B2 P/N 52646:B2 ECN 10-098 Document 52646 2/12/2010 Rev: Addressable Fire Alarm Control P anel MS-9600LS/MS-9600LSE MS-9600UDLS/MS-9600UDLSE MS-9600LSC Manual.
2 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Fire Alarm System Limit ations While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance! An automatic fire a.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 3 Inst allation Precautions Adherence to the followin g will aid in problem- free installation with long-term reliability: W ARNING - Several different sources of power can be connected to the fire alarm control p anel.
4 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Sof tware Downloads In order to supply the latest features and functionality in fire alarm and life safety techno logy to our cust omers, we make frequent upgrades to the embedded software in our products.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 5 T able of Content s Section 1: Product Description ..................................................... ........................................ 13 1.1: Inventory ........................ .........
Table of Contents 6 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Section 3: Programming ...................................................................... .................................. 6 1 3.1: Programming Data Entry ......... ........
Table of Contents MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 7 Section 4: Operating Instructions ....................................................................................... 150 4.1: Panel Control Buttons ..................... .....
Table of Contents 8 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 5.4.2: Selecting and Locating Batteries ....... ................ ................. ................. ................. .............. .............177 Appendix A: Software Zones .
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 9 It is imperative that the installer understand the req uirements of the Authority Having Ju risdiction (AHJ) and be familiar with the standards set.
10 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 + B A T T E R Y - LCD DISPLA Y K E Y P A D I / F O P T D A C T J 3 J 2 T B2 T B 3 J P 3 J P 2 S W 1 JP5 JP6 J 1 7 J16 J 6 J8 J 7 J 1 0 J1 1 R E M.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 11 Peripheral Devices an d Their Documents: Addressable Devices and SLC Wiring Doc. # 51309 CHG-120F Charger Doc. # 50888 SLC Loop Battery Connector TB2 9600LSperi .wmf CHG-75 Charger Doc. # 51315 DACT-UD2 Communicator Doc.
12 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Notes.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 13 Section 1: Product Description The MS-9600LS and MS-9600UDLS are compact, cost effective, intelligent addressable F ACPs (Fire Alarm Control Panels) w ith an extensive li st of powerful features .
14 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Product Description Features and Options • Optional module for addi ng a second SLC loop which meets NFP A Style 4, 6 and 7 requirements • 31.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 15 Specifications Product Description • Auto-program (learn mo de) reduces installation time. Reports two devi ces set to the same address • Pass.
16 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Product Description Specifications Maximum signaling current per circuit : 3.00 amps (see Figure 1.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 17 Controls and Indicators Product Description 1.3.1 Current A vailability The following figure illu strates the maximum current that is possible for each panel circuit and the total current available fr om the F ACP power supply .
18 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Product Description Circuits • Maintenance/presignal (yellow) • Alarm Silenced signals (yellow) • Disabled (yellow) • Battery fault (yell.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 19 Components Product Description NAC (Notification Appliance Circuits) Up to four NACs are provided w ith various programmable features: • four Style Y (Class B) NACs OR • two Style Z (Class A) NACs Relays One fixed and two fully pro grammable Form-C dry co ntact relays are provided.
20 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Product Description Components the BB-26 can be used fo r housing the batteries. The CHG-120 F can be used for charging 26 to 120 AH batteries and the BB-55F can be used for hou sing the batteries.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 21 Optional Modules Product Description N-ELR Mounting Plate The N-ELR is a single End-of-Lin e resistor plate which is requir ed for use in Canada. An ELR, which is supplied with each module and fire alarm control pane l, is mounted to the ELR plate.
22 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Product Description Accessor ies Important: Remote modification of F ACP programmin g requires that the panel be enabled for remote downlo ad (refer to th e DACT -UD2 m anual). Remote interrogation o f panel prog ramming, history logs, detector status, etc.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 23 Accessories Product Description 1.8.6 New ANN- BUS Annunciators/Devices The legacy ACS annunciators may not be used if new ANN-BUS annunciators are b eing used due to incompatible serial communicat ion protocols.
24 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Product Description Accessor ies capacitance is the limiting factor . These cases are ma rked in the chart with an asterisk (*). Maxi- mum length can never be more than 6,000 feet (1 ,800 m), rega rdless of gauge used.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 25 Accessories Product Description The total worst case current is calculated as follows: Using this value an d referring to the W iring Distance T able 1.
26 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Product Description Accessor ies Powering ANN-BUS Devices fr om Auxiliary Power Supply Figure 1.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 27 Accessories Product Description ANN-80 Remote Fire Annunciator The ANN-80(-W) Annunciator is a comp act, 80 character , backlit LCD remote fire annunciator .
28 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Product Description Accessor ies Mounting TheANN-80 can be surface or semi-f lush mounted to a single, double or 4” square electrical box.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 29 Accessories Product Description Wiring ANN-80 to FACP The following steps can be used as a guide to wi re the annunciator . Make certain all power has been removed from the F ACP prio r to annunciator installat ion.
30 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Product Description Accessor ies The following table shows the ANN-8 0 connections to the F ACP Programming Following installatio n and wiring of the ANN-80 LCD annunciator to the F AC P , the annunciator must added to the system via F ACP programming.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 31 Accessories Product Description 4. Select the address and configuration options for the ANN -S/PG module as described in the Programming section of this manual (ref er to “ANN-BUS Options” on page 121).
32 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Product Description Accessor ies ANN-I/O LED Driver Module* The ANN-I/O is an LED driver modul e that can be used in a wide variety of applications, incl uding as an interface with most customized graphic annunc iators.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 33 Accessories Product Description Specifications • Max. ANN-BUS V oltage: 2 8 VDC • Max. Current: • Alarm: 20 0 mA • Standby: 35 mA • .
34 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Product Description Accessor ies ANN-LED Annunciator Module* The ANN-LED and ANN-RLED annunciator modules provide LED annunciation of general sys- tem faults and input zones/po ints when used with a comp atible F ACP .
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 35 Accessories Product Description *In Canada, the color red must be used to indicat e active alarm inputs. Y e llow indicates su pervi- sory , burglary or trouble sig nals. Green indicat es the presence of power or an activated output.
36 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Product Description Accessor ies ANN-LED Board Layout and Connection to FACP Figure 1 .13 illustrates the ANN-LED b oard showing location s of screw terminals for connection to the F ACP and the DIP switches for selecting the ANN-BUS ID number .
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 37 Accessories Product Description Mounting/Installat ion The ANN-RL Y relay module can be mounted inside th e F ACP main circuit bo ard chassis or inside the ROME Series enclosure.
38 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Product Description Accessor ies ANN-RLY Board Layout and Connection t o FACP Figure 1 .15 illustrates the ANN-RL Y board showing location s of screw terminals for connection to the F ACP and the DIP switches for selecting the ANN-BUS ID number .
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 39 Accessories Product Description Examples: • F ACP Input programm ed to Zone 33 goes into alarm, the programmed message for Zone 33 [Message 1, 2, 3, 4 or 5] will play over the ACC-25/50ZS Series output circuit 1 which corresponds to F ACP Zone 33.
40 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Product Description Getting Started 1.8.7 Legacy ACS Annunciators The legacy ACS annunciators may not be used if new ANN-BUS annunciators are b eing used due to incompatible serial communicat ion protocols.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 41 Getting Started Product Description • Enter Autoprogramming (refer to “Autoprogram” on page 66). • Resolve Progr amming Conflicts. • Go to Point Program to Enter Specific Da ta (re fer to “Point Program” on page 6 7).
42 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Section 2: Inst allation The cabinet may be either semi-flush or surface mounted. The cabinet mounts using key slots and two 0.250” (6.35 mm ) diameter holes located in the backbox. The key slots are located at the top of the backbox and t he two securing ho les at the bottom.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 43 Mounting Installati on 1 2 6 # 1 st EVENT ABC DEF JKL MNO TUV WXY -/. CLR 9 ESC ENTER RECALL ACK/STEP ALARM SILENCE DRILL HOLD 2 S EC RESET MODE Figure 2.1 FACP Main Circ uit Board Installation 9600lsbrdinbox.
44 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Installation Mounting 3.37 cm 1.325“ 3.37 cm 4.13 cm 4.1 cm 1.625“ (4.128 cm) 1.625“ 16.65“ (42.29 cm) 2.00“ 4.128 cm 1.00“ (2.54 cm) 1.30“ 3.30 cm 13.23 cm 5.207“ 12.00“ (30.48 cm) 2.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 45 Mounting Installati on = 19.26" (48.92 cm) = 19.0" (48.26 cm) 5.325" (13.526 cm) = 16.821" (42.73 cm) = 16.65" (42.29 cm) = 5.207" (13.23 cm) Figure 2.3 FACP Ca binet Dimensions 9600cabnew.
46 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Installation Power 2.2 Power 2.2.1 AC Power and Ea rth Ground Connection Primary power required for the F ACP is 120 V AC, 60 Hz, 3.0 amp s for the MS-9600LS(C) and MS-9600UDLS or 240 V AC, 50 Hz, 1.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 47 Relays Installation 2.2.3 Special Application DC Power Output Connection All Special Application DC pow er outputs are power-limited. 2.3 Relays The F ACP pr ovides two pro grammable Form -C relays and one fixed fail- safe Form-C trou ble relay , all with contacts rated for 2.
48 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Installation Notification Appl iance Circuits The following sections describe the configuratio n and wiring of Style Y and S tyle Z Notification Appliance Circuits on the F ACP main circuit board.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 49 Notification Appliance Circ uits Installation 2.4.2 St yle Y (Class B) NAC Wiring 2.4.3 St yle Z (Class A) NAC Wiring Figure 2.7 NAC Style Y (Class B) Wiring 4 Style Y (Class B) Notification Applia nce Circuits, supervised and power-limit ed - 4.
50 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Installation Power-limited Wiring Requirements 2.5 Power-limited Wiring Requirement s Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 51 Optional Modules and Devices Installation 2.6 Optional Modules and Devices FACP Keypad/Display Re moval Removal of the keypad/display is normally not necessary .
52 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Installation Optional Modules and Devices 2.6.1 DACT -UD2 Inst allation The DACT -UD2 Digital Alarm Communicator/Transmitter , wh ich is supplied standard with the MS-9600UDLS/E, transmits system status to UL listed Centra l S tation receivers via the public switched telephone network.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 53 Optional Modules and Devices Installation The following steps must be followed when installin g the DACT -UD2 module: 1. Remove all power (AC and DC) from F A CP before proceedin g with installation 2.
54 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Installation Optional Modules and Devices 8. Reinstall Keypad/Display on the main circuit board by positioning the unit over the appropriate standoffs and securing with screws which were loosened in step 3 9.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 55 Optional Modules and Devices Installation 2.6.2 4XTMF T ransmitter Module Installation The 4XTMF provides a supervised output for a local energy municipal box transmitter in addition to alarm and trouble reverse polarity .
56 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Installation Optional Modules and Devices Remote S tation Service (NFP A 72 Remote S tatio n Fir e Alarm Systems) - Intended for connec- tion to .
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 57 Optional Modules and Devices Installation 8. When the installation h as been complete, enable th e 4XTMF module by sliding the disconnect switch to the left 9. T est system for proper operation 2.6.
58 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Installation Optional Modules and Devices 3. Carefully plug connector J3 on the SLC-2LS module into conn ector J3 on the MS-9600LS/MS-9600UDLS main circu it board, being careful not to bend any pin s 4.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 59 Optional Modules and Devices Installation installation details. Refer to “ANN-BUS Op tions” on page 121 for programming information. Installation Remote printers and PCs require separate primary power .
60 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Installation Optional Modules and Devices Legacy ACM Series Annunciators ACM and AFM Series Annun ciators provide visu al indications of F ACP status i n remote location s. Refer to the appropriat e annunciator manual for info rmation on instal lation, wiring and operation.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 61 Section 3: Programming 3.1 Programming Dat a Entry Programming can be accomplished using the F ACP keypad or by connecti ng an optional standard computer keyboard. The keyb oard can be connected to the PS-2 connector J7 on the cont rol panel main circuit board.
62 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Programming User Programming 3.2 User Programming The F ACP is completely field programmable and requires no special software skills. While pr o- gramming the F A CP , the fir e pr otection capabilities of the control panel ar e enabled.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 63 Initial Power-u p Programming Exit Programming or Read Status The programmer can exit Read Status or Programming mode by repeatedly pressing the keypad ESC (Escape) key until the display reads System Al l Normal.
64 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Programming Programmi ng and Passw ords Change” on page 135. If an invalid passw ord is entered, the blinking curso r will return to the first password character position. T o exit Programming or Read Status mode at any time, press the ESC (Escape) key repeatedly .
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 65 Master Programming Level Programming 3.6 Master Programming Level When the Master Program Level password is entere d, the control panel will en ter user Program - ming mode.
66 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Programming Master Programming Level 3.6.1 Autoprogram Pressing 1 while viewing Programmi ng Screen #1, will select the Autoprogram option, which prompts the control panel to poll all dev ices instal led on one or both SLC loops.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 67 Master Programming Level Programming 3.6.2 Point Program The Point Program option allow s the programmer to add a new addressabl e device to an SLC loop, delete an existing device from a lo op or change the programm ing for an existing device.
68 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Programming Master Programming Level A flashing cursor will appear in th e position of the first asterisk to the left.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 69 Master Programming Level Programming Edit Detector The programmer can change a detectors existing or factory defaul t programming by pressing 3 in the Detector Screen. The following screen will be displayed: A flashing cursor will appear in th e position of the first asterisk to the left.
70 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Programming Master Programming Level If the selected address has been added to pr ogramming and a detector (such as a phot oelectric detector) wi.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 71 Master Programming Level Programming The following examples show the editing of a photoelect ric smoke detector with address 017, located on the first SLC loop: Enable/Disable Detector T o Enable or Disable the detector , press the 1 key while viewing the Edit Detector Screen #2.
72 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Programming Master Programming Level Pressing the down arrow key will display additional det ector types as indicated in the following table: While viewing any Detector T ype sc reen, select the type of detector being programmed by pressing the corresponding keyboard numb er key .
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 73 Master Programming Level Programming • Program the des ired zone or zones to be ac tivated by this detector , in this example Z001 • Program a.
74 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Programming Master Programming Level Note that Z** represents t he Zone Number(s) co rresponding to this device. The factory default for an unprogrammed device is Z00 for general alarm zone . A flashing cursor w ill appear on the first 0 to the left.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 75 Master Programming Level Programming Pressing 1 while viewing the Noun/ Adjective Screen will cause the follow ing screen(s) to be dis- played. Note that the keyboard down arrow key must be pressed to see all the Adjective screens.
76 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Programming Master Programming Level Pressing 2 while viewing the Noun/ Adjective Screen will cause the follow ing screen(s) to be dis- played. Note that the keyboard down arrow key must be pressed to see all the Noun screens.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 77 Master Programming Level Programming Pressing 3 or 4 while viewing the Noun/Adjective Screen w ill display screens similar to the previ- ous Adjective and Noun Screens.
78 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Programming Master Programming Level 3. W ith the cursor on the last letter of the No un field, press the zero ke y again to increment the room number to 305. 4. Press the right arrow key to advance the zone field.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 79 Master Programming Level Programming Pressing 1 for Control Modu le or 2 for Monitor Module will cause the follo wing screen to be dis- played: The programmer can continue adding modul es by pressing the ESC or left arro w key which w ill return the display to the Add Module Screen #1.
80 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Programming Master Programming Level A flashing cursor will appear in th e position of the first asterisk to the left.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 81 Master Programming Level Programming If the selected address corresponds to a monitor module, a screen displayi ng info rmation about t he module .
82 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Programming Master Programming Level Type Monitor The F ACP response to the activati on of a user-defined type is the sam e as most previous standard types in the list, thus allowing a variety of user-defined types and responses.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 83 Master Programming Level Programming Monitor module type selection will affect the function of the point as follows: Monitor T yp e Action When Ac.
84 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Programming Master Programming Level Pre-signal T o enable the Pre-si gnal feature, press 1 while viewing Edit Monitor Screen #3 until the display reads Pr e-signal Y es . Each press of t he 1 key will cause the display to toggle between Pre-signal Ye s and Pr e-signal No .
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 85 Master Programming Level Programming Pressing 1 while viewing the Noun/ Adjective Screen will cause the follow ing screen(s) to be dis- played. Note that the keyboard down arrow key must be pressed to see all the Adjective screens.
86 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Programming Master Programming Level Pressing 2 while viewing the Noun/ Adjective Screen will cause the follow ing screen(s) to be dis- played. Note that the keyboard down arrow key must be pressed to see all the Noun screens.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 87 Master Programming Level Programming Description The Description selection allows th e programmer to enter additional information about the mo nitor module currently being program med. This information will be displayed as part of the device label on the LCD display .
88 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Programming Master Programming Level Edit Module Screen for Contro l Modules The programmer can change a module’ s existing or factory default programming by pressing 3 in the Modules Screen.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 89 Master Programming Level Programming T o change the programming fo r the di splayed module, press the keyboard do wn arrow key to view the following Edit Contro l screens: Enable/Disable Module T o Enable or Disable the control module, press the 1 key while viewing the Edit Control Screen #2.
90 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Programming Master Programming Level The following table contains control module type codes and th eir functions which are displayed in the Contr.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 91 Master Programming Level Programming remaining zones can be left blank or programm ed as general alarm zones Z00. When all desired changes have been made, press the Enter key to store the zone assi gnments.
92 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Programming Master Programming Level Pressing 1 while viewing the Noun/ Adjective Screen will cause the follow ing screen(s) to be dis- played. Note that the keyboard down arrow key must be pressed to see all the Adjective screens.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 93 Master Programming Level Programming Pressing 2 while viewing the Noun/ Adjective Screen will cause the follow ing screen(s) to be dis- played. Note that the keyboard down arrow key must be pressed to see all the Noun screens.
94 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Programming Master Programming Level Description The Description selection allows the programmer to enter additi onal information about the control module currently being program med. This information will be displayed as part of the device label on the display .
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 95 Master Programming Level Programming 3.6.3 Zone Setup Pressing 3 while viewing Programming Screen #1 will access the Zone Setup screens as illu st.
96 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Programming Master Programming Level Disable Pressing 2 for Disable, while view ing Zone Setup Screen #1, will display the follo wing screen: This screen allows the programmer to disable zones, one at a time.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 97 Master Programming Level Programming Zones Installed Pressing 1 for Zones Installed, while viewing Zone Setup Screen #2, will displa y a screen similar to the following: This display will show all o f the zones that have been programm ed into the control panel.
98 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Programming Master Programming Level Zone Type Zone T ypes must be p rogrammed only if a DACT , programmed for zo ne reporting, is i nstalled on the control panel.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 99 Master Programming Level Programming Zones Available Pressing 2 while viewing Zone Setup Screen #3 will display th e following screen: The display will show all of the zones that are s til l available for programming.
100 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Programming Master Programming Level Loop Protocol Loop Protocol refers to the SLC loop mode of operation. Refer to “Wire Requirements” on page 196 for wire specifications based upon SLC protocol.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 101 Master Programming Level Programming Pressing 2 for System Setup, while viewing Prog ramming Screen #2, will cause the following screens to be di.
102 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Programming Master Programming Level Pressing 1 while viewing the Banner Screen will select the blank factory default banner sett ing and display the following screen: Pressing the Enter key will store this selection in nonvolatile m emory and return the display to the Banner Screen.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 103 Master Programming Level Programming Time-Date The control panel time and date can be changed by pressing 3 while viewing the System Setup Screen #1. The following screen will be displ ayed: Time T o change the time, press 1 while viewing the T ime-Date Screen.
104 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Programming Master Programming Level digit is entered. After the last year digi t is ente red, the display will return to the Time-Date Screen which will show the new date entry . If an error is made while entering a digit, press the CLR key to delete the entire entr y and beginning again.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 105 Master Programming Level Programming Timers T imer delays for P AS, Pre-signal and waterflow activation can be programm ed by pressing 1 while viewing System Setup Screen #2.
106 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Programming Master Programming Level A flashing cursor is positio ned in the lower left co rner of the display .
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 107 Master Programming Level Programming Pressing 2 while viewing AC Loss Delay Screen #1 will display the followin g screen: A flashing cursor will appear in th e lower left corner of the display . The factory default setting is 02 hours.
108 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Programming Master Programming Level The following screens will be displayed for eith er selection: Enabled Pressing 1 while viewing NAC Scr een #1 will cause the display to change t o Enabled No .
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 109 Master Programming Level Programming Type The main circuit board N AC type can be program med by pressing 2 while viewi ng NAC Screen #1.
110 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Programming Master Programming Level Auto Silence The Auto Silence feature, when en abled, automatically silences a l l main circuit board silenceable notification appliances after a programmed length of time.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 111 Master Programming Level Programming The programmer can select the not ification appliance output by pressing the number corresponding to the desired output.
112 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Programming Master Programming Level Note that Z** represents the Zone Number(s) corresponding to the selected NAC. The factory default for an unprogrammed device is Z0 0 for general alarm zone. A flashing cursor will appear on the first 0 to the left.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 113 Master Programming Level Programming T o program Relay 1 or Relay 3, press the number corresponding to the selected relay . Note that Relay 2 is fixed as a T rouble relay . Selecting Relay 2 will have no effect on its programming.
114 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Programming Master Programming Level The Canadian Options configures the F ACP with the following as required by Canada: • The following monit.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 115 Master Programming Level Programming 3.6.7 History The History option allows an author ized user to view or erase even ts which have occurred in the control panel.
116 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Programming Master Programming Level 3.6.8 W alktest W alktest allows an individual to test the fire alarm system without the necessity to reset the control panel after each device activation.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 117 Master Programming Level Programming Pressing 2 for Vi e w P o i n t s while viewing the Unit In W alktest screen will display one of th e follow- ing screens: If the system has no points installed, the fi rst scr een will be displayed.
118 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Programming Master Programming Level Pressing 3 while viewing Programmi ng Screen #3 will display the followin g screen: Note that PR4800 in the display indicates that a superv ised printer , configured for 4800 baud, has been previously programmed into the system.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 119 Master Programming Level Programming ACS Options Pressing 2 for ACS Options while viewing th e Annunciators screen, will display the following screen: Pressing 1 while viewing the ACS Op tions screen will cause the display to to ggle between ACS Enabled Y es and ACS Enabled No .
120 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Programming Master Programming Level Annunciator addressing is specific to the F ACP control panel. The following table describes the annunciator addresses and the corresponding addressa ble devices that will be annunciated at each annunciator address.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 121 Master Programming Level Programming ANN-BUS Options Pressing 3 for ANN-BUS Options , while viewing the Ann unciators screen, will cause the following screens to be displayed:.
122 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Programming Master Programming Level Pressing 1 for Ty p e will display the following screens: Press the number correspondin g to the m odule type that i s installed with the selected address.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 123 Master Programming Level Programming ANN-I/O Options Pressing 2 for Module Options while view ing ANN-BUS Address Screen when th e ANN-I/O option.
124 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Programming Master Programming Level 4 Trouble Zone 33 Zone 73 5 Alarm Silenced Zone 3 4 Zone 74 6 Earth Fault Zone 35 Zone 75 7 Battery Fault Z.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 125 Master Programming Level Programming ANN-I/O Point Op tion If Point is selected as the module option, the firs t ten LE Ds on the first ANN-I/O module will display the system status i nformation.
126 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Programming Master Programming Level ANN-LED Options Pressing 2 for Module Options while view ing ANN-BUS Address Screen when th e ANN-LED optio.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 127 Master Programming Level Programming ANN-LED Zone Option - Alarm Only (for use with ANN-RLED module) If Zone is selected as the m odule option, and the mo dule is programmed to annunci ate alarms only , the first ten LEDs on the first ANN-LED module will disp lay the system status informati on.
128 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Programming Master Programming Level ANN-LED Zone Option - Alarm, Trouble and Supervisory If Zone is selected as the modul e option, and the mod.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 129 Master Programming Level Programming ANN-LED Point Option - Al arm Only (for use with ANN-RLED module) If Point is selected as the modul e option.
130 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Programming Master Programming Level ANN-LED Point Option - Alarm, Trouble an d Supervisory If Point is selected as the module option, and the m.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 131 Master Programming Level Programming ANN-RLY Optio ns Pressing 2 for Module Options wh ile viewing ANN-BUS Address Screen w hen the ANN-RL Y opti.
132 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Programming Master Programming Level ANN-S/PG (Print) Op tions The Print option allow s the programmer t o configure the optional printer .
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 133 Master Programming Level Programming ANN-80 Options Pressing 2 while viewing ANN-B US screen #2 will display the following screen: The Piezo Enabl e option allows the programmer to select whether the piezo sounder on any installed ANN-80 module will ever sou nd.
134 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Programming Master Programming Level On Board DACT The Onboard DACT (Digital Al arm Communicator/Transmitter) provides communication to a Central Station. Pressing 2 while viewing the Option Module Screen will allow prog ramming of the Onboard DACT .
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 135 Master Programming Level Programming 3.6.10 Password Change The factory set passwords, which ha ve been programmed into the control panel, can be changed by selecting the Password Change option.
136 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Programming Master Programming Level 3.6.1 1 Clear Program Pressing 2 while viewing Programmi ng Screen #4, will select the Clear Program option.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 137 Master Programming Level Programming 3.6.12 Program Check The Program Check feature allows the programme r to view the zones which have been pro-.
138 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Programming Maintenance Programming Level Pressing 3 while viewing Program Check sc reen will cause a screen sim ilar to the following to be dis.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 139 Maintenance Programming Level Programming Note that in the preceding screens, an arrow ap pears to inform the prog rammer that additional options can be viewed by pressing the keypad down arrow key , as shown in the following screen.
140 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Programming Maintenance Programming Level A flashing cursor will appear in the bottom left corn er of the display , prompting for the three digit device address.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 141 Maintenance Programming Level Programming Pressing 2 while viewing the History Screen will cause th e following screen to be displayed: Pressing 1 while viewing the Erase History Screen will cause the message ERASING HISTOR Y , PLEASE W AIT to be displayed.
142 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Programming Maintenance Programming Level Pressing 2 while viewing the Program Check screen wi ll display a screen similar to the followi ng: Th.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 143 Maintenance Programming Level Programming 3.7.5 System T o program the ti me and date in to the control panel, press 2 while viewing Maintenance Screen #2.
144 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Programming Maintenance Programming Level T o change the date, press 2 while viewing the T ime and Date Scre en. The following screen will be displayed: A flashing cursor will appear on the left side of the display .
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 145 Maintenance Programming Level Programming Pressing 1 while viewing Zone Setup screen #1 will display the following screen: A flashing cursor appears to the right of the Z. T o enable a zone , enter the two digit zon e number (00 - 99).
146 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Programming Maintenance Programming Level nected to the control module can be used to indicate a P AS condition in the control panel. Do not assign Zone 97 to a Notification App liance Cir cuit when using this zon e to indicate a P AS cond i- tion.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 147 Maintenance Programming Level Programming Zones Disabled Pressing 3 for Zones Disabled, while vi ewing Zone Setup Screen #2, will disp lay a screen similar to the following: This display will show all of the zones that are disabl ed in the control panel.
148 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Programming Maintenance Programming Level Zone types can be changed by pressing the keyp ad number key corresponding to the zo ne in each Zones Installed Screen. A vailable zone type s will be displayed in the resultant scree ns.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 149 Maintenance Programming Level Programming Zone Message Pressing 3 while viewing Zone Setup Screen #3 will display th e following screen: Pressing the down arrow key will display addi tional sc reens for Zones up to Z9 9.
150 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Section 4: Operating Instructions 4.1 Panel Control Buttons 4.1.1 Acknowledge/Step The first press of the Acknowledge/Step key silences the piezo sounder , changes flashing LEDs to steady and also changes the status field on the LCD display from capital letters to small letters.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 151 Normal Operation Operating Instructions Supervisory This is a yellow LED that flashes when one or more supervisory conditions occur , such as a sprin- kler valve tamper condition. It illuminates steady when the Acknowledge/Step or Alarm Silence key is pressed.
152 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Operating Instructions Trouble Operation 4.4 T rouble Operation W ith no alarms in the system, the detect ion of a trouble will cause the follow.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 153 Alarm Operation Operating Instructions INV ID - indicating that an incorrect device c ode (T ype ID) has been programmed for an installed dev.
154 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Operating Instructions Supervisory Operation Note that the device type, which in this example is PULL ST A TION , can be any other programma- ble alarm type.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 155 Process Monitor Operation Operating Instructions A typical Supervisory event would be di splayed as illustrated in the followin g: Note that, like alarms, supe rvis ory signals lat ch (except when programmed for supervisory auto re- settable) and can be assigned to software zones.
156 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Operating Instructions Medical Alert Condition Operation 4.9 Medical Alert Condition Operation Medical Alert Co ndition operat ion will initi at.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 157 Time Functions: Real-Time Clock Operating Instructions Type Code Supervisio n The F ACP monitors addressable hardware device code s at slow intervals. Mismatch of any type code, compared to the system pr ogram, will cause a device trouble.
158 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Operating Instructions Presignal 4.18 Presignal Presignal option programs an ini tiating device to de la y the activation of NACs and/or control mod- ules while allowing visual verification by a person.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 159 Special System Timers Operating Instructions • pressing the Alarm Silence or Acknowledge/Step key will start a timer which inhi bits output act.
160 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Operating Instructions Walktest all appropriate outputs and indicat e the alarm condition at the F ACP .
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 161 Read Status Operating Instructions Read Status Entry When the operator presses the control panel Enter key , the LCD will display the fo llowing:.
162 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Operating Instructions Read Status 4.22.1 System Point Pressing 1 while viewing Read Status Screen #1 will cau se the following screen to be displayed: The operator selects the loop containing the device to be read by pressing 1 for Loop 1 or 2 for Loop 2.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 163 Read Status Operating Instructions Pressing the down arrow key , while viewing the sc reen shown on the previous page, wi ll allow the operator t.
164 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Operating Instructions Read Status 4.22.3 Power Pressing 3 while viewing Read Status Screen #1 will display the following screens: A real-time display of control panel voltag es can be used to determine if system problems exist.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 165 Read Status Operating Instructions 4.22.4 T rouble Reminder Pressing 1 while viewing Read Status Screen #2 will display the followin g screen: The screen indicates whether the T rouble Reminder feature is On or Of f.
166 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Operating Instructions Read Status 4.22.6 NAC Pressing 3 while viewing Read Status Screen #2 will display the followin g screen: Note that 3=NAC 3 and 4=NAC 4 will only be displayed if the NACKEY NAC opti on card is installed, in JP8 of the main circuit board, for Class B operation.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 167 Read Status Operating Instructions 4.22.8 Program Check Pressing 2 while viewing Read Status Screen #3 will cau se a screen similar to the follow.
168 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Operating Instructions Read Status The Annunciator Screen indicates if T erminal mode options are enabled or disabled.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 169 Read Status Operating Instructions 4.22.1 1 Phone Line Pressing 2 while viewing Read Status Screen #4 will display the followin g screen: The second and third lines of this screen indicate that both the Primary and Second ary phone lines have been configured for touchtone dialing o peration.
170 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Operating Instructions Read Status 4.22.13 Service T erminal Pressing 1 while viewing Read Status Screen #5 will display the following screens: The Ring Count is displayed in the Service T erminal Screen.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 171 Read Status Operating Instructions 4.22.15 Print T o print program d ata or control p anel status, press 3 while viewing Read Status Screen #5.
172 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Operating Instructions Read Status Drift Compensation Drift compensation uses software algorithms that identify and comp ensate for long-term changes in the data readings from each addres sable smoke detector .
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 173 Read Status Operating Instructions 4.22.16 Time-Date The operator can view the daylight savings time and the month and week when daylight savings time will begin and end.
174 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Section 5: Power Supply Calculations 5.1 Overview This section contains instructions and tables fo r calculating power supply currents in alarm and standby conditions. This is a four-step process, consisting of the following: 1.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 175 Calculating the System Current Draw Power Supply Calculations • ‘Secondary’ refers to the control panel’ s backup batteries • All currents are given in amperes (A). T able 5.2 shows how to convert milliamperes and microamperes to full amperes.
176 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Power Supply Calculations Calculating the System Current Draw T able 5.3 contains columns for cal culating current draws. For each column, calculate the current and enter the total (in amperes) in the bo ttom row .
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 177 Calculating the Battery Size Power Supply Calculations 5.4 Calculating the Battery Size Use T able 5.4 to calculate the total Standby and Alar m load in ampere hours (AH). This total load determines the battery size (in AH), required to support the control panel under the loss of AC power .
178 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Appendix A: Sof tware Zones A.1 Correlations Setup and configuration of an a ddressable system is dif ferent th an a conventional system. In a conventional system, assignment of input devices (s moke detectors, pull stations, heat detectors, etc.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 179 Correlations Software Zones Correlation of Input and Output Zones The zone correlations which are shown graphically above are also presented in T able A.
180 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Software Zones Correlations DETECTOR ZONE ASSIGNMENT Address Device Ty p e Zone Number ADJ/NOUN Add ress Device Ty p e Zone Number ADJ/NOUN 01 SD350 1 FIRST HALL 51 02 SD350 1 ELEV .
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 181 Correlations Software Zones MONITOR/CONTROL MODULE ZONE ASSIGNMENT Address D evice T ype Zone Number ADJ/NOUN Address Device Ty p e Zone Number A.
182 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Software Zones Correlations DETECTOR ZONE ASSIGNMENT Address Device Ty p e Zone Number ADJ/NOUN Address Device Ty p e Zone Number ADJ/NOUN 01 51.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 183 Correlations Software Zones DETECTOR ZONE ASSIGNMENT Address Device Ty p e Zone Number ADJ/NOUN Address Device Ty p e Zone Number ADJ/NOUN 101 15.
184 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Software Zones Correlations MONITOR/CONTROL MODULE ZONE ASSIGNMENT Address Device Ty p e Zone Number ADJ/NOUN Address Device Ty p e Zone Number .
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 185 Correlations Software Zones MONITOR/CONTROL MODULE ZONE ASSIGNMENT Address Device Ty p e Zone Number ADJ/NOUN Address D evice Ty p e Zone Number .
186 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Appendix B: Default Programming The following table p rovides a list of the p rogramming option s and their factory default settings.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 187 Appendix C: NFP A S t andard-S pecific Requirement s The F ACP has been designed for use in commercial , industri al and institutional appli cations and meets the requirements for s erv ice under the National Fire Protection Association (NFP A) Standards outlined in this Appendix.
188 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 NFPA Standard-Spe cific Requirements NFPA Signaling Syst ems for Central Station Service (Pro tected Premises Unit)/Remote Station The following figure illustrat es an example of Central Station/Remote Station Reporting using a 41 1UDAC.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 189 NFPA Standard-S pe cific Requirements The following figure illustrat es an example of Central Station/Remote Station Reporting using a 41 1UD. The relay contacts from the F ACP may be used to trip any dialer UL listed for Central Station/Remote Station Reporting Services.
190 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 NFPA Standard-Spe cific Requirements NFPA 72 Auxiliary Fire Alarm System All connections are power -l imited and supervised. Th is application is not suitable for separate transmission of sprinkler supervisory or trouble conditions.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 191 NFPA Standard-S pe cific Requirements NFPA 72 Remote Station Protective Signaling Syste m Notes: 1. Cut Jumper JP6 on the F ACP main circuit board to supervise placement of the 4XTMF module. 2. Refer to “4XTMF Transmitter Module Installation” on page 55 for detailed in formation.
192 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 NFPA Standard-Spe cific Requirements NFPA 72 Proprietary Protective Signaling Sys tems Figure C.5 Proprietary Protective Signalin g System Form-C relay contact programmed to activate on Supervisory condition.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 193 Central Station/Remote St ation Transmitte r: Connectio n to FACP Dry Contacts NFPA Standard-Spe cific Requirements C.
194 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 NFPA Standard-Spe cific Requirements MBT-1 Municipal Box Trip - Silenceable C.2 MBT -1 Municip al Box T rip - Silenceable The following figure illustrat es the connection of the MBT -1 (Municipal Box T rip) between the F ACP and a Local Energy Municipal Box.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 195 Appendix D: F ACP with Keltron The following figure illustrat es the connections between the F ACP and Keltron Receiver/T ransmitter .
196 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Appendix E: Wire Requirement s T - tapping of the SLC loop wiring is allowed for 2-wire (Style 4) configurations. The total resistance of any branch cannot exceed 40 ohms. The total wire length of all branches cannot exceed 10,000 feet (3,000 m).
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 197 NAC Wiring Wire Requirements E.1 NAC Wiring The following table lists NAC wiring requ irements for the F ACP . Notes: 1. Calculations are based on Direct-Current Resistance data for uncoated copper wire , per National Electrical Code (2005 Edition) T able 8, Conductor Properties.
198 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Appendix F: HV AC Control The F ACP can be programmed to shu t down a building’ s HV AC fans in the event of a fire. The fans cannot be restarted until the fire alarm conditi on has been cleared and the F ACP has been reset to a normal (non-alarm) condition.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 199 Monitor Module Operation HVAC Control F .2.2 HV AC OVRRIDE The HV AC OVRRID E type code can be assigned to any addressable moni tor module for the purpose of overriding or preventing the HV AC SH UTDN control mod ules from activating.
200 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 Appendix G: Canadian Application • The MS-9600LSC is supplied with the DP-9692 Dress Panel. • When installing and programmi ng the F ACP , t.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 201 Index Numerics 300 Series addressable devices 20 4XTMF module 190 , 191 coil resistance 55 current 55 installation 55 installation steps 56 see a.
202 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 D–E Index Classic Loop Interface Protocol 100 CLIP Mode see also Classic Loop Interface Protocol 100 Clock Format 104 Coded Operation 157 Codi.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 203 Index F–N F FACP see also Fire Alarm Control Panel 13 Features 13 Fire Alarm Control Panel see also FACP 13 Form-C relay 19 , 47 , 59 G general.
204 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 O–P Index synchronized 157 voltage drop 15 voltage, operating 15 wiring St yle 47 NAC enable/disable 108 NAC options 100 NAC type 109 NACKEY c.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 205 Index R–S program keys see also Key Panel 18 Programming 61 , 62 autoprogramming 62 exiting 63 factory default 186 Level 1 63 Level 2 63 manual.
206 MS-9600LS Series Manual — P/N 52646:B2 2/12/2 010 T–Z Index Phone Line 2 169 Supervisory 154 SUPERVISORY AR 113 sync programming 108 see also synchronization 112 synchronization 157 , 166 by m.
Manufacturer W arranties and Limit ation of Liability Manufacturer W arranties. Subject to the limitations set forth herein, Manufacturer warrants tha t the Products manufa ctured by it in its Northfo.
Wor ld Headquarters 1 Firelite Plac e Northford, CT 06472- 1653 USA 203-484-7161 fax 203-484-71 18 www .firelite.com.
An important point after buying a device Honeywell MS-9600LSC (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Honeywell MS-9600LSC yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Honeywell MS-9600LSC - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Honeywell MS-9600LSC you will learn all the available features of the product, as well as information on its operation. The information that you get Honeywell MS-9600LSC will certainly help you make a decision on the purchase.
If you already are a holder of Honeywell MS-9600LSC, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Honeywell MS-9600LSC.
However, one of the most important roles played by the user manual is to help in solving problems with Honeywell MS-9600LSC. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Honeywell MS-9600LSC along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center