Instruction/ maintenance manual of the product MT2000 K-Tec
Go to page of 35
MT2000-0200-1 Rev f (10-2007) DCN0160 Guided W ave Radar Level T ransmitter Installation and Operational Manual 18321 Swamp Road Prairieville, Louisiana 70 769 USA Tel: (1) 225-673- 6100 / Toll Free 8 00-735-5835 Fax: (1) 225-673- 2525 / Toll Free 888- 442-1367 Email: service@kt ekcorp.
2 MT2000-0 200-01 Rev f (10-2007 ) DCN0160 T ABLE OF CONTENTS 1. INTROD UCTION ............................................................................................................... . 4 2. OVER VIEW ...........................................
MT2000-0200-1 Rev f (10-2007) DCN0160 3 T ABLE OF CONTENTS (CONTINUED) 9. APPENDIC ES .............................................................................................................. .. 23 9.1 APPENDIX A: Sensor Trim ....................
4 MT2000-0 200-01 Rev f (10-2007 ) DCN0160 1.0 INTRODUCTION Thank you for using the K-TEK MT2000 Guided Wave Radar Tran smitter. The MT2000 has been desi gned for ease of use and to offer extensive configurati on capabilitie s. You are urged to review this manual in its entirety prior to use.
MT2000-0200-1 Rev f (10-2007) DCN0160 5 2. OVERVIEW 2.1 Storage Information If required, storage prior to installation should be indoor s at ambient temperature, not to exceed the followin g: Temperature range: -40 to 150 de grees F. Humidity: 0 to 100% R.
6 MT2000-0 200-01 Rev f (10-2007 ) DCN0160 2.3.1 Direct Reflect Mode (standard) (cont’d) The measurement principle usin g TDR is based on the fact that a dielectric constant discontinuity or g eometric change will yield a negative pulse having certain amplitude belo w the baseline.
MT2000-0200-1 Rev f (10-2007) DCN0160 7 3. INST ALLA TION 3.1 Mounting Requirements IMPORTANT: To obtain the be st re turn s ignal from the product level it is recommended to mount the MT2000 cou- pler directly into the top of the vessel if the vessel material is metal, or into a metal plate if the vessel is non-metallic.
8 MT2000-0 200-01 Rev f (10-2007 ) DCN0160 3.2 Shortening of Probe The MT2000 single probe can be cut to length prior to in stallation. The MT2000 default factory configuration pro- vides a measurement in engineering units with a zero refe re nced to the bottom of the s ensing probe.
MT2000-0200-1 Rev f (10-2007) DCN0160 9 Rods: • 1/4”rod 5 ft. max, minimum 3” Dia. Stilling well if provided with stilling well. • 1/2” rod 10 ft. max, minimum 3” Dia. St illing well if provided with stilling well. • In 2” pipe: 5ft. Max 1/4” or 1/2” rod.
10 MT2000-0 200-01 Rev f (10-2007 ) DCN0160 Figure 4.1 4.2 Verify Proper Power-Up Apply power to the transmitter and ve rify that the display comes up and is acti ve. The display update rate is approxi- mately 4 seconds. The curre nt draw should un der no case ex ceed 21 mA and, in the event of a pro blem, refer to trouble-shooting section.
MT2000-0200-1 Rev f (10-2007) DCN0160 11 4.3.1 LCD Menu Operation The LCD display is menu driven, uses the UP , DO WN, and SELECT push buttons for navigation. • Press UP or DOWN to scroll through menu optio ns. • Press SELECT to select a menu option.
12 MT2000-0 200-01 Rev f (10-2007 ) DCN0160 4.4 Detailed Configuration Parameters 4.4.1 Direct Mode Blanking Menu Note: This section only applies to direct mode mea su reme nt.
MT2000-0200-1 Rev f (10-2007) DCN0160 13 The following values should be used as starting p oint s: For Mounting Configuration 1,2,3a and 3b, (d irect in sertion in tan k - no stilling well applications, no coaxial probes) with the following dielectri c constant: GS THV ≥ 10 2* 1.
14 MT2000-0 200-01 Rev f (10-2007 ) DCN0160 4.4.3 Advanced Parameter Settings (cont’d) • KO & KG KO and KG parameters should only be change d during the replacement of an electroni c module.
MT2000-0200-1 Rev f (10-2007) DCN0160 15 4.4.4 Ultra Low Dielectric (ULD) Mode Configuration Note: Use this method for very low dielectric solids o nly , when little or no usable signal ca n be obtained from the product surface. Use in solids measurement appli cations with 1.
16 MT2000-0 200-01 Rev f (10-2007 ) DCN0160 4.4.4 Ultra Low Dielectric (ULD) Mode Configuration (cont’d) If it is not practical to establish a known level in the vessel before commi ssioning the MT2.
MT2000-0200-1 Rev f (10-2007) DCN0160 17 4.5.5 Bench Calibration of the 4mA & 20mA Points: After the transmitter is configured correctly, a manual ben ch calibration of the 4mA and 20mA points using han ds or targets, can be done as follows. Note: The following applies to single or dual Ro d and Cable probes only.
18 MT2000-0 200-01 Rev f (10-2007 ) DCN0160 4.5.7 Reversing The Output Action Using Actual Level Input • Adjust the level to 50% ( + or - 10% ). • Enter the calibration mode by pressing the UP & DOWN buttons together for 1 se cond and press the DOWN button for 1 second to set the output at 4.
MT2000-0200-1 Rev f (10-2007) DCN0160 19 5. TROUBLESHOOTING INFORMA TION Use a milliamp (mA) meter to measure the output current. When power is applied the output will go to 4.00 mA for at least one (1) second and then to either the me asured level or an alarm condi tion output.
20 MT2000-0 200-01 Rev f (10-2007 ) DCN0160 5.2 Possible Symptoms (cont’d) SYMPTOM ACTION Raw Counts are 0 and Out put is in alarm Raise the Threshold Check probe for pre sence Decrease .
MT2000-0200-1 Rev f (10-2007) DCN0160 21 6.2 Operating Modes The MT2000 transmitter with DE option can be operated in two wa ys, selectable usin g the setup menu of the instru- ment: 1.
22 MT2000-0 200-01 Rev f (10-2007 ) DCN0160 8. GLOSSAR Y OF TERMS EU Engineering Units Display units selection (inc hes, mm, feet, %, etc.) URV Upper Range Value Location on the transmitter sensor to .
MT2000-0200-1 Rev f (10-2007) DCN0160 23 9. APPENDICES 9.1 APPENDIX A: Sensor Trim Sensor trim is preset at the factory for a specific type of probe, installation and applic ation condition. Re-trimming in the field should not be necessary unless a major c han ge in anten na length (+/- 40%) is requi red.
24 MT2000-0 200-01 Rev f (10-2007 ) DCN0160 END (CFG MENU) RNG - Range LTP - Low Trim Point HTP - High Trim Point LTC - Low Trim counts HTC - High Trim counts TMP - Module Temperature SOR - Signal Out.
MT2000-0200-1 Rev f (10-2007) DCN0160 25 9.2 APPENDIX B: Additional Special Functions in the CFG2 (Hidden) Menu (continued) These functions are accessed by pressi ng the ‘UP’ and ‘DOW N’ buttons togeth er, when the LCD display is on ‘END’ at the end of the CFG menu.
26 MT2000-0 200-01 Rev f (10-2007 ) DCN0160 9.3 APPENDIX C: Linearization The MT2000’s multi-point lineari zation system allows im proved measurement accu racy along the length of the probe.
MT2000-0200-1 Rev f (10-2007) DCN0160 27 9.4 APPENDIX D: Interface Applications It is possible to use an MT2000 to determine t he le vel of an interface but certain req uire- ments must be met: 1. The dielectric constant of the upper liqui d must be low (between 2 and 3).
28 MT2000-0 200-01 Rev f (10-2007 ) DCN0160 9.5 APPENDIX E: Oscilloscope Use & Setup for Troubleshooting 9.5.1 General Setup • Connect Channel A to Pin 6 • Connect GND to Pin 3 • Connect Tri.
MT2000-0200-1 Rev f (10-2007) DCN0160 29 9.6 APPENDIX F: CE Certificate of Conformity.
30 MT2000-0 200-01 Rev f (10-2007 ) DCN0160 9.7 APPENDIX G: Exida Certificate.
MT2000-0200-1 Rev f (10-2007) DCN0160 31 9.8 APPENDIX H: Installation Drawings for Intrinsic Safety & Standard Wiring.
32 MT2000-0 200-01 Rev f (10-2007 ) DCN0160 9.8 APPENDIX H: Installation Drawings for Intrinsic Safety & Standard Wiring (continued).
MT2000-0200-1 Rev f (10-2007) DCN0160 33 9.8 APPENDIX H: Installation Drawings for Intrinsic Safety & Standard Wiring (continued).
34 MT2000-0 200-01 Rev f (10-2007 ) DCN0160 9.9 APPENDIX I: Mounting Configurations External Chamber MINI MU M DIELECTRIC CONSTANT MAX IMU M PROBE LENGTH 1.7 20 ft./6.1 m 3 30 ft./9.1 m 10 50 ft./15.2 m 35 50 ft./15.2 m Coaxial Probe MINI MU M DIELECTRIC CONSTANT MAX IMU M PROBE LENGTH 1.
MT2000-0200-1 Rev f (10-2007) DCN0160 35 9.10 APPENDIX J: Warranty Statement 5 YEAR WARRANTY FOR: KM26 Magnetic Liquid Level Gaug es; MagWave Dual Cha mbe r System; LS Series M echanical Level Switches (LS500, LS550, LS600, LS700, LS800 & LS900); EC Exter nal Chambers, STW Stilling Wells and ST95 Seal Pots.
An important point after buying a device K-Tec MT2000 (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought K-Tec MT2000 yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data K-Tec MT2000 - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, K-Tec MT2000 you will learn all the available features of the product, as well as information on its operation. The information that you get K-Tec MT2000 will certainly help you make a decision on the purchase.
If you already are a holder of K-Tec MT2000, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime K-Tec MT2000.
However, one of the most important roles played by the user manual is to help in solving problems with K-Tec MT2000. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device K-Tec MT2000 along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center