Instruction/ maintenance manual of the product RM7800L Honeywell
Go to page of 16
INSTALLATION INSTRUCTIONS 66- 1085- 3 ® U.S. Registered T rademark Copyright © 2002 Honeywell • All Rights Reserved RM7800E,G,L,M; RM7840E,G,L,M 7800 SERIES Relay Modules APPLICATION The Hon eywel.
RM7800E,G ,L,M; RM7840E,G ,L,M 7800 SERIES RELAY MO DULES 66-1085—3 2 WARNING Fire or Ex plosion Haza rd. Can cause property dama ge, sev ere injury , or deat h. T o prevent possibl e hazardous burner operation, verify safety requirements each time a co ntrol is inst alled on a bur ner .
RM7800E,G ,L,M; RM78 40E,G,L,M 780 0 SERIES R ELAY MODULES 3 66-1085—3 4. All wir ing mu st co mply with all appli cable electric al codes, ordina nces and regula tions . Wiring , where required, must com ply wit h NEC, Class 1 (Line V oltage) wiring.
RM7800E,G ,L,M; RM7840E,G ,L,M 7800 SERIES RELAY MO DULES 66-1085—3 4 Fig. 1. Inte rnal block diagram of the RM780 0L/RM7840L (See Fig. 2, 3, 4 or 5 for individ ual deta iled wiri ng instructions ).
RM7800E,G ,L,M; RM78 40E,G,L,M 780 0 SERIES R ELAY MODULES 5 66-1085—3 T able 2. Recommended Groundi ng Practice s. T able 3. T ermina l Ratings. . a The re lay modu le mu st have a n earth ground providin g a co nnection betwe en the subbase and th e cont rol pan el or the equipm ent.
RM7800E,G ,L,M; RM7840E,G ,L,M 7800 SERIES RELAY MO DULES 66-1085—3 6 T able 4. Combinat ions for T er minals 8, 9 , 10 and 21. T able 5. Explana tion of Eac h Combination .
RM7800E,G ,L,M; RM78 40E,G,L,M 780 0 SERIES R ELAY MODULES 7 66-1085—3 Fig. 2. Wiring subbase and sequence for RM7800 E,L/RM7840E,L . M12261C G L2 3 4 4 5 5 6 7 8 9 10 F (L1) 13 14 15 16 17 18 19 20 21 22 12 LOCKOUT INTERLOCKS (INC.
RM7800E,G ,L,M; RM7840E,G ,L,M 7800 SERIES RELAY MO DULES 66-1085—3 8 Fig. 3. W iring subbase and sequen ce for RM7800 G/RM7840 G. RM7800G/RM7840G POWER OPERATING CONTROLS AND INTERLOCKS BURNER FLAME SIGNAL FIRING RATE MOTOR INITIATE (INITIAL POWERUP ONLY) POWER STANDBY PREPURGE HOLD DRIVE TO LOW FIRE POWER PILOT FLAME MAIN POWER PFEP 10 SEC.
RM7800E,G ,L,M; RM78 40E,G,L,M 780 0 SERIES R ELAY MODULES 9 66-1085—3 Fig. 4. Wiring subbase and sequen ce for RM780 0M/RM7840 M. M12262A G L2 3 4 5 6 7 8 9 10 F (L1) 13 14 15 16 17 18 19 20 21 22 .
RM7800E,G ,L,M; RM7840E,G ,L,M 7800 SERIES RELAY MO DULES 66-1085—3 10 Fig. 5. RM7800 /RM7840 R elay Module exploded vie w . SAFETY SHUTDOWN Safety Shutdown (Lockout) o ccurs if any of the following oc cur du ring the indicated period: 1. INITIA TE Period: a.
RM7800E,G ,L,M; RM78 40E,G,L,M 780 0 SERIES R ELAY MODULES 1 1 66-1085— 3 g. Lockout In terloc k opens d uring PREPURGE (RM7840E,L). h. Ignition /pilot valve/i ntermi ttent pi lot valv e term inal is energiz ed. i. Main v alve term inal i s energiz ed.
RM7800E,G ,L,M; RM7840E,G ,L,M 7800 SERIES RELAY MO DULES 66-1085—3 12 Ignition Trials 1. Pilo t F lame Es tabli shi ng Peri od ( PFEP ): a. With the firing rate mo tor at the l ow fire p ositio n: (1) The pilot valv e and igniti on transfo rmer , termina ls 8, 1 0 and 2 1, are ene rgized .
RM7800E,G ,L,M; RM78 40E,G,L,M 780 0 SERIES R ELAY MODULES 13 66-1085—3 Keyboard Disp lay Module (VFD) The Keyboard Display Module (see Fig. 5) is provided with the RM7800 R elay Module (but is not requir ed f or operatio n) and is an op tion fo r the RM7840 Rel ay Modu le.
RM7800E,G ,L,M; RM7840E,G ,L,M 7800 SERIES RELAY MO DULES 66-1085—3 14 T able 7. Sit e Configurable J umper Optio ns. a Pilot V alv e /First Sta ge Oi l V alve (V alve/S tart) T erminal 21. b A 30 sec ond MFEP c an be a ccompl ished by addin g a ju mper wire be tween T erminals 19 and 5.
RM7800E,G ,L,M; RM78 40E,G,L,M 780 0 SERIES R ELAY MODULES 15 66-1085—3 T able 8. Static C heckout. Te s t No. RM780 0/ RM7840 Models Te s t Jumper s V oltmete r Normal Opera tion If Operation is Abnormal, Check the Items Listed Be low 1 All None 4-L2 Line volta ge at T erminal 4.
66-1085—3 G.R. Rev . 02-02 www .honeywell.com RM7800E,G ,L,M; RM7840E,G ,L,M 7800 SERIES RELAY MO DULES Autom ati on and Contr ol Solut ions Honeywell Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, M N 55422 Scarborough, Ont ario M1V 4Z9 Printed in U.
An important point after buying a device Honeywell RM7800L (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Honeywell RM7800L yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Honeywell RM7800L - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Honeywell RM7800L you will learn all the available features of the product, as well as information on its operation. The information that you get Honeywell RM7800L will certainly help you make a decision on the purchase.
If you already are a holder of Honeywell RM7800L, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Honeywell RM7800L.
However, one of the most important roles played by the user manual is to help in solving problems with Honeywell RM7800L. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Honeywell RM7800L along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center