INSTALLATION INSTRUCTIONS Put Bar Code Here 95-7776-03 CE AND OTHER LOGOS WEB-700 WEB-700-O CP-700 APPLICATION The WEB-700 and CP-700 are compact, em bedded controller/ser ver platf or ms that allow integrated control and management of external devices ov er the Inter net.
WEB-700 WEB-700-O CP-700 95-7776—0 3 2 ABOUT THIS GUIDE This document covers the mounting and wirin g of the T r idium® WEB/CP-700 (T -700) controller . It assumes that you are an engineer , technician, or service person who is perf or ming control system installation.
WEB-700 WEB-700-O CP-700 3 95-7776—03 PR ODUCT DESCRIPTION The WEB/CP-700 controll er is a compac t embedded processor pl atform using on-board Flash memor y f or backup , in an ex pandable DIN-modular package.
WEB-700 WEB-700-O CP-700 95-7776—0 3 4 . Fig. 2. WEB/CP-700 main controller boar d and 2 option cards uninstalled. As a 7 ser ies controller , the WEB/CP-700 uses a Po werPC 440EPx processor , 1G B Flash storage, and 1 GB DDR-2 RAM. TCP/ IP access is via two standard Gigabit Ether net por ts.
WEB-700 WEB-700-O CP-700 5 95-7776—03 T echnical Specifications WEB/CP-700 PLATFORM • P o werPC 440Epx @ 667MHz processor (speed approximate due to spread spectrum clock). • 1GB on-board NAND Flash storage. • 1 GB DDR-2 333Mhz RAM (maximum Ja va Heap size 384MB).
WEB-700 WEB-700-O CP-700 95-7776—0 3 6 PREPARATION Unpack the WEB/CP-700 and inspect the package contents f or damaged or miss ing components. If damaged, notify the appropriate carrier at once and retur n any damaged components for immediate repair or replacement.
WEB-700 WEB-700-O CP-700 7 95-7776—03 WARNING A 120V a c or 240V ac cir cuit power s the NPB-PWR-UN-H power supply f or the controller . 15 Vdc input (DC only) to controller . Disconnect power bef ore in stallation or ser vicing to prevent electr ical shock or equipment damage.
WEB-700 WEB-700-O CP-700 95-7776—0 3 8 Ph ysical Mounting The follo wing information app lies about physically mounting the unit. • Y ou can mount the WEB/CP-700 in any orientation. It it not necessar y to remov e the cov er bef ore mounting. • Mounting on a 35mm wide DIN rail is recommended.
WEB-700 WEB-700-O CP-700 9 95-7776—03 T o mount on DIN rail 1. Securely install the DIN rail with at least two screws, near the tw o rail ends. 2. P osition the NPB-PWR- UN-H power supply module on the rail, t ilting to hook DIN rail tabs over one edge of the DIN rail (Fig.
WEB-700 WEB-700-O CP-700 95-7776—0 3 10 Boar d Lay o ut Fig. 5 shows the location of conn ectors, optio n slots, and other f eatures of th e main board in the WEB/CP-700 . F or side views o f communications por ts and other features, see Fig. 6, page 13.
WEB-700 WEB-700-O CP-700 11 95-7776—03 ABOUT EXPANSION OPTIONS The WEB/CP-700 provides for field-installab le expansion using these types of options: • Option card — Install on connectors inside the WEB/C P-700 base u nit. See About Option Ca rds, page 11.
WEB-700 WEB-700-O CP-700 95-7776—0 3 12 OPTION CARD COM PORT ASSIGNMENTS COM por t assignments for option cards installed in a WEB/CP-700 st ar t at COM5, with Slot 1 e valuated f irst, then Slot 2. (COM1 and COM2 are alwa ys assigned to the onboard RS-232 and RS-485 por ts, while COM3 and COM4 are reserved f or slots.
WEB-700 WEB-700-O CP-700 13 95-7776—03 WIRING DETAILS See Fig. 5, page 10 to locate connectors and ot h er components on the WEB/CP-700 controlle r . Make connections to the WEB/CP-700 in the follo wing order . 1. Install any option board (LON, RS-485, RS-232, etc.
WEB-700 WEB-700-O CP-700 95-7776—0 3 14 SERIAL There are two “RS” serial por ts on the W EB/CP-700 base board. Each has a UAR T capable of operation up to 115,200 b aud. At the bottom of the board (see Fig. 6, page 13) is an RS-232 por t using an DB-9 plug (male) connector .
WEB-700 WEB-700-O CP-700 15 95-7776—03 Fig. 7. Gr ounding and po wer wiring con nections to NPB-PWR-UN-H module. Po w e r W i r i n g There are two power options f or the WEB/ CP-700 controlle r : the NPB-PWR- UN-H power supply module (typical), or a NPB- WPM-US (W all Mount AC Adapter).
WEB-700 WEB-700-O CP-700 95-7776—0 3 16 Wiring NPB-PW R-UN-H input power and ear th ground. 1. Remove power from the A C circuit being wired to the NPB-PWR-UN-H—see pre vious . 2. Remov e the NPB-PWR-UN-H cov er . T o do this, press in the f our tabs on both ends of the unit, and lift the cov er off.
WEB-700 WEB-700-O CP-700 17 95-7776—03 Contact Inputs Three contact inputs (CIs) are availab le on a 6-position conn ector ne xt to the 2-posi tion external batter y conn ector . CIs are typically used to monitor nor mally-closed (N.C .) alar m contacts , if a vailab le on a UPS and/or the “door tamper” switch of an enclosure.
WEB-700 WEB-700-O CP-700 95-7776—0 3 18 EXTERNAL 12V BAC KUP BATTERY A 2-position connector provides suppor t for an e xternal 12V sealed lead -acid (SLA) type rechargable batter y . For more details, see About the Backup Batteries, page 20. Fig. 10.
WEB-700 WEB-700-O CP-700 19 95-7776—03 Wiring to Remote I/O Modules Wiring to remote I/O modules typically provides both 15Vdc power and 12V batter y backup , along with RS-485 communications to the module s.
WEB-700 WEB-700-O CP-700 95-7776—0 3 20 If after applying power , the ST A TUS LED goes out, or if t he BEA T LED comes on (steady) and sta ys lit longer than 2 minutes, contact your local distributor for technical a ssistance. See also “About LEDs” on page 21.
WEB-700 WEB-700-O CP-700 21 95-7776—03 ABOUT LEDS The WEB/CP-700 provides a number of LEDs on its main board. On ly the Status and Hear tbeat LEDs are visible on the cov er .
WEB-700 WEB-700-O CP-700 95-7776—0 3 22 Required NiMH Battery Maintenance Batter y life e xpectancy is a function of its discharge cycles (the number of discharges and their depth) and the ambient temperature of the batter y dur ing nor mal o peration.
WEB-700 WEB-700-O CP-700 23 95-7776—03 NO TE: Dispose of the use d NiMH batter y properly . 4. Unplug the NiMH batter y from the main board connector (see Fig. 12). 5. Using a 1/4" (6mm) nutdriver , unfasten and re tain the two k ep nuts that secure the m etal batter y brack et to the shield, and remov e the shield and batter y pack.
WEB-700 WEB-700-O CP-700 95-7776—0 3 24 Replacing the WEB/CP-700 NO TE: Before handling circuit boar ds, discharge an y accumulated static b y touching a nearby ear th ground.
WEB-700 WEB-700-O CP-700 25 95-7776—03 Returning a Defective Unit F or proper credit on an in-warranty unit, ship the def ective unit to T r idium within 30 days . NO TE: If the defective unit is under warranty , please fo llow return instructions pr ovided in this section.
WEB-700 WEB-700-O CP-700 95-7776—0 3 26 CER TIFICATIONS Federal Comm unications Commission (FCC) This equipment generates, uses, and can radiate radio frequency energy , and if not instal led and used in accordance with the instruction ma nual, ma y cause interference with radio communicati ons.
WEB-700 WEB-700-O CP-700 27 95-7776—03 T AB MOUNTING DIMENSIONS Measurements are in inches and (mm). DIN mounting is recommended ov er tab mounting. See Fig . 3, page 8. NO TE: Electronic and pr inted versions of this guide may not show the dimensio ns to scal e.
WEB-700 WEB-700-O CP-700 Automation and Control Solu tions Honeywell International Inc. 1985 Douglas Drive North Golden Valley, MN 55422 customer.honeywell.com ® U .S. Registe red T rademark © 2012 Hone ywell International I nc. 95-7776—03 M.S. Re v .
An important point after buying a device Honeywell CP-700 (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Honeywell CP-700 yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Honeywell CP-700 - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Honeywell CP-700 you will learn all the available features of the product, as well as information on its operation. The information that you get Honeywell CP-700 will certainly help you make a decision on the purchase.
If you already are a holder of Honeywell CP-700, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Honeywell CP-700.
However, one of the most important roles played by the user manual is to help in solving problems with Honeywell CP-700. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Honeywell CP-700 along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center