Go to page of 13
CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM APC Smart-UPS RT BID SPECIFICATIONS FOR 3000VA, 5000VA and 6000 VA Smart-UPS RT 230VAC Uninterruptible Power Supply PART 1 - GENERAL 1.
CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM H. Configuration Specifics: The UPS is available in one of the following configurations: MODEL SKU # TOWER APC Smart-UPS RT 3000VA RM 230V SURT3000XLI .
CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM A. Online: The input PFC power stage and the output power stage (inverter) shall operate in an on-line manner to continuously re gulate power to the critical load.
CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM 2.1 MECHANICAL DESIGN A. The UPS is contained in a rugged steel cabinet with two plastic front bezels; B. The UPS dimensions are 13 x 43 x 66cm (5.1 x 17 x 26 in.); C. The UPS cabinet is capable of conversion between Tower and Rack-Mount configurations; 2.
CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM 3. Output frequency: 50/60 +/- 3Hz tracking or 5 0/60 +/- 0.1Hz tracking (user selectable); 4. AC output voltage distortion: Max. 2% @ 100% linear load; Max. 5% @ 100% non-linear Load; 5. AC output static voltage regulation: +/-1%; 6.
CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM C. Input Current Limit: 1. The input converter shall control and limit the input current draw from utility to 150% of the UPS output.
CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM condition is removed from the critical bus output of the system. Automatic transfers of load to bypass also take place if for any reason the UPS cannot support the critical bus.
CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM 6. Self-diagnostics, self-test and proactive fault detection; 7. Communication to the host server via serial port; 8. Communication to the Network Interface Card or another SmartSlot accessory card if equipped.
CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM 6. The UPS is in fault state; 7. The battery needs to be replaced; 8. The battery capacity/utility voltage LED bar G. Audible Alarms: Using audio signal, the UPS will notify the user about important events.
CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM 3.2 SOFTWARE AND CONNECTIVITY A. Network Adaptor: APC SmartSlot Network Ma nagement Card shall allow one or more network management systems (NMS) to monitor and m anage the UPS in TCP/IP network environments.
CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM 7. TurboLinux v.7.0 and 8.0 8. Novell Netware 6.0 with Support Pack 1 9. Novell Netware 6.5 10. Novell Netware 5.1 with Support Pack 3 or above (using PowerChute Business Edition v6.2.2 agent) 11. Sun Solaris 8 and 9 PART 4 - Part 4 - EXECUTION 4.
CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM 1. Ensure proper system start-up. 2. Verify proper firmware control functions. 3. Verify proper firmware bypass operation. 4. Verify proper bypass switch operation (where applicab le). 5. Verify proper inverter operation and regulation circuits.
CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM identification and operation, system controls and adjustment, preventative maintenance, and troubleshooting.
An important point after buying a device APC 5000VA (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought APC 5000VA yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data APC 5000VA - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, APC 5000VA you will learn all the available features of the product, as well as information on its operation. The information that you get APC 5000VA will certainly help you make a decision on the purchase.
If you already are a holder of APC 5000VA, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime APC 5000VA.
However, one of the most important roles played by the user manual is to help in solving problems with APC 5000VA. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device APC 5000VA along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center