
Operation 43 The Summary screen ( Figure 27 ) s hows Total Number of Discha rge Cycles, Accumulated Battery Time, Accumulated Battery Amp Hours, Accumulated Battery Kilowatt Hours and Battery Tempera- ture. During a battery discharge event, the screen changes to show information about the present dis- charge cycle.
Operation 44 3.2.6 System Configuration Screens Go to the Master Menu and move the highlighted cursor to SYSTEM CONFIGURATION. Press the Select pad and the System Configuration screen is display ed. The System Configuration screen lists parameters that can be changed to adjust your UPS modules and the SCC to your site requirem ents.
Operation 45 Date This is the system’s real-t ime date setting. The system control program sends to each module the date entered at the Syst em Control Cabi net (SCC). You cannot change the system date f rom the control panel of a UPS module. Figure 30 Date screen To reset the date, do the fo llowing at the SCC.
Operation 46 Tim e This is the system’s real-time clock. The system control program sends to each module the time entered at the System Control Ca binet (SCC). You cannot change the system time from the control panel of a UPS module. Figure 31 Time screen To reset the time do the following at the SCC: 1.
Operation 47 Auto Dial This is a feature that automa tically dials (through a customer sup plied PC-compatible modem) a pre- programmed telephone numb er (up to 12 digits) when specified alarm condit ions occur within the UPS system. The connection for the modem is at the SCC.
Operation 48 Modem Baud Rate This sets the transmission rate at which the syst em relays data to a te rminal through the modem. Figure 33 Modem baud rate To change the modem baud rate, do the followin g at the SCC: 1. From the System C onfiguration screen , press the Up or Down pad to move the highlighted cursor to Auto Dial.
Operation 49 To change the Maximum Auto-Retransfer Attemp ts parameter, do the following at the SCC: 1. From the System Config uration Screen, press the Up or Down pad to highlight Maximum Auto- Retransfer Attempts. 2. Press the Select pad. The screen above will appear.
Operation 50 Figure 37 Battery test screen—MMU only Figure 38 Battery test resu lt s screen Continuous Duty Static Switch (Optional) This option applies to SCC only.
Operation 51 Figure 39 Monitor/Mimic display exam ple: Contin uous Duty St atic Switch Remote Monitor The Remote Monitor Pa nel (optional) displays eigh t (8) alarms. These alarms are also available for customer use through a set of contac ts on a separate terminal board.
Operation 52 3.2.7 Alarm Limit Settings Screen Go to the Master Menu and mo ve the highlighted cursor to LIMIT SETTINGS. Press the Select pad and the Limit Settings screen is displayed. The Alarm Limit Settings screen ha s Security Access to enable an authorized L iebert field-service engineer to adjust the UPS system alarm limit settings.
Operation 53 Battery Rating (Modules Only): This setting is a ba ttery discharge rating in kilowatts under par- tial load for an extended period , typically 60 mi nutes. The UPS uses the two battery s hutdown voltage settings and the two battery discha rge ratings in computing rated an d calculated time remaining dur- ing a discharg e event.
Operation 54 3.2.8 Load T ransfer Procedures Screen Go to the SCC Master Menu and mo ve the highlighted cursor to LOAD TRANSFER PROCE- DURES. Note that this screen is displayed at the Sy stem Control Cabinet but is not required at the UPS modules. Press the Select pad and the Load Transfer Procedures sc reen is displayed.
Operation 55 3.2.9 St art-Up Procedures Screen From the SCC Master Menu, move the highlighted cursor to START-UP PROCEDURES. Press the Select pad and the SCC Start-Up Procedures screen is displayed ( Figure 42 ). This screen contains the steps you must follow to start-up the UPS sy stem.
Operation 56 Figure 43 Module st art- up procedures screens Prior to this procedure, supply po wer to the critical load through th e bypass line (at the SCC).
Operation 57 Figure 44 SCC shut down procedures screen To perform the shutdown procedure, transfer the cri tical load from the UPS system to the bypass line. Shut down each UPS modu le according to the module Shutdown Procedures. Refer to 3.4.5 - S hutdown Procedures for more details, including emergency shutdowns.
Operation 58 To perform the shutdown procedure, transfer the criti cal load from the UPS sy stem to the bypa ss line (at the SCC). Then trip open the UPS module outp ut and battery circuit break er (MBD) and manually open the UPS module input circuit breaker.
Operation 59 Values for Calcu lated Total Time and Calculated Ti me Rema ining will ap pear on the screen approxi- mately two minutes after the begi nning of the discharge event. Calculated Time Rema ining also appears on the Present Status Report screen.
Operation 60 The Series 610 dynamically ad just s the Battery Shutdown voltage ba sed on battery characteristics and the length of the current disc harge event.
Operation 61 3.2.12 Meter Calibration Scre en Go to the Master Menu and mo ve the highlighted cursor to METER CALIBRATION. Press the Select pad and the Meter Calibration screen is disp layed. The Meter Calibration screen enables a Liebert field-servic e engineer to adjust the calibration of the UPS metered functions at ea ch cabinet.
Operation 62 3.2.13 Battery Equalize Scre en Go to the Master Menu and move the highlighted cursor to BATT ERY EQUALIZE. P ress the Select pad and the Battery Equali ze screen is displayed. The Battery Equalize screen enables the operator to adjust the battery equalize time.
Operation 63 3.2.14 Alarm and S tatus Messages Module St atus Messages The module status messages indica te how many UPS modules are included in the system and the present status of each module. The following status messages may app ear in the module status area.
Operation 64 Load Block Messages Status messages in the Load Block indicate how many modules are in the system, how many modules are ON LINE and whether the sy stem is operatin g in the red undant mode. The following status messages may app ear in the load block.
Operation 65 T able 9 Alarm messages - meaning and corrective action Alarm Message Cabinet Location Special Functions Meaning and Corrective Action AC INPUT Input Fail MMU — The rectifier input line voltage is outs ide of specified limits or th e input circuit breaker is op ened while the battery circuit breaker remains close d.
Operation 66 BYPASS (Cont’d.) Auto Tran sfer to Bypass SCC D, E, F The critical load has been automatical ly transferred to the bypass line. Use the History Status screen to det ermine the cause for the transfer. Clear all of the alarms before atte mpting to retransfer the load fro m bypass to UPS.
Operation 67 UPS SYSTEM (Cont’d.) Overload Transfer SCC D, F, L, S The load on the UPS has exceeded the current versus time window of system overload capacity.
Operation 68 Battery Overtemp MMU D, S Battery Temp option must be installed and enabled. Battery Temp exceeds the programmed limit set i n Alarm Settings screen for more th an one minutes.
Operation 69 T able 10 Alarm message s - summary Alarm Message MMU SCC Special Functions Input Fail X — — DC Ground Fault X — D, L, S DC Capacitor Fuse Blown X — D , F, S Battery CB Open X, R .
Operation 70 3.2.15 Communication Interfaces Your Liebert Series 610 UPS includes the follow ing communication ports: • Worldwide reporting to a remo te terminal through a modem • Reporting to a l.
Operation 71 For example, to see a copy of information on the Present Status Report screen from the SCC (see Present Status in this manua l), press the “A” key (either uppercase or lowercase can be used for all except the date and time commands) and then the En ter key.
Operation 72 Remote Monitor Panel The Liebert Remote Monitor Panel provides an LED indication of the followin g conditions: • Load On UPS • Load On Bypass • Battery Discharge • Low Battery War.
Operation 73 3.3 Modes of Operation This section il lustrates the flow o f power throug h circuit breakers, switch es and UPS components during various modes of operation. An SCCT with three modules is shown. The same modes of opera- tion apply to all configurat ions of the Liebert Series 610 UPS multi- module system.
Operation 74 3.3.1 Load on Byp ass Load on Bypass, with the UPS not available, is shown in Figure 52 . The UPS system could be in this mode of operat ion during either initial start-up or UPS system shutdown and isolation for mai nte- nance. Figure 52 Load on byp ass, UPS not available 3.
Operation 75 Figure 53 Load on byp ass, UPS available Figure 54 Load on UPS, byp ass available BIB SKRU MIB MBB I R #2 UPS CB1 CB2 I R #1 UPS CB1 System Controls I R #3 UPS CB1 CB2 RIB RIB CB2 RIB BFB.
Operation 76 3.3.3 Moment ary Overloads An overload in the critical load will continue to be supplied by the UPS system if the overload condi- tion does not exceed the curre nt vers us time curve of overload capacity fo r either the SCC rating or for the number of modules on-lin e.
Operation 77 3.3.4 Input Power Failure—Load on Battery If the utility AC p ower source fails o r is outside the acceptable range, the battery plant becomes the power source for the UPS mo dule inverter s. The UPS system continues to supp ly power to the critical load and al so to the controls of the UPS modu les and the SCC.
Operation 78 3.3.5 One Module Off-Line A multi-module UPS system can be supplied with a back-up (red undant) UPS module, which is the typical configura tion. A redundan t system includes one more modu le than the number required to supply the critical load.
Operation 79 3.3.6 Off Battery The battery plant can be disconnected from the UPS modules, i f required for b attery maintenance , by opening the module battery disco nnect (MBD) circuit brea ker(s).
Operation 80 3.3.7 Emergency Modules Off The Local Emergency Modules Off (LEMO) mod e is used to remove power from all UPS system com- ponents and the critical load will continue to b e supplied through the bypass line. The Emergency Module Off control is a guarded pad on the SCC Control Panel (see Figure 10 ).
Operation 81 3.3.8 Remote Emergency Power Off The Remote Emergency Power Of f (REPO) mode is us ed to remove all power from the critical load. The Remote Emergency Power Of f co ntrol is a switch located remote ly from the UPS system. It will normally be in the same room as the critical load equipment.
Operation 82 3.3.9 System Shut down Perform a System Shutdown procedure when you mu st disconnect the UPS system components from all power sources when required for maintenance procedures. Use the Shutdown Proce dures screen when per forming a manual System Shut down.
Operation 83 . Figure 62 Load on maintenance byp ass, two breakers Figure 63 Load on maintenance byp ass, three breakers ! CAUTION Instructions for operating the Maintenance Bypass circuit brea kers are on the Maintenance Bypass cabinet. Make sure you understand the pr oper sequence before operating any circuit breaker.
Operation 84 3.4 Manual Procedures The Liebert Series 610 UPS system is desi gned to functi on while unattende d by an operator. The sys- tem control logic at the System Control Cabinet (SCC) monitors th e performance of the UPS system, the availabili ty of power sources and th e current required by the critical load.
Operation 85 Step 1. Before you apply power to the UPS modules, de termine the position of the follow ing circuit breakers and switches: a. Bypass Input Breaker (BIB) - If this circuit breaker is cl osed, you may already have power to the critical load through the by pass line.
Operation 86 Step 2. If the bypass line is not supp lied to the SCC, the LCD screen will be blank. Energize the bypass line by operating th e following controls: a. Close the Bypass Input Breaker (BIB). Th is breaker m ay be in your M aintenan ce Bypass cabinet.
Operation 87 e. If the UPS Bypass line is available, but not ye t supplying power to the load, clos e the circuit breakers (external to the UPS) required to provide power to the critical load equipment. Follow the three steps shown below. 1. Verify the Bypass Input Brea ker (BIB) and System Bypass circuit breakers are closed.
Operation 88 3.4.2 UPS Module St art-Up When a UPS module has been shut down for any re ason, use this procedure to start-up the UPS mod- ule to provide filtered , reliable po wer to the critical bus. This proc edure gives step-by- step instruc- tions for controls to operate and conditions to observ e.
Operation 89 Figure 65 Module st art-up procedures screen Select the Walk-In screen on the LCD. Step 3. To energize the UPS module, manually close the input circu it breaker (CB1, Figure 8 ). This will provide power to the rectifier. Use the Walk -In screen to monitor the Module DC Bus voltage.
Operation 90 The Battery block in the Monitor/Mimic Display indicates the batte ry voltage and charge current. Use the Monitor/Mimic Display s creen to determine the conditio n of the UPS module. Press the Alarm Reset pad to clear the Alar m Messages.
Operation 91 3.4.3 Load T ransfer Procedures Use the Monitor/Mimic Display at the SCC to dete rmine the operating cond ition of the UPS syst em. Press the Alarm Reset pad to clear the Alarm Message s. If al l UPS modules are on-line, the only message remaining should be Load On Bypass.
Operation 92 3.4.4 Maintenance Byp ass Load T ransfers To manually transfer the load be tween Maintenance Bypass and the UPS system bypass line, care- fully follow these instructions. Do not transf er the load between Maintenance Bypass an d the UPS system (module inverters) output.
Operation 93 3.4.5 Shut down Procedures System Shut down Procedure Perform a System Shutdown Procedure when you w ant to remove power from the UPS system and System Control Cabinet (SC C) when required for ma intenance or if you need to perform maintenance on a UPS module in a non-redundant system.
Operation 94 Module Shut down Procedure Perform a Module Shutdown Procedure when you wa nt to remove power from a UPS module when required for maintenance. Before performing any maintenance on your Liebert Series 610 UPS, observe ALL of the WARN- INGS in 4.
Operation 95 Local Emergency Modules Off (LEMO) The UPS controls at the SCC include an Emergency M odule Off pad ( Figure 10 , item 12). When this guarded pad is pressed, the load is auto matically tran sferred to the bypass line and the module output, battery and input circuit break ers trip open to isolate and shut down all the UPS modules.
Operation 96 3.5.1 Overloads (Without T ransfer) The UPS system is capable of sustai ning full output voltage (±2% of the nominal voltage ) for overload conditions that remain within ( under) the current versus time curv e of system overload capacity and the capacity of modules on-line ( Figure 69 ).
Operation 97 3.5.3 Automatic Retransfers to UPS Automatic Retransfer to UPS is an option that you ca n select from the SCC System Config uration screen. If you do not want the UP S system to initiate any automati c retransfers, set Max Auto-Rexfer Attempts to zero (0).
Maintenance 98 4.0 M AINTENANCE 4.1 Safety Precautions Observe the safety precautions in Important Safety Instructions on page 1 and in 1.3 - Safety Precautions .
Maintenance 99 4.2 Liebert Global Services Start-up, UPS maintenance, batte ry mainten ance and training programs are avai lable for the Series 610 UPS through your L iebert sales representative.
Maintenance 100 4.3 Routine Maintenance You are encouraged to become thoroughly familiar wi th the equipment, but at no time should you go beyond the specific procedures in this manual wh ile performing maintenanc e or correcting a malfunc- tion.
Maintenance 101 4.3.3 Limited Life Component s Your Liebert UPS has a design life well in excess of 10 years. Well-main taine d units can continue to provide e conomic benef its for 20 years or more. Lo ng-life components are used in your UPS wherever practical and cost-effectiv e.
Maintenance 102 4.4 Battery Maintenance 4.4.1 Battery Safety Precautions Servicing of batteries should be performed or supe rvised by personnel know ledgeable of batteries and the required precautions. Keep unauthorized person nel away from batteries.
Maintenance 103 Battery Safety Precautions In French Per CSA Require ment s Instructions Import antes Concernant La Sécurité Conserver Ces Instructions ! AVERTISSEMENT Respecter toutes les consignes de sécurité ap plicables à l'installation , le chargement ou l'entretien des batteries.
Maintenance 104 Regular maintenance of the battery module is an absolute necessity. Periodic inspections of battery and terminal voltages, specific gravity and connection resistance should be made. Strictl y follow the procedures outlined in the battery manufa cturer’s manual, available on t he manufacturer’s Web site.
Maintenance 105 If you have a different model battery, contact Liebert Global Services for th e required torqu e value. To access battery cell te rminals, disconnect the inter-tier cable and two shelf retaining screws. Once disconnected, insula te (with protecti ve boot or ele ctrical tape) the c ables to prevent accid ental shorts.
Maintenance 106 4.4.2 T orque Requirement s All electrical connectio ns must be tight. Table 15 provides the torque values for the connections in the UPS.
Maintenance 107 4.6 Reporting a Problem If a problem occurs within the UP S, review all alarm messages along with other pertinent data. This information should be given by telephone to the Li ebert se rvice representative’s office neares t you. This information can be down loaded to Lie bert Global Services by using the optional modem.
Specifications 108 5.0 S PECIFICATIONS 5.1 Rating The kVA and kW ra tings and the nominal volta ges and currents for conti nuous operation are listed on the unit nameplates (inside Operator Contro l Pane l door) and on the System One-Line Diag ram. The rated output power envelope of the UPS is il lustrated in Figure 70 .
Specifications 109 5.2 Environment al Conditions T able 17 S pecifications applicable to envir onment Enclosure The UPS is housed in a NEMA-1 en closure. The enclosure is design ed for indoor use only and is not to be subjected to falling objects or precipitation.
Specifications 110 5.3 Adjustment s All adjustments are set at the factory or during st ar t-up and normally do not have to be field read- justed. • Input Current Limit: Normal, 115%; on generator (.
Specifications 111 5.5 Electrical Sp ecifications RECTIFIER INPUT Input Voltage Standard voltages for 100 - 450kVA units: 208, 480 and 600VAC Standard voltages for 500 - 1000kVA units: 480 and 600VAC Other voltages available on request. 3-ph ase, 3-wire plus ground.
Specifications 112.
.
The Comp any Behind the Products With over a million installations around th e globe, Liebert is the world leader in computer protection systems. Since its founding in 1965, Liebert has developed a co.
An important point after buying a device Liebert 1000kVA (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Liebert 1000kVA yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Liebert 1000kVA - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Liebert 1000kVA you will learn all the available features of the product, as well as information on its operation. The information that you get Liebert 1000kVA will certainly help you make a decision on the purchase.
If you already are a holder of Liebert 1000kVA, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Liebert 1000kVA.
However, one of the most important roles played by the user manual is to help in solving problems with Liebert 1000kVA. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Liebert 1000kVA along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center