347337-UIM-A-0408 R-22 OUTDOOR SPLIT -SYSTEM AIR CONDITIONING MODELS: 13 SEER A Y018-030 SERIES 1.5 TO 2.5 T ONS INSTALLATION MANUAL LISTED ISO 9001 Certified Quality Management System SECTION I: GENERAL The outdoor units are designed to be connected to a matching indoor coil with sweat connect lines.
347337-UIM-A-0408 2 Johnson Controls Unitary Products SECTION III: UNIT INST ALLA TION LOC A T IO N Before starting the installation, select and check the suitability of the location for both the indoor and outdoor unit. Observe all limitations and clearance requirements.
347337-UIM-A-0408 Johnson Controls Unitary Produ cts 3 PIPING CONNECTIONS The outdoor condensing unit must be connected to the indoor evapora - tor coil using field supplied r efrigerant grade (ACR) co pper tubing that is internally clean and dry .
347337-UIM-A-0408 4 Johnson Controls Unitary Products Connect the refrigerant lines u sing the following proced ure: 1. Remove the cap and Schrader core from both the liquid and vapor service valve service ports at the outdoor unit. Connect low pres- sure nitrogen to the liquid line service port.
347337-UIM-A-0408 Johnson Controls Unitary Produ cts 5 SECTION V : INST ALLA TIONS REQUIRING AN ADD-ON TXV KIT For installations requiring a TXV kit, refer to the Installation Instruct ions accompanying the TXV kit. SECTION VI: EV ACU A TI ON It will be necessary to evacuate the system to 500 microns or less.
347337-UIM-A-0408 6 Johnson Controls Unitary Products SECTION VIII: ELECTRICAL CONNECTIONS GENERAL INFORMA TION & GROUNDING Check the electrical supply to be sure that it meets the values specified on the unit nameplate and wiring label.
347337-UIM-A-0408 Johnson Controls Unitary Produ cts 7 For additional connection diagrams for a ll UP G equipment refer to “Low V oltage System Wiring” document available online at www .
347337-UIM-A-0408 8 Johnson Controls Unitary Products FIGURE 10: Thermostat Chart - Single S tage AC with PSC Air Handler AC 1B Single Stage Air Conditioner – PSC Air Handler C 24 – Volt Comm on Y.
347337-UIM-A-0408 Johnson Controls Unitary Produ cts 9 FIGURE 1 1: Thermostat Chart - Single St age AC with PSC Fur nace AC 5D Single Stage Air Conditioner – Single Stage PSC Furnace HM1 Humidistat .
347337-UIM-A-0408 10 Johnson Controls Unitary Products FIGURE 12: Thermostat Chart - Single S tage AC with PSC Furnace AC 5E Single Stage Air Conditioner – Single Stage PSC Furnace C 24 – Volt Com.
347337-UIM-A-0408 Johnson Controls Unitary Produ cts 11 INDICA TIONS OF PROPER OPERA TION Cooling 1. The outdoor fan should be running, with warm air being dis- charged from the top of the unit. 2. The indoor blower (furnace or air handler) will be operating, dis- charging cool air from the ducts.
Subject to change without notice. Printed in U.S.A. 347337-UIM-A-0408 Copyright © 2008 by Johnson Controls, Inc. All rights reserved. Supersedes: 259715-UIM-A-0606 Johnson Contro ls Unitary Produc t .
An important point after buying a device Johnson Controls 13 SEER (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Johnson Controls 13 SEER yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Johnson Controls 13 SEER - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Johnson Controls 13 SEER you will learn all the available features of the product, as well as information on its operation. The information that you get Johnson Controls 13 SEER will certainly help you make a decision on the purchase.
If you already are a holder of Johnson Controls 13 SEER, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Johnson Controls 13 SEER.
However, one of the most important roles played by the user manual is to help in solving problems with Johnson Controls 13 SEER. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Johnson Controls 13 SEER along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center