Instruction/ maintenance manual of the product DFS2A318J2A ICP DAS USA
Go to page of 15
1 CONTENTS Page 5130261891 9 - A 0606 SAFETY CONSIDERA TIONS ................................ 1 GENERAL ........................................................... 1-4 INST ALLA TION ................................................ 4-1 1 Indoor Unit Installation .
2 T able 1 — Parts List — High W all Units ITEM QTY DIAGRAM Mounting Bracket 2 X 1 DFF2A/DFF2H 09, 12 Long Screws 2 X 8 Outdoor Sensor Connecting Cable 2 X 1 (Available for HEA T PUMP ONL Y) Absor.
3 T able 2 - Physical Data - Cooling Only INDOOR UNIT 2 X DFF2AH09J1A 2 X DFF2AH12J1A COOLING CAP ACITY (Btuh) 2 X 9,000 2 X 1 1,400 SEER 13.0 13.0 SYSTEM CHARGE (Ib)* 2 X 2.4 2 X 3.1 MOISTURE REMOV AL (pt/hr) 2 X 2.6 2 X 4.5 AIRFLOW (3 Speeds) High / Med.
4 2.5-IN. Fig. 2 — Indoor Unit Clearances INST ALLA TION Plan the installation carefully to avoid component failures and make installation easier . Indoor Unit Installation REFRIGERANT LINE ROUTING — The refrigerant lines may be routed in any of the four directions shown in Fig.
5 CAUTION REASSEMBLE 1. Connect the display connector to the display panel printed circuit board. 2. Put the control box cover and grille frame back on using the appropriate screws (Steps 3 and 4 of W ire the Indoor Unit section). Put the grille insert back on.
6 A TT ACH THE REMOTE CONTROLLER MOUNTING BRACKET 1. Use the two screws supplied with the controller to attach the mounting bracket to the wall in the location selected by the customer (see Fig. 10 ). 2. Install batteries in the remote control. 3. Place remote control into remote control mounting bracket.
7 FLARING AND CONNECTING REFRIGERANT LINES 1. Remove the protective cap from the flare fitting. 2. Remove the protective cap from the tubing and cut to the required length. Be sure that the cut is perpendicular and clean, without burrs. 3. Slip the flare nut on the tubing and flare the tube end using standard flaring tools.
8 318J2A 1 15 V AC 19.8 25 18.0 1.00 7.2 42 324J2A 1 15 V AC 2 4.6 3 0 2 2.2 1.00 9.3 58 3095897 3095897 09J1A 30VDC N/A N/A 1.8 1.1 N/A N/A 12J1A 30VDC N/A N/A 1.
9 51302523981-A Models 2 X 09 / 2 X 12 Wiring Diagram Heat pump TB 1 G R / Y E L B L K W H T HL TV BLK * BLUE * BR *GR/YEL FAN J1 K4 K3 K2 K1 DC RTN FAN FUSE 6A W H T RVS BLK RVS B R N FC COMP 1 TB * .
10 51302523982-A Models 2 X 09 / 2 X 12 Wiring Diagram Cooling Only TB 1 G R / Y E L B L K W H T HL TV BLK * BLUE * BR *GR/YEL FAN J1 K4 K3 K2 K1 DC RTN FAN FUSE 6A W H T RVS BLK RVS B R N FC COMP 1 T.
11 ST ART -UP System Checks 1. Conceal the tubing where possible. 2. Make sure that the drainage tube slopes downward along its entire length. 3. Ensure all tubing and connections are properly insulated. 4. Fasten tubes to the outside wall. 5. Seal the hole through which the cables and tubing pass.
12 TROUBLESHOOTING (T ables 6-8, and Fig. 19) T able 6 — Service Indicators LAMP ST A TUS INDICA TION CORRECTION ACTION Check the TH1 thermistor for correct resistance. 1 Flash Faulty TH1 Sensor Check for proper connection. Replace thermistor if necessary .
13 ,, p NO TE: Resistance tolerance ± 3%. TEMPEA TURE ( 0 F) TEMPERA TURE ( 0 C) TEMPERA TURE T OLERANCE ( 0 F) TEMPERA TURE T O LERANCE ( 0 C) MIN IMUM RESI ST AN CE (K ) MEAN RESIST ANCE (K ) MAXIMUM RESIST ANCE (K ) 4.0 20 ±2.0 ±1.1 30.89 32.
14 NO TE: Resistance tolerance ± 3%. TEMPEA TURE ( 0 F) TEMPERA TURE ( 0 C) TEMPERA TURE T OLERANCE ( 0 F) TEMPERA TURE T O LERANCE ( 0 C) MIN IMUM RESI ST AN CE (K ) MEAN RESIST ANCE (K ) MAXIMUM RESIST ANCE (K ) 100.4 38 ±2.0 ±1.1 3.058 3.167 3.277 102.
15 T able 8 — General System T roubleshooting Guide SYM PTOM PROBABLE CAUSE CORRECTIVE ACTION Power supply from outdoor unit to indoor Check for proper connection of power at disconnect. unit is not connected. Power supply to unit not connected Unit Fails to Start.
An important point after buying a device ICP DAS USA DFS2A318J2A (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought ICP DAS USA DFS2A318J2A yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data ICP DAS USA DFS2A318J2A - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, ICP DAS USA DFS2A318J2A you will learn all the available features of the product, as well as information on its operation. The information that you get ICP DAS USA DFS2A318J2A will certainly help you make a decision on the purchase.
If you already are a holder of ICP DAS USA DFS2A318J2A, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime ICP DAS USA DFS2A318J2A.
However, one of the most important roles played by the user manual is to help in solving problems with ICP DAS USA DFS2A318J2A. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device ICP DAS USA DFS2A318J2A along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center