Battery Inst allation MGE™ Galaxy™ 3 00 10-40 kV A 380/400/415 V 10-40 kVA.
.
Content s MGE™ Galaxy ™ 300 10-40 kVA 3: 3 - 380/400 /415 V, 10-30 kVA 3:1 - 380/4 00/415 V Installatio n i Overview . ............. ......... ............. ...... ...... ......... ............. .... 1 IMPORTANT SAFETY INSTRUCTIONS - SAVE THESE INSTRUCTIONS .
MGE™ Ga laxy™ 300 1 0-40 kVA 3:3 - 380 /400/415 V , 10-30 kVA 3:1 - 3 80/400/415 V Insta llation ii Checklist.... ............. ...... ......... ............. ......... ............. ...... 15 Appendi x .......... ............ ...... ....... .....
1 MGE™ Galax y™ 300 10-4 0 kVA 3:3, 10-30 kVA 3:1 - 3 80/400 /415 V Inst allation Overview IMPORT ANT SAFETY INSTRUCTIONS - SA VE THESE INSTRUCTIONS W arning: ALL safety i nstructions in t he Safety S heet (990-3620 ) must be r ead, understo od and followed when ins t alli ng the UPS and XR Battery e nclsour e(s).
MGE™ Ga laxy™ 300 10-40 kVA 3:3, 10 -30 kVA 3:1 - 380/ 400/415 V Installation 2 Product Overview Battery shelves Battery circuit breaker Ground cable conn ect ion (from the UP S) B.
3 MGE™ Galax y™ 300 10-4 0 kVA 3:3, 10-30 kVA 3:1 - 3 80/400 /415 V Inst allation Cables and Batteries Note: The batter y enclosure mu st be inst alled on a non-i nflammable, level and solid floor . Prep are for Cab les 1. Open the fr ont door . 2.
MGE™ Ga laxy™ 300 10-40 kVA 3:3, 10 -30 kVA 3:1 - 380/ 400/415 V Installation 4 Battery enclos ure with p re-inst alled batteries W arning: Remove al l card board used to pr otect the batter ies during transport. Make sur e that cables and coppe r bars are se parated.
5 MGE™ Galax y™ 300 10-4 0 kVA 3:3, 10-30 kVA 3:1 - 3 80/400 /415 V Inst allation 2. Connect th e batteries to the batt ery breaker by running t he cables from the ba ttery br eaker to each shel ve. Note! Make sure to run th e cab les in this order .
MGE™ Ga laxy™ 300 10-40 kVA 3:3, 10 -30 kVA 3:1 - 380/ 400/415 V Installation 6 Note: A maximum of t wo batter y enclosures can be connect ed to the UPS (one XR Bat tery enclos ure with a circ uit breake r plus one en closure wi thout a circuit b r eaker ) by a batch cable betwe en the UPS an d the circuit br eaker in th e batter y enclosure.
7 MGE™ Galax y™ 300 10-4 0 kVA 3:3, 10-30 kVA 3:1 - 3 80/400 /415 V Inst allation Connect Co mmunicatio n Cables between the UPS and Ba ttery En closure External battery tempera ture (A TIZ) and externa l battery breaker signal Note: The A TIZ c able is f or external bat tery tempe rature detect ion si gnal (cab le is pre- instal led).
MGE™ Ga laxy™ 300 10-40 kVA 3:3, 10 -30 kVA 3:1 - 380/ 400/415 V Installation 8 Connect the Battery Cable s between th e UPS and Battery Enclosure W arning: This pr ocedure de scribes how to connect t he initi al battery ca bles between the UPS and XR befor e star t-up.
9 MGE™ Galax y™ 300 10-4 0 kVA 3:3, 10-30 kVA 3:1 - 3 80/400 /415 V Inst allation 5. Connect th e battery cable s to the batter y terminal s in the UPS. See the UPS inst allation manual for info rmation on how to remove the I/ O sheet metal c over .
MGE™ Ga laxy™ 300 10-40 kVA 3:3, 10 -30 kVA 3:1 - 380/ 400/415 V Installation 10 Connect an XR Battery Enclosure to a r unning UPS W arning: Befor e connecting an XR bat tery encl osure , ALL safety instructi ons in the Safety S heet (990-3620) must be r ead, understood and followed.
11 MGE™ Galaxy™ 3 00 10-40 k VA 3:3, 10-30 kVA 3 :1 - 380/400/415 V Installation Electrica l Hazard: Check the DC volta ges with a DC volt age multimeter versus the bat t ery voltage before continui ng. 7. T urn the XR batter y breaker (QFB) to the ON ( closed) posit i on.
MGE™ Ga laxy™ 300 10-40 kVA 3:3, 10 -30 kVA 3:1 - 380/ 400/415 V Installation 12 Replace t he Batteries W arning: Befo re battery replace ment, A LL sa fety ins truc tions in the S afety S heet ( 990- 3620) must be r ead, understood and followed. Fa ilur e to do so could r esult in equ ipment damage, ser i ous i njury , or death.
13 MGE™ Galaxy™ 3 00 10-40 k VA 3:3, 10-30 kVA 3 :1 - 380/400/415 V Installation S pecifications Battery Output Recommended Cable Sizes Caution: All wirin g must co mply with all appl icable nationa l and/or e lectrical co des.
MGE™ Ga laxy™ 300 10-40 kVA 3:3, 10 -30 kVA 3:1 - 380/ 400/415 V Installation 14 Recommended Bolt and Lug Size T orque sp ecifications Battery T erminal Bolt size T orque CSB 910-0631 c lip 910-0633 M6 5.4 NM (max 8.2 NM) YUASA 912-0001 M5 2.5 NM (max 6 NM) 910-0632 M6 4.
15 MGE™ Galaxy™ 3 00 10-40 k VA 3:3, 10-30 kVA 3 :1 - 380/400/415 V Installation Checklist Make sure th at all cardb oard and st rappings h ave been r emoved. Check that the power wiring is torqued as described in the torque specification table above.
MGE™ Ga laxy™ 300 10-40 kVA 3:3, 10 -30 kVA 3:1 - 380/ 400/415 V Installation 16 Appe ndix One-li ne diagrams Note: Use the bel ow table as a hel p to find t he diagram that f its your system. Note: - marked cables are a ssembled by the manufacturer .
17 MGE™ Galaxy™ 3 00 10-40 k VA 3:3, 10-30 kVA 3 :1 - 380/400/415 V Installation Battery cabling YUASA 15 kV A 60 min. No. Item Description Part no.
MGE™ Ga laxy™ 300 10-40 kVA 3:3, 10 -30 kVA 3:1 - 380/ 400/415 V Installation 18 Battery cabling YUASA 20/30 kV A 60 min. No. Item Description Part no.
19 MGE™ Galaxy™ 3 00 10-40 k VA 3:3, 10-30 kVA 3 :1 - 380/400/415 V Installation Battery cabling YUASA 40 kV A 60 min. No. Item Description Part no.
MGE™ Ga laxy™ 300 10-40 kVA 3:3, 10 -30 kVA 3:1 - 380/ 400/415 V Installation 20 Battery cabling CSB 15 kV A 60 min. No. Item Description Part no. Qty .
21 MGE™ Galaxy™ 3 00 10-40 k VA 3:3, 10-30 kVA 3 :1 - 380/400/415 V Installation Battery cabling CSB 30 kV A 60 min. No. Item Description Part no. Qty .
MGE™ Ga laxy™ 300 10-40 kVA 3:3, 10 -30 kVA 3:1 - 380/ 400/415 V Installation 22 Battery cabling CSB 40 kV A 60 min. No. Item Description Part no. Qty .
.
6/2010 990-3617-001 *990-3617-001* APC W orldwide Customer Support Customer s upport for this or any other AP C product is avai lable at no char ge in any of the foll owing ways: • V isit th e APC W eb site to acce ss docu ments in t he APC Knowledge Base a nd to subm it custo m er support requests.
An important point after buying a device APC 300 (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought APC 300 yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data APC 300 - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, APC 300 you will learn all the available features of the product, as well as information on its operation. The information that you get APC 300 will certainly help you make a decision on the purchase.
If you already are a holder of APC 300, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime APC 300.
However, one of the most important roles played by the user manual is to help in solving problems with APC 300. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device APC 300 along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center