INST ALLA TION INSTRUCTIONS 62-0278-07 TB6575/TB8575 SuitePR O™ Digital F an Coil Thermostats PR ODUCT DESCRIPTION The SuitePRO™ is a f amily of Digital F an Coil ther mostats for residential and commercial applications such as hotels, condominiums, school classrooms, etc.
TB6575/TB8575 SUITEPRO™ DIGI TAL F AN COIL THER MOSTATS 62-0278—0 7 2 SPECIFICATIONS Supply V oltages: TB6575A1000 and TB657 5B1000: • 120 V ac ±10% at 50/60Hz • 240 V ac -15% to +10% at 50/6.
TB6575/TB8575 SUITEPRO™ DIGITAL F AN COIL THER MOSTATS 3 62-0278—07 Fig. 1. Dimensi ons in inches (mm). INSTALLATION When Installing this Pr oduct… 1. Read these instructions carefully . F ailure to follo w them could damage the product or cause a ha zard- ous condition.
TB6575/TB8575 SUITEPRO™ DIGI TAL F AN COIL THER MOSTATS 62-0278—0 7 4 (1) Attach the supply wires directly to the ter mi- nals on the sub-base. See T able 3 on page 5 f or ter minal identification. (2) Push the supply wires back into the junction bo x.
TB6575/TB8575 SUITEPRO™ DIGITAL F AN COIL THER MOSTATS 5 62-0278—07 • Ps: Pipe sensor (optiona l) • R: 24 V ac power • Rs: Remote sensor (optional) • SB: Remote setback (optional) • Sc: .
TB6575/TB8575 SUITEPRO™ DIGI TAL F AN COIL THER MOSTATS 62-0278—0 7 6 Accessory Wiring Remote Pipe Sensor Wiring The remote pipe sensor is used for 2 pipes auto an d 2 pipes heat and cool with auxiliar y heat chan geov er . The pipe sensor will sense the temperature in the pipes to tell the thermostat when the system is set fo r Heat or Cool.
TB6575/TB8575 SUITEPRO™ DIGITAL F AN COIL THER MOSTATS 7 62-0278—07 Thermostat Wiring Diagrams The figures in this section illustrate typical wirin g f or : • TB6575A1000, TB6575B1000 an d TB6575C1000 fan coil ther mostats, which ar e 120/240/27 7 V ac pow ered.
TB6575/TB8575 SUITEPRO™ DIGI TAL F AN COIL THER MOSTATS 62-0278—0 7 8 . Fig. 13. Wiring diagram when missing a wire fo r electromechanical retr ofit (120/240/277 V ac shown). 24 V ac Wiring Dia grams (TB8575) F or the TB8575A1000 mode l, a 24 V ac Class 2 NEMA rated transf or mer must be used.
TB6575/TB8575 SUITEPRO™ DIGITAL F AN COIL THER MOSTATS 9 62-0278—07 Fig. 17. T w o pipes (Heat or Cool) auto c hangeover wiring diagram (24 V ac shown). Fig. 18. Four pipes (Heat and Cool) Manual/Auto Changeo ver wiring diagr am (24 V ac sho wn). Fig.
TB6575/TB8575 SUITEPRO™ DIGI TAL F AN COIL THER MOSTATS 62-0278—0 7 10 Fig. 21. Removing the thermostat. SETUP The ther mostat provides an LCD displa y , two b uttons below the displa y for System and F an control and two adjustment buttons (Up and Down) to the right of the display .
TB6575/TB8575 SUITEPRO™ DIGITAL F AN COIL THER MOSTATS 11 62-0278—07 Fig. 24. Instal ler Setup (IS) mode screen. M27585 Setup T able 4. Installer Setup (IS) Codes and Options.
TB6575/TB8575 SUITEPRO™ DIGI TAL F AN COIL THER MOSTATS 62-0278—0 7 12 6 Pipe Sensor Threshold for Cooling 50 to 72 Range is 50°F to 72°F . Default is 60°F . Changes to Cool when pipe temper ature is below threshold. 7 Pipe Sensor Threshold for Heating 75 to 90 Range is 75°F to 90°F .
TB6575/TB8575 SUITEPRO™ DIGITAL F AN COIL THER MOSTATS 13 62-0278—07 Installer T est (IT) Mode T o enter Installer T est Mode: • Press and hold both th e Up arr ow button and the Down Arr ow bu tton for three (3) seconds. This displays all segments of the LCD screen on the LCD .
TB6575/TB8575 SUITEPRO™ DIGI TAL F AN COIL THER MOSTATS 62-0278—0 7 14 T able 5 provides the T est codes (IT codes) and values. T o enter the IT codes: 1. Press the System (Heat/Cool) button to cycle through the IT codes, which displa y in the upper right ab ov e the word Te s t .
TB6575/TB8575 SUITEPRO™ DIGITAL F AN COIL THER MOSTATS 15 62-0278—07 BUTT ON PRESS SETBA CK (IS CODE #19-5) The default remote setbac k option is for economy setbac k via a button press on the thermostat. In this mode, the ther mostat can quickly be setback by pressing and holding down the System Mode button f or more than 3 seconds.
TB6575/TB8575 SUITEPRO™ DIGI TAL F AN COIL THER MOSTATS 62-0278—0 7 16 2 Pipes with A uto Changeover F or this application the system s witch only provides "Off" and "Auto". When in "Auto" mode the w ater temperature will indicate if th e thermostat should operate in hea ting or cooling.
TB6575/TB8575 SUITEPRO™ DIGITAL F AN COIL THER MOSTATS 17 62-0278—07 Fig. 29. 4 Pi pe Auto Changeover with Single Setpoi nt and Switching Points Heat/Cool Setpoint Metho d In 4 pipe auto changeover with heat and cool setpoints, the system ke y is used to switch betw een the heating setpoint and cooling setpoin ts.
TB6575/TB8575 SUITEPRO™ DIGI TAL F AN COIL THER MOSTATS 62-0278—0 7 18 Both the heating and cooling equipment are running at the same time. Incorrect Syst em T ype selected. Check that the Installer Setup code #2 (System T ype ) v alue matches the installed heati ng an d/or cooling equipment.
TB6575/TB8575 SUITEPRO™ DIGITAL F AN COIL THER MOSTATS 19 62-0278—07 LIMITED T WO-Y EAR W ARRANTY Honeywell warrants this pro duct, excluding battery , to be free f rom defects in the workmanship or materi als, under normal use and service, f or a period of two (2) years from the date of purcha se by the consumer .
TB6575/TB8575 SUITEPRO™ DIGI TAL F AN COIL THER MOSTATS Automation and Control Solu tions Honeywell International Inc. 1985 Douglas Drive North Golden Valley, MN 55422 customer.honeywell.com ® U .S. Regi stered T r ademark © 2011 Hone ywell International Inc.
An important point after buying a device Honeywell TB8575 (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Honeywell TB8575 yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Honeywell TB8575 - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Honeywell TB8575 you will learn all the available features of the product, as well as information on its operation. The information that you get Honeywell TB8575 will certainly help you make a decision on the purchase.
If you already are a holder of Honeywell TB8575, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Honeywell TB8575.
However, one of the most important roles played by the user manual is to help in solving problems with Honeywell TB8575. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Honeywell TB8575 along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center